S.O 140.— In exercise of the powers conferred by Section 37 of the Jammu and Kashmir
Fire Force Act, 1967( Act No. XXII of 1967)(hereinafter referred to as the said Act) , read
with S.O. 3775 (E) of 2020, dated 23.10.2020, issued by Ministry of Home Affairs
(Department of Jammu,Kashmir and Ladakh Affairs), and in supersession of all previous
orders or notifications issued in this regard, the Administration of Union territory of Ladakh,
do hereby make the following rules, namely:⎯
1. Short title and Commencement. -
(1) These rules may be called the Ladakh Fire Prevention and Fire Safety Rules, 2025.
(2) They shall come into force from the date of their publication in the Official Gazette.
लद्दाख, 29 नवंबर, 2025
LADAKH, SATURDAY, NOVEMBER, 29, 2025
भारत सरकार
GOVERNMENT OF INDIA
एस.जी.-एल.डी.-अ.-01122025-1659
SG-LD-E-01122025-1659
LADAKH GAZETTE : EXTRAORDINARY 2
2. Definitions:
(1) In these rules, unless the context otherwise requires,⎯
(a) “Act” means the Jammu and Kashmir Fire Force Act, 1967;
(b) “Authorised member” means an officer not below the rank of Station Officer
authorised by Director Ladakh Fire and Rescue Service;
(c) “Director” means director as defined under Section 2(a) of the said Act;
(d) “Fire Safety Certificate” means the Fire Safety Certificate/ No Objection
Certificate (NOC) issued under these rules on completion of project after fire
safety inspection by the Director or Authorized member;
(e) “Fire Safety Recommendation” means fire safety guidelines issued by the
Director or Authorized member, at the stage of plan approval or before the
commencement of proposed project;
(f) “Fire Safety Renewal Certificate” means the Fire Safety Certificate/ NOC issued
under these rules on expiry of Fire Safety Certificate after fire safety inspection
by the Director or Authorized member;
(g) “Form” means the forms annexed to these rules;
(h) “Licensed Agency” means third party agency empanelled to conduct fire safety
audit under Rule 6 of these rules;
(i) “schedule” means the schedule(s) annexed to these Rules;
(2) The words and expressions used but not defined in these rules shall have the same
meanings as assigned to them in the Act and the Ladakh Building Bye-Laws, 2025.
3. Fire Prevention and Fire Safety measures required for various groups of
buildings. -
The fire protection systems, equipment, installations and fire safety measures required
for various types of buildings shall be as provided in Schedule-I of these rules.
The fire protection systems, equipment, installations and fire safety measures
provided in Schedule-I are only recommendatory for buildings which are exempted
from obtaining a fire safety certificate/ NOC under the Ladakh Building Bye-Laws,
2025 as amended from time to time.
All the fire protection systems, equipment and installations shall conform to the
relevant Indian Standards as prescribed by the Bureau of Indian Standards (BIS) from
time to time.
All matters relating to floor area ratio (FAR), side and rear setbacks, coverage,
height, and other aspects of building design and construction shall be governed by the
relevant provisions of the Ladakh Building Bye-Laws, 2025, or any other rules,
regulations, or orders notified by the Administration in this regard from time to time.
LADAKH GAZETTE : EXTRAORDINARY 3
4. Exceptions and Deviations. -
In case of practical difficulty or to avoid unnecessary hardship, without sacrificing
reasonable safety, the Director may consider exceptions from these rules for existing
buildings.
5. Issue of Fire safety Certificate/ NOC. Fire safety recommendations and Fire
Safety Renewal Certificate. -
(1) No Fire Safety Certificate/ NOC, Fire safety recommendation and Fire Safety
Renewal Certificate is required to be issued for buildings exempted from abstaining
Fire Safety Certificate/ NOC and Fire safety recommendation under the Ladakh
Building Bye-Laws, 2025, as amended from time to time.
(2) Fire Safety Certificate/ NOC, Fire safety recommendation and Fire Safety Renewal
Certificate, shall be issued on the basis of self-certification for buildings which are
classified as self-certification category under the Ladakh Building Bye-Laws, 2025, as
amended from time to time.
(3) For building that requires to obtain Fire Safety Certificate/ NOC, Fire safety
recommendation and Fire Safety Renewal Certificate as per the provisions of Ladakh
Building Bye-Laws, 2025 Fire Safety Certificate/ NOC, Fire safety recommendation,
and Fire Safety Renewal Certificate may be issued based on certificate issued by a
Licenced Agency
(4) The validity of Fire Safety Certificate/ NOC, Fire safety recommendation, and Fire
Safety Renewal Certificate, shall be as provided in the Ladakh Building Bye-Laws,
2025, as amended from time to time.
(5) The Director shall frame guidelines governing the procedure for issue of Fire Safety
Certificate/ NOC, Fire safety recommendation and Fire Safety Renewal Certificate.
6. Power to grant license to act as a Licensed Agency. -
(1) The Director, Ladakh Fire and Rescue Service may grant any person or association of
persons, as he thinks fit, a licensee to act as a Licensed Agency for the purposes of
conducting Fire Audit and installation of Fire Prevention and Protection Systems.
(2) Any person intending to have or renew such license shall apply to the Director, Ladakh
Fire and Rescue Service in the prescribed form and in the prescribed manner.
(3) On receipt of such application, the Director, Fire and Rescue Service, may, after
holding such, inquiry as he deems fit, either grant the license in the prescribed form for
initial period of one year or renew the same for a like period or, for reasons to be
recorded in writing, by order refuse to grant or renew the license.
(4) Where the Director, Fire and Rescue Service, has reason to believe that any person to
whom a license has been granted and who failed to comply with the conditions of the
license or is unfit by reason of incompetency, misconduct or any other grave reasons,
Director, Fire and Rescue Service may, after giving to the person a reasonable
opportunity to show cause, for reasons to be recorded in writing, by order suspend or
cancel the license.
LADAKH GAZETTE : EXTRAORDINARY 4
7. Licensed Agency to carry out work of providing fire prevention and life safety
measures and Fire Auditing. -
(1) No person other than a Licensed Agency shall carry out the work of providing fire
prevention and life safety measures or performing such other related activities required
to be carried out in any place or building or part thereof.
(2) No Licensed Agency or any other person claiming to be such Licensed Agency shall
give an Audit certificate regarding the compliance of the fire prevention and life safety
measures or maintenance thereof in good repair and efficient condition, without there
being such compliance or maintenance.
8. Eligibility to act as licensed Agency. - No, person shall be eligible to apply for a grant
of license to act as Licensed Agency, and shall be granted a license to act as a Licensed
Agency, unless he possesses: -
(1) At least any of the following qualifications, namely: -
(a) A degree or advanced diploma or diploma in Fire Engineering awarded by the
National Fire Service College, Ministry of Home Affairs, Government of India; or
(b) Fellow of fire engineering of the Institution of Fire Engineer (U.K.) or M.I. Fire
(U.K.) or A.M.I.F.E, India, Graduate Examination of the Institution of Fire
Engineer (U.K.) or the Institution of Fire Engineers (India); or
(c) A Degree or Diploma in Mechanical, Electrical, Chemical, Civil Engineering or
Architecture from a recognized university, and experience in executing fire
prevention and fire protection systems as laid down in relevant codes or norms
issued by the Administration. The applicant must have executed work related to fire
prevention and fire protection systems during the three (3) years immediately
preceding the year of application.
(2) Holds a solvency certificate for an amount as may be specified by the Director, Ladakh
Fire and Rescue Service, with prior approval of the Administration;
(3) Has adequate machinery, tools and other requisite equipment in relation to fire
prevention and fire protection systems; and
(4) Has not been black-listed by any Department of the Administration or Organization or
any other State Government/ UT Administration or the Union Government.
9. Application to be made for Licensed Agency, manner of making it, and fees in
respect thereof. -
(1) Every application for License to act as Licensed Agency for the purpose shall be in
“Form-I”.
LADAKH GAZETTE : EXTRAORDINARY 5
(2) Such application may be submitted online or offline as may be prescribed by the
Director, Ladakh Fire and Rescue Service.
(3) Every such application shall be accompanied by the following: -
(a) Fee:
Class of
licenced
Agency
Minimum
solvency
certificate for
(Rupees in lakh)
Prescribed
limit for
execution of
the works as
per estimated
cost (Rupees
in lakhs)
Cost of annual works minimum executed
in the last three years (in lakhs)
Registration
(fee in Rs.)
Firefighting
system
installation
such as
hydrants,
sprinklers,
Pumping etc.,
Detection and
fire separation
system
Passive
protection
such as cable
protection
fire doors
etc.,
(1)
(2)
(3)
(4)
(5)
(6)
(7)
A
15.00
Unlimited
500.00
200.00
200.00
25000
B
10.00
1000.00
300.00
100.00
100.00
15000
C
5.00
600.00
200.00
50.00
50.00
5000
D
2.50
300.00
100.00
25.00
25.00
2500
(b) Documents as may be specified by the Director Ladakh Fire and Rescue Service and
which shall include the following, namely: -
(i) Solvency certificate for an appropriate amount as specified and shown above.
(ii) attested copy of deed of partnership and power of attorney or articles of
memorandum of association or affidavit on stamp paper in case the individual is
the sole proprietor of the firm:
(iii) Certificate from the charted accountant or registered income tax practitioner in
the prescribed form in case of private works;
(iv) Certificate regarding appointment of at least one person possessing any of the
qualifications specified in rule 8(1).
(v) attested passport size photographs of partners or directors or individual
proprietor.
(vi) Attested copy of GST Registration Certificate;
(vii) Affidavit on appropriate stamp paper stating that his or her firm is not been
black-listed by any Department of the Administration or Organization or any
other State Government/ UT Administration or the Union Government.
LADAKH GAZETTE : EXTRAORDINARY 6
10. License to act as Licensed Agency. - The License to act as a Licensed Agency shall be
granted in “Form-II” and shall be subject to the following conditions, namely: -
(1) The License shall be:
(a) non-transferable;
(b) valid for one year from the date of issue, unless suspended or cancelled earlier; and
(c) renewable, if so desired, before expiry of the License.
(2) Changes, if any, in respect of the
(a) Partners, Directors or Members,
(b) Address of the office of the Licensed Agency
shall be forthwith reported to the Authority issuing the License.
(3) The Licensed Agency shall always keep the work, open for inspection by the Director,
Ladakh Fire and Rescue Service or any fire officer authorized by the Director, Fire
Services.
11. Renewal of License. -
An application for renewal of a License granted under rule 10 shall also be made in
“Form-I” and shall be accompanied by a fee specified in rule 9 (3) (a) and also
documents as mentioned in rule 9 (3) (b).
12. Certificate to be issued by a Licensed Agency. –
(1) Certificate regarding the compliance of the fire prevention and fire safety measures, in
building plans:- A certificate regarding the compliance of the Fire prevention and Fire
safety measures in the building plans, including Site Plan Layout, Fire Fighting Plan,
Floor-wise Fire Fighting Plan, etc as required by or under the provisions of the applicable
rules, shall be issued by the Licenced Agency in “Form-III (A)” and submitted along with
the application for issuance of Provisional Fire Safety Certificate.
(2) Certificate regarding the compliance of the fire prevention and fire safety measures,
during the execution of work: A certificate regarding the compliance of the Fire
Prevention and Fire safety measures in a building or premise or occupancy, during the
execution of the work, as required by or under the provisions of the applicable rules, shall
be issued by the Licenced Agency in “Form-III (B)” and submit along with the
application for issuance of Fire Safety Certificate.
(3) Certificate regarding compliance of the fire prevention and fire safety measures by
proper maintenance of fire prevention and fire safety measures:-: A certificate regarding
the proper maintenance of fire prevention and fire safety measures in the building or
premise or occupancy, shall be issued by the Licenced Agency in “Form-III(C)” and
shall be submitted, along with application for the renewal of fire safety certificate, a self-
certificate by the owner of a building or premise or occupancy that has been issued with a
LADAKH GAZETTE : EXTRAORDINARY 7
Fire safety certificate and a minimum of fifteen (15) photos as evidence of different
stages of inspection, for the renewal of Fire Safety Certificate.
13. Notice to show cause why license be not suspended or cancelled. -
Where any person to whom the License has been granted fails to comply with the
conditions of the License or is unfit by reason of incompetency, misconduct or any other
grave reason, a notice to show cause as to why the License granted to him to act as
Licensed Agency should not be suspended or cancelled, will have to be given to such
person, by the Licensing authority in “Form-IV”.
14. Fire prevention and fire safety measures in temporary structures. -
The person desirous to erect temporary structures over an area of 1000 square meter or
more or where the congregation of persons is more than 2000 for the purpose of
observance of festivities, for holding commercial shows, melas, operas, temporary
cinemas etc. or premises where highly flammable or explosive materials are proposed to
be used shall apply along with the sketch map of proposed site with layout, means of
access, entrance, exit to Director of Fire and Rescue Service before 7 days of
construction for issue of Fire Safety Recommendation.
It shall be lawful for the Director or the authorised member or any other officer
authorized by Administration in this behalf to enter and inspect the structure or pandal
with a view to verify the correctness of fire safety measures undertaken & point out the
short comings, if any and direct to rectify or remove such short comings within specified
time and if the directions are not complied with within the time so given, the same shall
be intimate the Licensing Authority to cancel the permission & initiate action under
applicable laws.
15. Power of inspection etc.-
(1) The Director or an authorised member by general or special order, may, enter and inspect
such premises with a view to verify the correctness of the information furnished under
Rule 5 and to ascertain the adequacy and operability of fire prevention and fire safety
measures or violation of any provision of the Act or these rules and direct the owner or
occupier to rectify the deficiencies, if any, within such period as may be specified in the
order.
(2) The Director or an authorised member as specified in sub-rule (1) shall be provided with
all possible assistance and cooperation by the owner or occupier or any lawful authorised
person of such premises for carrying out inspection under sub-rule (1).
(3) If the directions of the Director or an authorised member under sub-rule (1) are not
complied with within the specified time, the Fire Safety Certificate of the said premises
may be cancelled by the Issuing Authority with due intimation to concerned regulatory or
Licensing Authority.
(4) Where the inspection is carried out by an authorised member under sub-rule (1), he shall
submit a report of such inspection to the Director.
LADAKH GAZETTE : EXTRAORDINARY 8
16. Power of Director to issue order. -
The Director may issue such orders, directions or instructions as may be necessary to
give effect to the provisions of these rules and to carry out their purposes.
By order of the Lieutenant Governor, Union territory of Ladakh.
Sd/-
(डॉ पवन कोतवाल, भ प्र से / Dr. Pawan Kotwal, IAS)
मुख्य सचिव/Chief Secretary/
प्रशासननक सनिव /Administrative Secretary
गृह नवभाग /Home Department
(अनुपम भारद्वाज / Anupam Bhardwaj)
अवर सचिव/ Under Secretary
ANUPAM
BHARDWAJ
Digitally signed by
ANUPAM BHARDWAJ
Date: 2025.11.29
13:20:01 +05'30'
LADAKH GAZETTE : EXTRAORDINARY 9
“FORM-I”
[Rule 9 (1) and Rule 11]
Application for License to act as Licensed Agency
To
The Licensing Authority
-------------------------------
-------------------------------
Sub: Grant or renewal of License to act as Licensed Agency for the purposes of the Union
territory of Ladakh, guidelines for empanelment of Licensed Agencies for third party audit
and installation of Fire Prevention and Protection measures.
Sir,
The undersigned hereby applies for grant of or renewal of License to act as a Licensed
Agency for undertaking and executing the work of providing installation of equipment and
maintenance of fire prevention and Fire safety measures in buildings/premises/occupancies.
The particulars regarding the Agency are given below:-
(1) Full name of the Applicant
(In capital Letters).
(2) Whether Licensed Agency will be
proprietary concern or an Association
of persons such as a Firm or company, etc.
(3) Registration No of Firm or Company
(Copies of Registration Certificate,
Article of Association or other relevant
document appended)
(4) Address
(5) If the Licensed Agency will be. -----
(a) A proprietary concern, the name qualification and address of the person operating the same.
(b) A firm of company, names, qualifications and addresses of each of the partners, or as the case
may be, Directors.
(6) Office address from where the Agency will act as a Licensed Agency -----
(7) Class for which License is applied for -----
(8) Personnel with the Agency -----
(a) Supervisory staff-names, qualifications and addresses of each.
(b) Other employees-names, qualifications and addresses of each.
(9) Details of work with regard to fire prevention and Fire safety measures, if any, undertaken
and executed previously-----
(a) Name or nature of work
(b) Approximate cost of workWhether the work executed or still in progress and remains to be
executed.
LADAKH GAZETTE : EXTRAORDINARY 10
(Note. – Original or attested copies of Certificate of verification of above details by the
officers under whom works are carried out are attached.)
(10) Technical qualifications and experience of the proprietor or partners of directors and dealing
technical officers or employees of or with the applicant.
(11) Workshop machinery, tolls and plant owned by the applicant, (location and site of workshop
and full details to be given).
(12) Whether enlisted with any other Department or Organization in any other State. If so, in
which category.
(a) Has the applicant or his partners or Directors been blacklisted in the past by any government
Department or Organization or other State?
(b) Has the applicant applied for registration elsewhere in his name or in the names of partner,
Director or firm or company? If so, whether the application is rejected? Give particulars.
(13) Whether the applicant has produced up to date Income tax certificate.
(14) Amount of solvency certificate which the applicant has held or produced.
(15) A fee of Rs ……….
Remitted herewith by Demand Draft No. ………… Dated
………….. Drawn on ………. Bank.
(16) If the application is for renewal of the existing license, the details in respect of the license and
the period of its validity (copy of the license appended).
(17) Whether, the license to act as Licensed Agency granted any time previously has been
suspended or cancelled; and if so, reasons thereof.
l/We certify that I/We have not been and will not get myself or ourselves
registered as contractor in the department under more than one name.”
Thanking you,
Yours faithfully,
(Applicant)
LADAKH GAZETTE : EXTRAORDINARY 11
"FORM-II”
[Rule 10]
License to act as a Licensed Agency for the purposes of Fire Prevention and Fire
Safety Measures
License No.
Date:
License is hereby granted or renewed under the provisions of the Union territory of
Ladakh, guidelines for empanelment of Licensed Agencies for third party audit and
installation of Fire Prevention and Protection measures to ________________________
having their registered office at ________________________________ to act as a
Licensed Agency for the purposes of the said guidelines for execution of the fire prevention
and Fire safety measures in ___________class of Licensed Agency.
The License will be valid for a period from___________ to ____________.
Licensing Authority
LADAKH GAZETTE : EXTRAORDINARY 12
"FORM-III (A)”
(Rule 12 (1))
Certificate by the Licensed Agency regarding the compliance of the Fire Prevention and
Fire Safety Measures, in building plans.
CERTIFICATE
Certified that I/We have prepared the building plans towards compliance in relation to
Measures to be provided for fire prevention and fire safety measures, for the following
buildings, or premises or occupancies as required under the provisions of the rules applicable.
Description and Location of Buildings or Premises or Occupancies
-----------------------------------------------------------------------------------
-----------------------------------------------------------------------------------
The attested copies of the building plans which I/ we have prepared is appended herewith.
Place: Signature and Address of the Licensed Agency.
Date:
License No. ……………………………………”
(*Note. --- For each building/tower a separate certificate in Form-III(A) should be necessary)
LADAKH GAZETTE : EXTRAORDINARY 13
"FORM-III (B)”
( Rule 12 (2))
Certificate by the Licensed Agency regarding the compliance of the Fire Prevention and
Fire Safety Measures.
CERTIFICATE
Certificate that I/We have executed the works towards compliance in relation to Measures
to be provided for Fire Prevention and Fire Safety and performed other related activities
required to be carried out, in the following buildings or premises or occupancies, as required
under the provisions of applicable rules.
Description and Location of Buildings or Premises or Occupancies
-----------------------------------------------------------------------------------
-----------------------------------------------------------------------------------
The details of the work and related activities which I/we have executed or performed are
mentioned in the list appended herewith.
Place: Signature and Address of the Licensed Agency.
Date:
License No. ……………………………………”
(*Note. --- For each building/tower a separate certificate in Form — IV(B) should be
necessary)
LADAKH GAZETTE : EXTRAORDINARY 14
"FORM- III (C)”
(Rule 12 (3))
Certificates to be given by the Licensed Agency for compliance of the Fire
Prevention and Fire safety measures.
CERTIFICATE
Certified that I/We have carried out inspection of the Measures in the following buildings
or premises or occupancies, namely*:-
------------------------------------------------------------------------
------------------------------------------------------------------------
I/We further certify that the installations in the above-mentioned buildings or premises or
occupancies are maintained in good repair and efficient conditions during the period
………………. as required under the provisions of the applicable rules. The details of the
inspection of installations carried out by me/us are mentioned in the report appended along
with photographs (min. 15 nos.) of inspection stages of Fire safety installations. Any lapses
in fire safety installation during fire incident if any shall be my responsibility.
Place: Signature and Address of the Licensed Agency
Date:
License No. …………………………….”
(*Note. ----- Detailed location and postal addresses are to be provided here).
LADAKH GAZETTE : EXTRAORDINARY 15
“FORM IV”
(Rule 13)
Notice to show cause as to why license granted or renewed to act as a Licensed
Agency be not suspended or cancelled
To
---------------------
---------------------
Where a License to act as Licensed Agency for the purpose of the Union territory of
Ladakh, guidelines for empanelment of Licensed Agencies for third party audit and
installation of Fire Prevention and Protection measures, under license No. ___________dated
____________ has been granted or renewed in the name of ___________________; and the
license, so granted or renewed was subject to the provisions of the Union territory of Ladakh,
guidelines for empanelment of Licensed Agencies for third party audit and installation of Fire
Prevention and Protection measures;
And whereas it is noticed that you are guilty of the following acts, namely:-
(1) .
(2) .
(3) .
And where these acts amount to __________________
Now, Therefore, in exercise of the powers conferred on me by clause 8 of the Union territory
of Ladakh, guidelines for empanelment of Licensed Agencies for third party audit and
installation of Fire Prevention and Protection measures I Now, hereby call upon you to show
cause in writing so as to reach the undersigned by ___________ on ____________ as to why
the license so granted or renewed in your favor should be suspended or cancelled,”
Licensing Authority
______________”.
LADAKH GAZETTE : EXTRAORDINARY 16
Ladakh Fire Prevention and Fire Safety Rules, 2025
Schedule-I
1. Group A: Residential buildings: includes any building in which sleeping
accommodation is provided for normal residential purpose with or without cooking or
dining or both facilities, except institutional buildings.
(i) Subdivision A1- Lodging and Rooming Houses: These shall include any building
or group of buildings under the same management, in which separate sleeping
accommodation on transient or permanent basis, with or without dining facilities but
without cooking facilities for individuals is provided. This includes inns, clubs,
motels, guest houses and home stays.
Upto 15 meters in height
Above 15
meters in
height
S.
No
Firefighting
installations
Up to 15 rooms
More than 15
rooms and up to
30 rooms
More than 30
rooms
1
Fire
Extinguishers
Required
Required
Required
Required
2
First Aid Hose
Reel
Not Required
Required
Required
Required
3
Down Comer
Not Required
Not Required
Not Required
Required
4
Automatic
sprinkler
System
Required to be
provided in the
basement if it
exceeds 200 m2
Required to be
provided in the
basement if it
exceeds 200 m2
Required to be
provided in the
basement if it
exceeds 200 m2
Required to
be provided
in the
basement if
it exceeds
200 m2
5
Manually
operated
Electronic Fire
Alarm System
Not required
Not required
Required to be
provided for
buildings with
more than two
storeys
Required
6
Terrace Tank
5000 Litres (if
basement area
exceeds 200 m2)
5000 Litres (plus
5000 Litres if
basement area
exceeds 200 m2)
10000 Litres
(plus 5000 Litres
if basement area
exceeds 200 m2)
25000
7
Fire Pump (at
terrace Level)
Not Required
450 LPM (plus
450 LPM if
basement area
exceeds 200 m2
450 LPM (plus
450 LPM if
basement area
exceeds 200 m2
900 LPM
Life Safety (Passive Defence)
LADAKH GAZETTE : EXTRAORDINARY 17
8
Staircase
minimum 1.25
meter wide
minimum 1.25
meter wide
Minimum two
separate exits
(minimum 1.25
meter wide) so
arranged that
maximum travel
distance on the
floor shall not
exceed 30 meters
Minimum
two
Separate
exits
(minimum
1.25 meter
wide) so
arranged
that
maximum
travel
distance on
the floor
shall not
exceed 30
meters
9
"Exit" signage
photoluminesce
nt exit signage
shall be
provided along
the way to exits
(no point shall
be more than 30
meters from a
visible exit
signage).
photoluminescent
exit signage shall
be provided along
the way to exits
(no point shall be
more than 30
meters from a
visible exit
signage).
photoluminescent
exit signage shall
be provided along
the way to exits
(no point shall be
more than 30
meters from a
visible exit
signage).
photolumin
escent exit
signage
shall be
provided
along the
way to exits
(no point
shall be
more than
30 meters
from a
visible exit
signage).
10
Emergency
Lights
Required to be
provided along
the means of
egress with
alternate power
source
Required to be
provided along
the means of
egress with
alternate power
source
Required to be
provided along
the means of
egress with
alternate power
source
Required to
be provided
along the
means of
egress with
alternate
power
source
11
Doorways
Shall not be less
than 1 meter in
width and 2
meter in height
Shall not be less
than 1 meter in
width and 2 meter
in height
Shall not be less
than 1 meter in
width and 2 meter
in height
Shall not be
less than 1
meter in
width and 2
meter in
height
LADAKH GAZETTE : EXTRAORDINARY 18
12
Fire drill and
fire order
Fire drill to be
conducted once
in a year, fire
order should be
displayed at
each floor.
Fire drill to be
conducted once in
a year, fire order
should be
displayed at each
floor.
Fire drill to be
conducted once in
a year, fire order
should be
displayed at each
floor.
Fire drill to
be
conducted
once in a
year, fire
order
should be
displayed at
each floor.
13
Cable and other
ducts
Shall be sealed
at each floor
level
Shall be sealed at
each floor level
Shall be sealed at
each floor level
Shall be
sealed at
each floor
level
14
Fire lift
Not required
Not required
Not required
At least one
Fire lift per
building
block
15
Fire damper
Not required
Not required
Not required
shall be
provided
where ducts
enter
vertical
shafts, pass
through
floors or
fire-rated
walls, and
at the inlets
of supply
and return
air ducts.
16
Lightening
arrester
Not required
Not required
Not required
Required
17
Compartmentali
zation
Not required
Not required
750m2
750m2
(ii) Sub-Division A2- One or Two family Private dwellings: These shall include any
private dwellings, which is occupied by members of one or two families and has a
total sleeping accommodation for not more than 20 persons. If rooms in a private
dwelling are rented to outsiders, these shall be for accommodating not more than three
persons per room. If sleeping accommodation for more than 20 persons is provided in
any one residential building, it shall be classified as a building in Subdivision A1 or
Subdivision A4 as the case may be.
The subdivision is exempted from fire safety norms.
(iii) Subdivision A3 - Dormitories: - These Shall include any building in which group
sleeping accommodation is provided, with or without dining facilities for persons who
are not members of the same family, in one room or a series of closely associated
LADAKH GAZETTE : EXTRAORDINARY 19
rooms under joint occupancy and single management, for example, school and college
dormitories, students, and other hostels and military barracks.
(iv) Subdivision A4 – Apartment houses: - These shall include any building or structure
in which living quarters are provided for three or more families, living independently
of each other and with independent cooking facilities, for example, apartment houses,
mansions and Chawls.
S.
No
Types of Fire
Protection (Active
Defence)
A3 Dormitories and A-4Apartment Houses
Upto 15 meters in height
Above 15 meters in height
1
Fire Extinguishers
Required
Required
2
First Aid Hose Reel
Required
Required
3
Down Comer
Not Required
Required
4
Automatic sprinkler
System
Required to be provided in the
basement if it exceeds 200 m2
Required to be provided in the
basement if it exceeds 200 m2
5
Manually operated
Electronic Fire
Alarm System
Not required
Required
6
Terrace Tank
5000 Litres (plus 5000 Litres if
basement area exceeds 200 m2)
25000 Litres
7
Fire Pump (at
terrace Level)
450 LPM (plus 450 LPM if
basement area exceeds 200 m2
900 LPM
Life Safety (Passive Defence)
8
Staircase
Minimum two separate exits
(minimum 1.25 meter wide) so
arranged that maximum travel
distance on the floor shall not
exceed 30 meters. Sleeping
rooms with occupancy > 10
persons require two separate and
distinct exit accesses in different
directions
Minimum two separate exits
(minimum 1.25 meter wide) so
arranged that maximum travel
distance on the floor shall not
exceed 30 meters. Sleeping
rooms with occupancy > 10
persons require two separate
and distinct exit accesses in
different directions
9
"Exit" signage
photoluminescent exit signage
shall be provided along the way
to exits (no point shall be more
than 30 meters from a visible exit
signage).
photoluminescent exit signage
shall be provided along the way
to exits (no point shall be more
than 30 meters from a visible
exit signage).
10
Emergency Lights
Required to be provided along
the means of egress with alternate
power source
Required to be provided along
the means of egress with
alternate power source
11
Doorways
Shall not be less than 1 meter in
width and 2 meter in height
Shall not be less than 1 meter in
width and 2 meter in height
12
Fire drill and fire
order
Fire drill to be conducted once in
a year, fire order should be
displayed at each floor.
Fire drill to be conducted once
in a year, fire order should be
displayed at each floor.
13
Cable and other
ducts
Shall be sealed at each floor level
Shall be sealed at each floor
level
14
Fire lift
Not required
At least one Fire lift per
building block
LADAKH GAZETTE : EXTRAORDINARY 20
15
Fire damper
Not required
shall be provided where ducts
enter vertical shafts, pass
through floors or fire-rated
walls, and at the inlets of
supply and return air ducts.
16
Lightening arrester
Not required
Required
17
Compartmentalizati
on
750 m2
750 m2
(v) Subdivision A5 - Hotels: - These shall include any building or group of buildings
under single management, in which sleeping accommodation is provided, with or
without dining facilities for hotels classified up to Four Star Category.
Upto 15 meters in height
Above 15
meters in
height
S.
No
Firefighting
installations
Floor area upto
300 m2 on any
of the floor
Floor area more
than 300 m2 and
upto 1000 m2 on
any of the floor
Floor area more
than 1000 m2 on
any of the floor
1
Fire
Extinguishers
Required
Required
Required
Required
2
First Aid Hose
Reel
Required
Required
Required
Required
3
Wet Riser
Not Required
Required to be
provided for
buildings with
more than two
storeys.
Required to be
provided for
buildings with
more than one
storey
Required
4
Yard Hydrant
Not Required
Not Required
Required
Required
5
Automatic
sprinkler
System
Required to be
provided in the
basement if it
exceeds 200 m2
Required to be
provided in the
basement if it
exceeds 200 m2
Required
Required
6
Manually
operated
Electronic Fire
Alarm System
Required
Required
Required. Shall
also include
talkback system
and public
address system
Required.
Shall also
include
talkback
system and
public
address
system
7
Automatic
Detection and
Alarm System
Not Required
Required
Required
Required
LADAKH GAZETTE : EXTRAORDINARY 21
8
Underground
Static water
Storage Tank
Not required
Required to be
provided for
building with
more than two
storeys at the rate
of 10000 Litres
per 500 m2
subject to a
minimum of
50000 Litres.
100000 Litres
(required to be
provided for
buildings with
more than one
storey.
150000
Litres
9
Terrace Tank
5000 Litres
(plus 5000
Litres if
basement area
exceeds 200 m2)
10000 Litres
(plus 5000 Litres
if basement area
exceeds 200 m2)
10000 Litres
(plus 10000
Litres if
basement area
exceeds 200 m2)
20000 Litres
10
Fire Pump (for
underground
water storage
Tank)
Not Required
One set of pumps
(one electric and
one diesel pump
of capacity 1620
Litres/ min) for
each 100 hydrant
or part thereof.
One set of pumps
(one electric and
one diesel pump
of capacity 1620
Litres/ min) for
each 100 hydrant
or part thereof
(only in buildings
with more than
one storey)
One set of
pumps (two
electric and
one diesel
pump of
capacity
2280 Litres/
min) for each
100 hydrant
or part
thereof (only
in buildings
with more
than one
storey)
11
Fire Pump (at
terrace Level)
450 LPM (plus
450 LPM if
basement area
exceeds 200 m2)
450 LPM (plus
450 LPM if
basement area
exceeds 200 m2)
450 LPM (plus
450 LPM if
basement area
exceeds 200 m2)
900 LPM
Life Safety (Passive Defence)
12
Staircase
Minimum two
separate exits
(minimum 1.5
meter wide) so
arranged that
maximum travel
distance on the
floor shall not
exceed 30
meters
Minimum two
separate exits
(minimum 1.5
meter wide) so
arranged that
maximum travel
distance on the
floor shall not
exceed 30 meters
Minimum two
separate exits
(minimum 1.5
meter wide) so
arranged that
maximum travel
distance on the
floor shall not
exceed 30 meters
Minimum
two separate
exits
(minimum
1.5 meter
wide) so
arranged that
maximum
travel
distance on
the floor
shall not
exceed 30
meters
LADAKH GAZETTE : EXTRAORDINARY 22
13
"Exit" signage
photoluminesce
nt exit signage
shall be
provided along
the way to exits
(no point shall
be more than 30
meters from a
visible exit
signage).
photoluminescent
exit signage shall
be provided
along the way to
exits (no point
shall be more
than 30 meters
from a visible
exit signage).
photoluminescent
exit signage shall
be provided
along the way to
exits (no point
shall be more
than 30 meters
from a visible
exit signage).
photolumines
cent exit
signage shall
be provided
along the
way to exits
(no point
shall be more
than 30
meters from
a visible exit
signage).
14
Emergency
Lights
Required to be
provided along
the means of
egress with
alternate power
source
Required to be
provided along
the means of
egress with
alternate power
source
Required to be
provided along
the means of
egress with
alternate power
source
Required to
be provided
along the
means of
egress with
alternate
power source
15
Doorways
Shall not be less
than 1 meter in
width and 2
meter in height
Shall not be less
than 1 meter in
width and 2
meter in height
Shall not be less
than 1 meter in
width and 2
meter in height
Shall not be
less than 1
meter in
width and 2
meter in
height
16
Fire drill and
fire order
Fire drill to be
conducted once
in a year, fire
order should be
displayed at
each floor.
Fire drill to be
conducted once
in a year, fire
order should be
displayed at each
floor.
Fire drill to be
conducted once
in a year, fire
order should be
displayed at each
floor.
Fire drill to
be conducted
once in a
year, fire
order should
be displayed
at each floor.
17
Compartmentali
zation
Not required
750 m2
750 m2
750 m2
18
Cable and other
ducts
Shall be sealed
at each floor
level
Shall be sealed at
each floor level
Shall be sealed at
each floor level
Shall be
sealed at
each floor
level
19
Fire lift
Not required
Not required
Not required
At least one
Fire lift
Required
20
Fire damper
Not required
Not required
Not required
shall be
provided
where ducts
enter vertical
shafts, pass
through
floors or fire-
rated walls,
and at the
LADAKH GAZETTE : EXTRAORDINARY 23
inlets of
supply and
return air
ducts.
21
Fire Command
Centre
Not required
Not required
Not required
Required
22
Lightening
arrester
Not required
Not required
Not required
Required
2. Group B-Educational Buildings: This shall include any building used for schools,
college other training institutions involving assembly for instruction, education or
recreation for not less than 20 students. It is further divided in to following
subdivisions:
(i) Subdivision B1: School up to senior secondary level: This includes any building or
a group of buildings under single management which is used for not less than 20
students.
(ii) Subdivision B2: All others/training institutions: This includes any building or a
group of buildings under single management which is used for not less than 100
students
S.No
Firefighting
installations
Upto 15 meters in height
(ground plus one or more
storeys)
Above 15 meters in height
1
Fire
Extinguishers
Required
Required
2
First Aid Hose
Reel
Required
Required
3
Down Comer
Not Required
Required
4
Automatic
sprinkler System
Required to be provided in the
basement if it exceeds 200 m2
Required to be provided in
the basement if it exceeds
200 m2
5
Manually
operated
Electronic Fire
Alarm System
Not Required
Required.
6
Terrace Tank
10000 Litres (plus 5000 Litres if
basement area exceeds 200 m2)
25000
7
Fire Pump (at
terrace Level)
450 LPM (plus 450 LPM if
basement area exceeds 200 m2)
900 LPM
8
Public address
system
Shall be provided for buildings
more than one storey
Required
Life Safety (Passive Defence)
LADAKH GAZETTE : EXTRAORDINARY 24
9
Staircase
Minimum two separate exits
(minimum 1.5 meter wide) so
arranged that maximum travel
distance on the floor shall not
exceed 30 meters. Exit doors shall
be operated by panic bars
Minimum two separate
exits (minimum 1.5 meter
wide) so arranged that
maximum travel distance
on the floor shall not
exceed 30 meters. Exit
doors shall be operated by
panic bars.
10
"Exit" signage
photoluminescent exit signage
shall be provided along the way to
exits (no point shall be more than
30 meters from a visible exit
signage).
photoluminescent exit
signage shall be provided
along the way to exits (no
point shall be more than 30
meters from a visible exit
signage)
11
Emergency
Lights
Required to be provided along the
means of egress with alternate
power source
Required to be provided
along the means of egress
with alternate power
source
12
Doorways
Shall not be less than 1 meter in
width and 2 meter in height. Every
room with a capacity of over 45
persons shall gave at least two
doorways
Shall not be less than 1
meter in width and 2 meter
in height. Every room with
a capacity of over 45
persons shall gave at least
two doorways
13
Fire drill and fire
order
Fire drill to be conducted once in a
year, fire order should be displayed
at each floor.
Fire drill to be conducted
once in a year, fire order
should be displayed at
each floor.
14
Compartmentaliz
ation
750 m2
750 m2
15
Cable and other
ducts
Shall be sealed at each floor level
Shall be sealed at each
floor level
16
Fire lift
Not required
At least one fire lift
required
17
Fire damper
Not required
shall be provided where
ducts enter vertical shafts,
pass through floors or fire-
rated walls, and at the
inlets of supply and return
air ducts.
18
Lightening
arrester
Not required
Required
19
Refuge area
Not required
Required to be provided at
each floor and terrace level
20
Public address
system
Required
required
3. Group C: Institutional Building: This shall include any building or part thereof,
which is used for purposes, such as medical or other treatment or care of persons
LADAKH GAZETTE : EXTRAORDINARY 25
suffering from physical or mental illness, disease or infirmity; care of infants,
convalescents or aged persons and for penal or correctional detention in which the
liberty of the inmates is restricted. Institutional buildings ordinarily provide sleeping
accommodation for the occupants. It is divided in to following subdivisions:
(i) Subdivision C1 Hospital and Sanatoria: This includes any building or a group of
buildings under single management which is used for housing persons suffering from
physical limitations because of health or age and those incapable of self-preservation,
for example hospitals, infirmaries, sanitoria and nursing homes.
Upto 15 meters in height
Above 15
meters in
height
S.
No
Firefighting
installations
Plot area upto 1000 m2
Plot area
more
than 1000
m2
Upto
ground
plus one
storey
with no
beds
Upto
ground
plus one
storey
with beds
Ground
plus two
or more
storeys
with no
beds
Ground
plus two
or more
storeys
with beds
1
Fire
Extinguishers
Required
Required
Required
Required
Required
Required
2
First Aid
Hose Reel
Not
Required
Required
Required
Required
Required
Required
3
Wet Riser
Not
Required
Not
required
Not
required
Required
Required
Required
4
Down Comer
Not
Required
Not
Required
Required
Not
Required
Not
Required
Not
Required
5
Yard Hydrant
Not
Required
Not
Required
Not
Required
Not
Required
Required
Required
6
Automatic
sprinkler
System
Required
to be
provided
in the
basement
if it
exceeds
200 m2
Required
to be
provided
in the
basement
if it
exceeds
200 m2
Required
to be
provided
in the
basement
if it
exceeds
200 m2
Required
Required
Required
7
Manually
operated
Electronic
Fire Alarm
System
Required
Required
Required. Required
(shall also
include
talk back
system
and public
address
system)
Required
(shall also
include
talk back
system
and public
address
system)
Required.
Shall also
include
talkback
system
and public
address
system
8
Automatic
Detection and
Alarm System
Not
Required
Not
required
Required
Required
Required
Required
LADAKH GAZETTE : EXTRAORDINARY 26
9
Underground
Static water
Storage Tank
Not
required
Not
required
Not
required
75000
Litres
100000
litres
150000
Litres
10
Terrace Tank
5000
Litres
(plus
5000
Litres if
basement
area
exceeds
200 m2)
5000
Litres
(plus
5000
Litres if
basement
area
exceeds
200 m2)
10000
Litres
(plus
5000
Litres if
basement
area
exceeds
200 m2)
10000
Litres
10000
Litres
20000
Litres
11
Fire Pump
(for
underground
water storage
Tank)
Not
Required
Not
required
Not
required
One set of
pump
(one
electric
and one
diesel
pump of
capacity
1620
Litres/
min) for
each 100
hydrant or
part
thereof
(only in
buildings
with more
than one
storey)
One set of
pump
(one
electric
and one
diesel
pump of
capacity
1620
Litres/
min) for
each 100
hydrant or
part
thereof
(only in
buildings
with more
than one
storey)
One set of
pump
(one
electric
and one
diesel
pump of
capacity
2280
Litres/
min) for
each 100
hydrant or
part
thereof
(only in
buildings
with more
than one
storey)
12
Fire Pump (at
terrace Level)
450 LPM
(plus 450
LPM if
basement
area
exceeds
200 m2)
450 LPM
(plus 450
LPM if
basement
area
exceeds
200 m2)
900 LPM
(plus 450
LPM if
basement
area
exceeds
200 m2)
900 LPM
(plus 450
LPM if
basement
area
exceeds
200 m2)
900 LPM
(plus 450
LPM if
basement
area
exceeds
200 m2)
900 LPM
(plus 450
LPM if
basement
area
exceeds
200 m2)
Life Safety (Passive Defence)
LADAKH GAZETTE : EXTRAORDINARY 27
13
Staircase
Minimum
two
separate
exits
(minimum
2 meter
wide) so
arranged
that
maximum
travel
distance
on the
floor shall
not
exceed 30
meters
Minimum
two
separate
exits
(minimu
m 2 meter
wide) so
arranged
that
maximum
travel
distance
on the
floor shall
not
exceed 30
meters
Minimum
two
separate
exits
(minimum
2 meter
wide) so
arranged
that
maximum
travel
distance
on the
floor shall
not
exceed 30
meters
Minimum
two
separate
exits
(minimum
2 meter
wide) so
arranged
that
maximum
travel
distance
on the
floor shall
not
exceed 30
meters
Minimum
two
separate
exits
(minimum
2 meter
wide) so
arranged
that
maximum
travel
distance
on the
floor shall
not
exceed 30
meters
Minimum
two
separate
exits
(minimum
2 meter
wide) so
arranged
that
maximum
travel
distance
on the
floor shall
not
exceed 30
meters
14
"Exit" signage
photolumi
nescent
exit
signage
shall be
provided
along the
way to
exits (no
point shall
be more
than 30
meters
from a
visible
exit
signage).
photolumi
nescent
exit
signage
shall be
provided
along the
way to
exits (no
point
shall be
more than
30 meters
from a
visible
exit
signage).
photolumi
nescent
exit
signage
shall be
provided
along the
way to
exits (no
point shall
be more
than 30
meters
from a
visible
exit
signage).
photolumi
nescent
exit
signage
shall be
provided
along the
way to
exits (no
point shall
be more
than 30
meters
from a
visible
exit
signage).
photolumi
nescent
exit
signage
shall be
provided
along the
way to
exits (no
point shall
be more
than 30
meters
from a
visible
exit
signage).
photolumi
nescent
exit
signage
shall be
provided
along the
way to
exits (no
point shall
be more
than 30
meters
from a
visible
exit
signage).
15
Emergency
Lights
Required
to be
provided
along the
means of
egress
with
alternate
power
source
Required
to be
provided
along the
means of
egress
with
alternate
power
source
Required
to be
provided
along the
means of
egress
with
alternate
power
source
Required
to be
provided
along the
means of
egress
with
alternate
power
source
Required
to be
provided
along the
means of
egress
with
alternate
power
source
Required
to be
provided
along the
means of
egress
with
alternate
power
source
LADAKH GAZETTE : EXTRAORDINARY 28
16
Doorways
Shall not
be less
than 1
meter in
width and
2 meter in
height
Shall not
be less
than 1
meter in
width and
2 meter in
height
Shall not
be less
than 1
meter in
width and
2 meter in
height
Shall not
be less
than 2
meter in
width and
2 meter in
height
with
double
swing
double
leaf type
door
Shall not
be less
than 2
meter in
width and
2 meter in
height
with
double
swing
double
leaf type
door
Shall not
be less
than 2
meter in
width and
2 meter in
height
with
double
swing
double
leaf type
door
17
Fire drill and
fire order
Fire drill
to be
conducted
once in a
year, fire
order
should be
displayed
at each
floor.
Fire drill
to be
conducted
once in a
year, fire
order
should be
displayed
at each
floor.
Fire drill
to be
conducted
once in a
year, fire
order
should be
displayed
at each
floor.
Fire drill
to be
conducted
once in a
year, fire
order
should be
displayed
at each
floor.
Fire drill
to be
conducted
once in a
year, fire
order
should be
displayed
at each
floor.
Fire drill
to be
conducted
once in a
year, fire
order
should be
displayed
at each
floor.
18
Compartment
alization
Not
required
750 m2
(1800 m2
in case of
sprinklere
d
basement/
building)
750 m2
(1800 m2
in case of
sprinklere
d
basement/
building)
750 m2
(1800 m2
in case of
sprinklere
d
basement/
building)
750 m2
(1800 m2
in case of
sprinklere
d
basement/
building)
750 m2
(1800 m2
in case of
sprinklere
d
basement/
building)
19
Cable and
other ducts
Shall be
sealed at
each floor
level
Shall be
sealed at
each floor
level
Shall be
sealed at
each floor
level
Shall be
sealed at
each floor
level
Shall be
sealed at
each floor
level
Shall be
sealed at
each floor
level
20
Fire lift
Not
required
At least
one Fire
lift
Required
Not
required
At least
one Fire
lift
Required
At least
one Fire
lift
Required
At least
one Fire
lift
Required
21
Fire damper
shall be
provided
where
ducts
enter
vertical
shafts,
pass
through
floors or
fire-rated
walls, and
shall be
provided
where
ducts
enter
vertical
shafts,
pass
through
floors or
fire-rated
walls, and
shall be
provided
where
ducts
enter
vertical
shafts,
pass
through
floors or
fire-rated
walls, and
shall be
provided
where
ducts
enter
vertical
shafts,
pass
through
floors or
fire-rated
walls, and
shall be
provided
where
ducts
enter
vertical
shafts,
pass
through
floors or
fire-rated
walls, and
shall be
provided
where
ducts
enter
vertical
shafts,
pass
through
floors or
fire-rated
walls, and
LADAKH GAZETTE : EXTRAORDINARY 29
at the
inlets of
supply
and return
air ducts.
at the
inlets of
supply
and return
air ducts.
at the
inlets of
supply
and return
air ducts.
at the
inlets of
supply
and return
air ducts.
at the
inlets of
supply
and return
air ducts.
at the
inlets of
supply
and return
air ducts.
22
Fire
Command
Centre
Not
required
Not
required
Not
required
Not
required
Required
Required
23
Lightening
arrester
Not
required
Required
Required
Required
Required
Required
24
Ramp
Not
required
Minimum
one
required
Minimum
one
required
Minimum
one
required
Minimum
one
required
Minimum
one
required
25
Automatic
Smoke
ventilation
system
Not
required
Required
for
ground
plus one
storey
Required
Required
Required
Required
26
Fire resistant
compartment
Not
required
Required
for
ground
plus one
storey
Required
at each
floor
Required
at each
floor
Required
at each
floor
Required
at each
floor
27
Refuge area
Not
required
Not
required
Not
required
Not
required
Not
required
Compart
mentation
of two
hour fire
resistance
with area
not less
than 25
m2 or 2
m2 per
ICU
patient in
each
floor.
(ii) Subdivision C2: Custodial institutions: This includes any building or a group of
buildings under single management which is used for the custody and care of
persons, such as children, convalescents and the aged who are incapable of self-
preservation, for example home for the aged and infirm, convalescent home and
orphanages.
(iii) Subdivision C3: penal and mental institutions: This includes any building or a
group of building under single management, which is used for housing persons under
restraint, or who are detained for penal or corrective purposes, in which the liberty of
the inmates is restricted, for example jails, prisons, mental hospitals, mental sanatoria
and reformatories.
LADAKH GAZETTE : EXTRAORDINARY 30
S.
No
Firefighting
installations
Upto 10 meters in height
Above 10 meters
and upto 15
meters in height
Above 15
meters in
height
Upto 300
persons
More than 300
persons
1
Fire
Extinguishers
Required
Required
Required
Required
2
First Aid Hose
Reel
Required
Required
Required
Required
3
Wet Riser
Not Required
Not required
Required to be
provided for
buildings with
more than one
storey
Required
4
Yard Hydrant
Not Required
Not Required
Required
Required
5
Automatic
sprinkler
System
Required to be
provided in the
basement if it
exceeds 200 m2
Required to be
provided in the
basement if it
exceeds 200 m2
Required to be
provided in the
basement if it
exceeds 200 m2
Required
6
Manually
operated
Electronic Fire
Alarm System
Required
Required
Required.
Required.
Shall also
include
talkback
system and
public address
system
7
Automatic
Detection and
Alarm System
Not Required
Not Required
Required
Required
8
Underground
Static water
Storage Tank
Not required
Not required
100000 Litres
150000 Litres
9
Terrace Tank
10000 Litres
(plus 5000
Litres if
basement area
exceeds 200
m2)
15000 Litres
(plus 5000 Litres
if basement area
exceeds 200 m2)
5000 Litres (plus
5000 Litres if
basement area
exceeds 200 m2)
10000
10
Fire Pump (for
underground
water storage
Tank)
Not Required
Not required
One set of pump
(one electric and
one diesel pump
of capacity 2280
Litres/ min) for
each 100 hydrant
or part thereof
(only in
buildings with
more than one
storey)
One set of
pump (two
electric and
one diesel
pump of
capacity 2280
Litres/ min)
for each 100
hydrant or
part thereof
(only in
buildings with
more than one
LADAKH GAZETTE : EXTRAORDINARY 31
storey)
11
Fire Pump (at
terrace Level)
450 LPM (plus
450 LPM if
basement area
exceeds 200
m2)
900 LPM (plus
450 LPM if
basement area
exceeds 200 m2)
450 LPM (plus
450 LPM if
basement area
exceeds 200 m2)
900 LPM
Life Safety (Passive Defence)
12
Staircase
Minimum two
separate exits
(minimum 2
meter wide) so
arranged that
maximum
travel distance
on the floor
shall not exceed
30 meters
Minimum two
separate exits
(minimum 2
meter wide) so
arranged that
maximum travel
distance on the
floor shall not
exceed 30 meters
Minimum two
separate exits
(minimum 2
meter wide) so
arranged that
maximum travel
distance on the
floor shall not
exceed 30 meters
Minimum two
separate exits
(minimum 2
meter wide)
so arranged
that
maximum
travel
distance on
the floor shall
not exceed 30
meters
13
"Exit" signage
photoluminesce
nt exit signage
shall be
provided along
the way to exits
(no point shall
be more than 30
meters from a
visible exit
signage).
photoluminescen
t exit signage
shall be provided
along the way to
exits (no point
shall be more
than 30 meters
from a visible
exit signage).
photoluminescen
t exit signage
shall be provided
along the way to
exits (no point
shall be more
than 30 meters
from a visible
exit signage).
photolumines
cent exit
signage shall
be provided
along the way
to exits (no
point shall be
more than 30
meters from a
visible exit
signage).
14
Emergency
Lights
Required to be
provided along
the means of
egress with
alternate power
source
Required to be
provided along
the means of
egress with
alternate power
source
Required to be
provided along
the means of
egress with
alternate power
source
Required to
be provided
along the
means of
egress with
alternate
power source
15
Doorways
Shall not be less
than 1 meter in
width and 2
meter in height
Shall not be less
than 1 meter in
width and 2
meter in height
Shall not be less
than 2 meter in
width and 2
meter in height
with double
swing double
leaf type door
Shall not be
less than 2
meter in
width and 2
meter in
height with
double swing
double leaf
type door
LADAKH GAZETTE : EXTRAORDINARY 32
16
Fire drill and
fire order
Fire drill to be
conducted once
in a year, fire
order should be
displayed at
each floor.
Fire drill to be
conducted once
in a year, fire
order should be
displayed at each
floor.
Fire drill to be
conducted once
in a year, fire
order should be
displayed at each
floor.
Fire drill to be
conducted
once in a
year, fire
order should
be displayed
at each floor.
17
Compartmental
ization
750 m2 (1125
m2 in case of
sprinklered
basement/
building)
750 m2 (1125 m2
in case of
sprinklered
basement/
building)
750 m2 (1125 m2
in case of
sprinklered
basement/
building)
750 m2 (1125
m2 in case of
sprinklered
basement/
building)
18
Cable and other
ducts
Shall be sealed
at each floor
level
Shall be sealed at
each floor level
Shall be sealed at
each floor level
Shall be
sealed at each
floor level
19
Fire damper
Not required
Not required
shall be provided
where ducts enter
vertical shafts,
pass through
floors or fire-
rated walls, and
at the inlets of
supply and return
air ducts.
shall be
provided
where ducts
enter vertical
shafts, pass
through floors
or fire-rated
walls, and at
the inlets of
supply and
return air
ducts.
20
Lightening
arrester
Not required
Not required
Not required
Required
4. Group D Assembly Buildings: This shall include any building or part of a building,
where not less than 50 persons congregate or gather for amusement, recreation, social,
religious, patriotic, civil, travel and similar purposes.
(i)
Subdivision D-1 Buildings having a theatrical or motion picture or any other stage
and fixed seats for over 1 000 persons
(ii) Subdivision D-2 Buildings having a theatrical or motion picture or any other stage
and fixed seats up to 1 000 persons
(iii) Subdivision D-3 Buildings without a permanent stage having accommodation for 300
or more persons but no permanent seating arrangement
(iv) Subdivision D-4 Buildings without a permanent stage having accommodation for less
than 300 persons with no permanent seating arrangement
(v) Subdivision D-5 All other structures including temporary structures designed for
assembly of people not covered by Subdivisions D-1 to D-4, at ground level
(vi) Subdivision D-6 Buildings having mixed occupancies of assembly and mercantile
(for example, shopping malls providing facilities such as shopping, cinema theatres,
multiplexes and restaurants/food courts)
LADAKH GAZETTE : EXTRAORDINARY 33
S.
No
Firefighting
installations
Subdivision D-1 to D-5
Subdivisio
n D-6
Upto 10 meters in height
Above 10
meters and
upto 15
meters in
height
Above 15
meters in
height
Upto 300
persons
More than
300 persons
1
Fire
Extinguisher
s
Required
Required
Required
Required
Required
2
First Aid
Hose Reel
Required
Required
Required
Required
Required
3
Wet Riser
Not Required
Not required
Required
Required
Required
4
Down
Comer
Required
Required
Not Required
Not
Required
Not
Required
5
Yard
Hydrant
Not Required
Not Required
Not Required
Required
Required
6
Automatic
sprinkler
System
Required to be
provided in
the basement
if it exceeds
200 m2
Required to be
provided in
the basement
if it exceeds
200 m2
Required to be
provided in
the basement
if it exceeds
200 m2
Required
Required
7
Manually
operated
Electronic
Fire Alarm
System
Required
Required
Required.
Shall also
include
talkback
system and
public address
system
Required.
Shall also
include
talkback
system and
public
address
system
Required.
Shall also
include
talkback
system
and public
address
system
8
Automatic
Detection
and Alarm
System
Not Required
Not Required
Required
Required
Required
9
Undergroun
d Static
water
Storage
Tank
Not required
Not required
100000 Litres 150000
Litres
200000
Litres
10
Terrace
Tank
20000 Litres
(plus 5000
Litres if
basement area
exceeds 200
m2)
25000 Litres
(plus 5000
Litres if
basement area
exceeds 200
m2)
5000 Litres
(plus 5000
Litres if
basement area
exceeds 200
m2)
10000 Litres
20000
Litres
LADAKH GAZETTE : EXTRAORDINARY 34
11
Fire Pump
(for
underground
water
storage
Tank)
Not Required
Not required
One set of
pump (one
electric and
one diesel
pump of
capacity 2280
Litres/ min)
for each 100
hydrant or
part thereof
(only in
buildings with
more than one
storey)
One set of
pump (one
electric and
one diesel
pump of
capacity
2280 Litres/
min) for
each 100
hydrant or
part thereof
(only in
buildings
with more
than one
storey)
One set of
pump (two
electric
and one
diesel
pump of
capacity
2850
Litres/
min) for
each 100
hydrant or
part
thereof
(only in
buildings
with more
than one
storey)
12
Fire Pump
(at terrace
Level)
450 LPM
(plus 450
LPM if
basement area
exceeds 200
m2)
900 LPM
(plus 450
LPM if
basement area
exceeds 200
m2)
450 LPM
(plus 450
LPM if
basement area
exceeds 200
m2)
900 LPM
900 LPM
Life Safety (Passive Defence)
13
Staircase
Minimum two
separate exits
(minimum 2
meter wide
(1.5m for
occupancy
less than 150
persons) so
arranged that
maximum
travel distance
on the floor
shall not
exceed 30
meters
Minimum two
separate exits
(minimum 2
meter wide)
so arranged
that maximum
travel distance
on the floor
shall not
exceed 30
meters
Minimum two
separate exits
(minimum 2
meter wide)
so arranged
that maximum
travel distance
on the floor
shall not
exceed 30
meters
Minimum
two separate
exits
(minimum 2
meter wide)
so arranged
that
maximum
travel
distance on
the floor
shall not
exceed 30
meters
Minimum
two
separate
exits
(minimum
2 meter
wide) so
arranged
that
maximum
travel
distance
on the
floor shall
not exceed
30 meters
LADAKH GAZETTE : EXTRAORDINARY 35
14
"Exit"
signage
photoluminesc
ent exit
signage shall
be provided
along the way
to exits (no
point shall be
more than 30
meters from a
visible exit
signage).
photoluminesc
ent exit
signage shall
be provided
along the way
to exits (no
point shall be
more than 30
meters from a
visible exit
signage).
photoluminesc
ent exit
signage shall
be provided
along the way
to exits (no
point shall be
more than 30
meters from a
visible exit
signage).
photolumine
scent exit
signage shall
be provided
along the
way to exits
(no point
shall be
more than 30
meters from
a visible exit
signage).
photolumi
nescent
exit
signage
shall be
provided
along the
way to
exits (no
point shall
be more
than 30
meters
from a
visible
exit
signage).
15
Emergency
Lights
Required to be
provided
along the
means of
egress with
alternate
power source
Required to be
provided
along the
means of
egress with
alternate
power source
Required to be
provided
along the
means of
egress with
alternate
power source
Required to
be provided
along the
means of
egress with
alternate
power source
Required
to be
provided
along the
means of
egress
with
alternate
power
source
16
Doorways
Shall not be
less than 2
meter in width
and 3 meter in
height
Shall not be
less than 2
meter in width
and 3 meter in
height
Shall not be
less than 2
meter in width
and 3 meter in
height
Shall not be
less than 2
meter in
width and 3
meter in
height
Shall not
be less
than 2
meter in
width and
3 meter in
height
17
Entrance
gate
Shall not be
less than 2
meter in width
and 3 meter in
height
Shall not be
less than 2
meter in width
and 3 meter in
height
Shall not be
less than 2
meter in width
and 3 meter in
height
Shall not be
less than 4.5
meter in
width and 5
meter in
height
Shall not
be less
than 4.5
meter in
width and
5 meter in
height
18
Evacuation
plan
Should be
displayed at
each floor
Should be
displayed at
each floor
Should be
displayed at
each floor
Should be
displayed at
each floor
Should be
displayed
at each
floor
LADAKH GAZETTE : EXTRAORDINARY 36
19
Assembly
point
Not required
Not required
Should be
designated at
the ground
floor for the
occupant of
each floor
Should be
designated at
the ground
floor for the
occupant of
each floor
Should be
designated
at the
ground
floor for
the
occupant
of each
floor
20
Fire drill and
fire order
Fire drill to be
conducted
once in a year,
fire order
should be
displayed at
each floor.
Fire drill to be
conducted
once in a year,
fire order
should be
displayed at
each floor.
Fire drill to be
conducted
once in a year,
fire order
should be
displayed at
each floor.
Fire drill to
be conducted
once in a
year, fire
order should
be displayed
at each floor.
Fire drill
to be
conducted
once in a
year, fire
order
should be
displayed
at each
floor.
21
Compartmen
talization
750 m2 (2000
m2 in case of
sprinklered
basement/
building)
750 m2 (2000
m2 in case of
sprinklered
basement/
building)
750 m2 (2000
m2 in case of
sprinklered
basement/
building)
750 m2
(2000 m2 in
case of
sprinklered
basement/
building)
750 m2
(2000 m2
in case of
sprinklere
d
basement/
building)
22
Cable and
other ducts
Shall be
sealed at each
floor level
Shall be
sealed at each
floor level
Shall be
sealed at each
floor level
Shall be
sealed at
each floor
level
Shall be
sealed at
each floor
level
23
Fire lift
Not required
Not required
Not required
At least one
Fire lift
Required
At least
one Fire
lift
Required
24
Fire damper
shall be
provided
where ducts
enter vertical
shafts, pass
through floors
or fire-rated
walls, and at
the inlets of
supply and
return air
ducts.
shall be
provided
where ducts
enter vertical
shafts, pass
through floors
or fire-rated
walls, and at
the inlets of
supply and
return air
ducts.
shall be
provided
where ducts
enter vertical
shafts, pass
through floors
or fire-rated
walls, and at
the inlets of
supply and
return air
ducts.
shall be
provided
where ducts
enter vertical
shafts, pass
through
floors or
fire-rated
walls, and at
the inlets of
supply and
return air
ducts.
shall be
provided
where
ducts enter
vertical
shafts,
pass
through
floors or
fire-rated
walls, and
at the
inlets of
supply and
return air
ducts.
LADAKH GAZETTE : EXTRAORDINARY 37
25
Fire
Command
Centre
Not required
Not required
Required
Required
Required
26
Lightening
arrester
Not required
Not required
Not required
Required
required
27
Smoke vent
system
Not required
Not required
Not required
Required
Required
5. Group E Business Buildings These shall include any building or part thereof which is
used for transaction of business for keeping of accounts and records and similar
purposes, professional establishments, service facilities, etc. City halls, town halls,
courthouses and libraries shall be classified in this group so far as the principal function
of these is transaction of public business and keeping of books and records. Buildings
under Group E shall be further subdivided as follows:
(i)
Subdivision E-1 Offices, banks, professional establishments, like offices of
architects, engineers, doctors, lawyers, post offices and police stations etc.
(ii) Subdivision E-2 Laboratories, outpatient clinics, research establishments, libraries
and test houses, etc
(iii) Subdivision E-3 Electronic data processing centres, computer installations,
information technology parks and call centres, etc
(iv) Subdivision E-4 Telephone exchanges, etc
(v) Subdivision E-5 Broadcasting stations, T.V. stations and air traffic control towers,
etc
S.
No
Firefighting
installations
Upto 10 meters in
height
Above 10 meters
and upto 15 meters
in height
Above 15 meters in
height
1
Fire Extinguishers
Required
Required
Required
2
First Aid Hose
Reel
Required
Required
Required
3
Wet Riser
Not Required
Required
Required
4
Down Comer
Required
Not Required
Not Required
5
Yard Hydrant
Not Required
Not Required
Required
6
Automatic
sprinkler System
Required to be
provided in the
basement if it
exceeds 200 m2
Required to be
provided in the
basement if it exceeds
200 m2
Required
7
Manually operated
Electronic Fire
Alarm System
Required
Required
Required.
8
Automatic
Detection and
Alarm System
Not Required
Required
Required
9
Underground
Static water
Not required
50000 litres
100000 Litres
LADAKH GAZETTE : EXTRAORDINARY 38
Storage Tank
10
Terrace Tank
10000 Litres (plus
5000 Litres if
basement area
exceeds 200 m2)
5000 Litres (plus
5000 Litres if
basement area
exceeds 200 m2)
10000 Litres
11
Fire Pump (for
underground water
storage Tank)
Not Required
One set of pump (one
electric and one diesel
pump of capacity
1620 Litres/ min) for
each 100 hydrant or
part thereof.
One set of pump (one
electric and one diesel
pump of capacity 2280
Litres/ min) for each 100
hydrant or part thereof
(only in buildings with
more than one storey)
12
Fire Pump (at
terrace Level)
450 LPM (plus
450 LPM if
basement area
exceeds 200 m2
450 LPM (plus 450
LPM if basement area
exceeds 200 m2
450 LPM (plus 450 LPM
if basement area exceeds
200 m2
Life Safety (Passive Defence)
13
Staircase
Minimum two
separate exits
(minimum 1.5
meter wide) so
arranged that
maximum travel
distance on the
floor shall not
exceed 30 meters
Minimum two
separate exits
(minimum 1.5 meter
wide) so arranged that
maximum travel
distance on the floor
shall not exceed 30
meters
Minimum two separate
exits (minimum1.5
meter wide) so arranged
that maximum travel
distance on the floor
shall not exceed 30
meters
14
"Exit" signage
photoluminescent
exit signage shall
be provided along
the way to exits
(no point shall be
more than 30
meters from a
visible exit
signage).
photoluminescent exit
signage shall be
provided along the
way to exits (no point
shall be more than 30
meters from a visible
exit signage).
photoluminescent exit
signage shall be
provided along the way
to exits (no point shall
be more than 30 meters
from a visible exit
signage).
15
Emergency Lights
Required to be
provided along the
means of egress
with alternate
power source
Required to be
provided along the
means of egress with
alternate power
source
Required to be provided
along the means of
egress with alternate
power source
16
Doorways
Shall not be less
than 1 meter in
width and 2 meter
in height
Shall not be less than
1 meter in width and
2 meter in height
Shall not be less than 1
meter in width and 2
meter in height
17
Fire drill and fire
order
Fire drill to be
conducted once in
a year, fire order
should be
displayed at each
Fire drill to be
conducted once in a
year, fire order should
be displayed at each
floor.
Fire drill to be conducted
once in a year, fire order
should be displayed at
each floor.
LADAKH GAZETTE : EXTRAORDINARY 39
floor.
18
Compartmentalizat
ion
750 m2 (3000 m2
in case of
sprinklered
basement/
building)
750 m2 (3000 m2 in
case of sprinklered
basement/ building)
750 m2 (3000 m2 in case
of sprinklered basement/
building)
19
Cable and other
ducts
Shall be sealed at
each floor level
Shall be sealed at
each floor level
Shall be sealed at each
floor level
20
Fire lift
Not required
Not required
At least one fire lift
required
21
Fire damper
Not required
shall be provided
where ducts enter
vertical shafts, pass
through floors or fire-
rated walls, and at the
inlets of supply and
return air ducts.
shall be provided where
ducts enter vertical
shafts, pass through
floors or fire-rated walls,
and at the inlets of
supply and return air
ducts.
22
Fire Command
Centre
Not required
Not required
Required
23
Lightening arrester
Not required
Not required
Required
24
Smoke vent
system
Not required
Not required
Required
6. Group F Mercantile Buildings These shall include any building or part thereof, which
is used as shops, stores, market, for display and sale of merchandise, either wholesale or
retail, except hazardous and highly inflammable goods. Mercantile buildings shall be
further subdivided as follows:
(i) Subdivision F-1 Shops, stores, departmental stores, markets (any with covered area
up to 500 m2)
(ii) Subdivision F-2 Shops, stores, departmental stores, markets (any with covered area
more than 500 m2)
(iii) Subdivision F-3 Underground shopping centres Storage and service facilities
incidental to the sale of merchandise and located in the same building shall also be
included under this group.
Subdivision F1 and F2
Sub-
division F3
S.
No
Firefighting
installations
Upto 15 meters in height
Above 15
meters in
height
Ground plus
one storey
with total of
all floor
area not
exceeding
500 m2
Ground plus
one storey
and total of
all floor area
exceeding 500
m2
More than
ground plus
one storey
LADAKH GAZETTE : EXTRAORDINARY 40
1
Fire
Extinguisher
s
Required
Required
Required
Required
Required
2
First Aid
Hose Reel
Required
Required
Required
Required
Required
3
Wet Riser
Not
Required
Not required
Not
Required
Required
Required
4
Down
Comer
Not
Required
Required
Required
Not Required
Not
Required
5
Yard
Hydrant
Not
Required
Not Required
Not
Required
Required
Required
6
Automatic
sprinkler
System
Required to
be provided
in the
basement if
it exceeds
200 m2
Required to be
provided in
the basement
if it exceeds
200 m2
Required to
be provided
in the
basement if
it exceeds
200 m2
Required
Required
7
Manually
operated
Electronic
Fire Alarm
System
Not
Required
Required
Required
Required
Required.
8
Automatic
Detection
and Alarm
System
Not
Required
Not Required
Not
Required
Required
Required
9
Undergroun
d Static
water
Storage
Tank
Not
Required
Not required
Not required
100000 litres
150000
Litres
10
Terrace
Tank
5000 Litres
(plus 5000
Litres if
basement
area exceeds
200 m2)
20000 Litres
(plus 5000
Litres if
basement area
exceeds 200
m2)
25000 Litres
(5000 Litres
if basement
area exceeds
200 m2)
10000 litres
10000
Litres
11
Fire Pump
(for
underground
water
storage
Tank)
Not
Required
Not required
Not required One set of
pumps (one
electric and
one diesel
pump of
capacity 2280
Litres/ min)
for each 100
hydrant or
part thereof
(only in
buildings with
more than one
One set of
pumps (two
electric and
one diesel
pump of
capacity
2280 Litres/
min) for
each 100
hydrant or
part thereof
(only in
buildings
LADAKH GAZETTE : EXTRAORDINARY 41
storey)
with more
than one
storey)
12
Fire Pump
(at terrace
Level)
450 LPM
(plus 450
LPM if
basement
area exceeds
200 m2
900 LPM
(plus 450
LPM if
basement area
exceeds 200
m2
900 LPM
(plus 450
LPM if
basement
area exceeds
200 m2
900 LPM
(plus 450
LPM if
basement area
exceeds 200
m2
900 LPM
Life Safety (Passive Defence)
13
Staircase
Minimum
two separate
exits
(minimum
1.5 meter
wide) so
arranged that
maximum
travel
distance on
the floor
shall not
exceed 30
meters
Minimum two
separate exits
(minimum 1.5
meter wide)
so arranged
that maximum
travel distance
on the floor
shall not
exceed 30
meters
Minimum
two separate
exits
(minimum
1.5 meter
wide) so
arranged that
maximum
travel
distance on
the floor
shall not
exceed 30
meters
Minimum two
separate exits
(minimum 1.5
meter wide)
so arranged
that maximum
travel distance
on the floor
shall not
exceed 30
meters
Minimum
two
separate
exits
(minimum
1.5 meter
wide) so
arranged
that
maximum
travel
distance on
the floor
shall not
exceed 30
meters
14
"Exit"
signage
photolumine
scent exit
signage shall
be provided
along the
way to exits
( no point
shall be
more than 30
meters from
a visible exit
signage).
photoluminesc
ent exit
signage shall
be provided
along the way
to exits ( no
point shall be
more than 30
meters from a
visible exit
signage).
photolumine
scent exit
signage shall
be provided
along the
way to exits
( no point
shall be
more than 30
meters from
a visible exit
signage).
photoluminesc
ent exit
signage shall
be provided
along the way
to exits ( no
point shall be
more than 30
meters from a
visible exit
signage).
photolumin
escent exit
signage
shall be
provided
along the
way to exits
( no point
shall be
more than
30 meters
from a
visible exit
signage).
LADAKH GAZETTE : EXTRAORDINARY 42
15
Emergency
Lights
Required to
be provided
along the
means of
egress with
alternate
power
source
Required to be
provided
along the
means of
egress with
alternate
power source
Required to
be provided
along the
means of
egress with
alternate
power source
Required to be
provided
along the
means of
egress with
alternate
power source
Required to
be provided
along the
means of
egress with
alternate
power
source
16
Doorways
Shall not be
less than 1
meter in
width and 2
meter in
height
Shall not be
less than 1
meter in width
and 2 meter in
height
Shall not be
less than 1
meter in
width and 2
meter in
height
Shall not be
less than 1
meter in width
and 2 meter in
height
Shall not be
less than 1
meter in
width and 2
meter in
height
17
Fire drill and
fire order
Fire drill to
be conducted
once in a
year, fire
order should
be displayed
at each floor.
Fire drill to be
conducted
once in a year,
fire order
should be
displayed at
each floor.
Fire drill to
be conducted
once in a
year, fire
order should
be displayed
at each floor.
Fire drill to be
conducted
once in a year,
fire order
should be
displayed at
each floor.
Fire drill to
be
conducted
once in a
year, fire
order
should be
displayed at
each floor.
18
Compartmen
talization
750 m2
(2000 m2 in
case of
sprinklered
basement/
building)
750 m2 (2000
m2 in case of
sprinklered
basement/
building)
750 m2
(2000 m2 in
case of
sprinklered
basement/
building)
750 m2 (2000
m2 in case of
sprinklered
basement/
building)
750 m2
(2000 m2 in
case of
sprinklered
basement/
building)
19
Cable and
other ducts
Shall be
sealed at
each floor
level
Shall be
sealed at each
floor level
Shall be
sealed at
each floor
level
Shall be
sealed at each
floor level
Shall be
sealed at
each floor
level
20
Fire lift
Not required Not required
Not required Not required
At least one
Fire lift
Required
21
Fire damper
Not required Not required
Not required shall be
provided
where ducts
enter vertical
shafts, pass
through floors
or fire-rated
walls, and at
the inlets of
supply and
return air
ducts.
shall be
provided
where ducts
enter
vertical
shafts, pass
through
floors or
fire-rated
walls, and
at the inlets
of supply
and return
air ducts.
LADAKH GAZETTE : EXTRAORDINARY 43
22
Fire
Command
Centre
Not required Not required
Not required Required
Required
23
Lightening
arrester
Not required Not required
Not required Required
Not
required
7. Group G Industrial Buildings-These shall include any building or part of a building or
structure, in which products or materials of all kinds and properties are fabricated,
assembled, manufactured or processed, The hazard of occupancy, shall be the relative
danger of the start and spread of fire, the danger of smoke or gases generated, the
danger of explosion or other occurrences potentially endangering the lives and safety of
the occupants of the buildings. Hazard of occupancy shall be determined by the
Authority on the basis of the fire loads of the contents, and the processes or operations
conducted in the building, provided, however, that where the combustibility of the
material, the flame spread rating of the interior finish or other features of the building or
structure are such as to involve a hazard greater than the occupancy hazard, the greater
degree of hazard shall govern the classification. Buildings under Group G shall be
further subdivided as follows:
(i) Subdivision G-1 Buildings used for low hazard industries: This subdivision shall
include any building in which the contents are of such comparative low
combustibility and the industrial processes or operations conducted therein are of
such a nature that there is hardly any possibility for any self-propagating fire to occur
and the only consequent danger to life and property may arise from panic, fumes or
smoke, or fire from some external source. For example, Brick works, canning
factories, clay works, milk pasteurising plant and dairies, confectionery
manufacturing, engineering workshops, fruit and vegetable dehydrating and drying
factories, fruit products and condiment factories, godowns and warehouses storing
non combustible goods only, poultry farms, water treatment/ filtration plants etc
Upto 15 meters in height
Above 15
meters in
height
S.
No
Firefighting
installations
Covered area
upto 100 m2
Covered area
more than 100 m2
and upto 500 m2
Covered are
more than 500
m2
1
Fire
Extinguishers
Required
Required
Required
Required
2
First Aid Hose
Reel
Not Required
Required
Required
Required
3
Wet Riser
Not Required
Not required
Not required
Required
4
Down Comer
Not Required
Required
Required
Not Required
5
Yard Hydrant
Not Required
Not Required
Not Required
Required
LADAKH GAZETTE : EXTRAORDINARY 44
6
Automatic
sprinkler System
Required to be
provided in
the basement
if it exceeds
200 m2
Required to be
provided in the
basement if it
exceeds 200 m2
Required to be
provided in the
basement if it
exceeds 200 m2
Required to be
provided in the
basement if it
exceeds 200 m2
7
Manually
operated
Electronic Fire
Alarm System
Not Required
Not Required
Required.
Required
8
Automatic
Detection and
Alarm System
Not Required
Not Required
Not Required
Required
9
Underground
Static water
Storage Tank
Not required
Not required
Not required
75000 Litres
10
Terrace Tank
5000 Litres
(plus 5000
Litres if
basement area
exceeds 200
m2)
20000 Litres (plus
5000 Litres if
basement area
exceeds 200 m2)
20000 Litres
(plus 5000
Litres if
basement area
exceeds 200
m2)
5000 Litres
(plus 5000
Litres if
basement area
exceeds 200 m2)
11
Fire Pump (for
underground
water storage
Tank)
Not Required
Not required
Not required
One set of
pump (one
electric and one
diesel pump of
capacity 1620
Litres/ min) for
each 100
hydrant or part
thereof (only in
buildings with
more than one
storey)
12
Fire Pump (at
terrace Level)
450 LPM
(plus 450
LPM if
basement area
exceeds 200
m2)
450 LPM (plus
450 LPM if
basement area
exceeds 200 m2)
450 LPM (plus
450 LPM if
basement area
exceeds 200
m2)
900 LPM
Life Safety (Passive Defence)
13
Staircase
Minimum two
separate exits
(minimum 1.5
meter wide)
so arranged
that maximum
travel distance
on the floor
shall not
exceed 30
Minimum two
separate exits
(minimum 1.5
meter wide) so
arranged that
maximum travel
distance on the
floor shall not
exceed 30 meters
Minimum two
separate exits
(minimum 1.5
meter wide) so
arranged that
maximum
travel distance
on the floor
shall not exceed
30 meters
Minimum two
separate exits
(minimum 1.5
meter wide) so
arranged that
maximum travel
distance on the
floor shall not
exceed 30
meters
LADAKH GAZETTE : EXTRAORDINARY 45
meters
14
"Exit" signage
photoluminesc
ent exit
signage shall
be provided
along the way
to exits (no
point shall be
more than 30
meters from a
visible exit
signage).
photoluminescent
exit signage shall
be provided along
the way to exits
(no point shall be
more than 30
meters from a
visible exit
signage).
photoluminesce
nt exit signage
shall be
provided along
the way to exits
(no point shall
be more than 30
meters from a
visible exit
signage).
photoluminesce
nt exit signage
shall be
provided along
the way to exits
(no point shall
be more than 30
meters from a
visible exit
signage).
15
Emergency
Lights
Required to be
provided
along the
means of
egress with
alternate
power source
Required to be
provided along the
means of egress
with alternate
power source
Required to be
provided along
the means of
egress with
alternate power
source
Required to be
provided along
the means of
egress with
alternate power
source
16
Doorways
Shall not be
less than 1
meter in width
and 2 meter in
height
Shall not be less
than 1 meter in
width and 2 meter
in height
Shall not be
less than 1
meter in width
and 2 meter in
height
Shall not be less
than 1 meter in
width and 2
meter in height
17
Fire drill and fire
order
Fire drill to be
conducted
once in a year,
fire order
should be
displayed at
each floor.
Fire drill to be
conducted once in
a year, fire order
should be
displayed at each
floor
Fire drill to be
conducted once
in a year, fire
order should be
displayed at
each floor
Fire drill to be
conducted once
in a year, fire
order should be
displayed at
each floor
18
Compartmentaliz
ation
In
consultation
with fire
department
In consultation
with fire
department
In consultation
with fire
department
In consultation
with fire
department
19
Cable and other
ducts
Shall be
sealed at each
floor level
Shall be sealed at
each floor level
Shall be sealed
at each floor
level
Shall be sealed
at each floor
level
20
Fire lift
Not required
Not required
Not required
At least one fire
lift required
LADAKH GAZETTE : EXTRAORDINARY 46
21
Fire damper
Not required
Not required
shall be
provided where
ducts enter
vertical shafts,
pass through
floors or fire-
rated walls, and
at the inlets of
supply and
return air ducts.
shall be
provided where
ducts enter
vertical shafts,
pass through
floors or fire-
rated walls, and
at the inlets of
supply and
return air ducts.
22
Fire Command
Centre
Not required
Not required
Not required
Required
23
Lightening
arrester
Not required
Not required
Not required
Required
(i) Subdivision G-2 Buildings used for moderate hazard industries: This subdivision
shall include any building in which the contents or industrial processes or operations
conducted therein are liable to give rise to a fire which will burn with moderate
rapidity or result in other hazardous situation and may give off a considerable volume
of smoke, but from which neither toxic fumes nor explosions are to be feared in the
event of fire. For example, atta and cereal grinding, bakeries and biscuit factories,
carpenter, wood wool and furniture manufacturing, cold storage premises, dry
cleaning, dyeing and laundries, electric substations/distribution stations, flour mills,
oxygen plants, plastic good manufacturing, plywood /wood veneering factories,
printing press premises, soap and glycerine factories, spray painting, textile mills
woollen mills etc.
Upto 15 meters in height
Covered
area more
than 500
m2 and
upto 1000
m2 and
height
above 15
meters
Covered
area more
than 1000
m2
S.
N
o
Firefightin
g
installation
s
Covered
area upto
100 m2
Covered
area more
than 100 m2
and upto 500
m2
Covered
area more
than 500 m2
and upto
1000 m2
1
Fire
Extinguishe
rs
Required
Required
Required
Required
Required
2
First Aid
Hose Reel
Required
Required
Required
Required
Required
3
Wet Riser
Not Required
Not required
Not required
Required
Required
4
Down
Comer
Not Required
Not Required
Required
Not
Required
Not Required
LADAKH GAZETTE : EXTRAORDINARY 47
5
Yard
Hydrant
Not Required
Not Required
Not Required
Required
Required
6
Automatic
sprinkler
System
Required
Required
Required
Required
Required
7
Manually
operated
Electronic
Fire Alarm
System
Not Required
Not Required
Required
Required
Required
8
Automatic
Detection
and Alarm
System
Not Required
Not Required
Required
Required
Required
9
Undergroun
d Static
water
Storage
Tank
Not required
Not required
Not required
100000
Litres
150000 Litres
10
Terrace
Tank
10000 Litres
20000 Litres
50000 Litres
10000
Litres
20000 Litres
11
Fire Pump
(for
undergroun
d water
storage
Tank)
Not Required
Not required
Not required
One set of
pumps (one
electric and
one diesel
pump of
capacity
1620 Litres/
min) for
each 100
hydrant or
part thereof
(only in
buildings
with more
than one
storey)
One set of
pumps (two
electric and
one diesel
pump of
capacity 2280
Litres/ min)
for each 100
hydrant or
part thereof
(only in
buildings
with more
than one
storey)
12
Fire Pump
(at terrace
Level)
450 LPM
900 LPM
900 LPM
900 LPM
900 LPM
Life Safety (Passive Defence)
13
Staircase
Minimum
two separate
exits
(minimum
1.5 meter
wide) so
arranged that
maximum
travel
Minimum
two separate
exits
(minimum
1.5 meter
wide) so
arranged that
maximum
travel
Minimum
two separate
exits
(minimum
1.5 meter
wide) so
arranged that
maximum
travel
Minimum
two separate
exits
(minimum
1.5 meter
wide) so
arranged that
maximum
travel
Minimum
two separate
exits
(minimum
1.5 meter
wide) so
arranged that
maximum
travel
LADAKH GAZETTE : EXTRAORDINARY 48
distance on
the floor shall
not exceed 30
meters
distance on
the floor shall
not exceed 30
meters
distance on
the floor shall
not exceed 30
meters
distance on
the floor
shall not
exceed 30
meters
distance on
the floor shall
not exceed 30
meters
14
"Exit"
signage
photolumines
cent exit
signage shall
be provided
along the
way to exits
(no point
shall be more
than 30
meters from a
visible exit
signage).
photolumines
cent exit
signage shall
be provided
along the
way to exits
(no point
shall be more
than 30
meters from a
visible exit
signage).
photolumines
cent exit
signage shall
be provided
along the
way to exits
(no point
shall be more
than 30
meters from a
visible exit
signage).
photolumines
cent exit
signage shall
be provided
along the
way to exits
(no point
shall be more
than 30
meters from
a visible exit
signage).
photolumines
cent exit
signage shall
be provided
along the
way to exits
(no point
shall be more
than 30
meters from a
visible exit
signage).
15
Emergency
Lights
Required to
be provided
along the
means of
egress with
alternate
power source
Required to
be provided
along the
means of
egress with
alternate
power source
Required to
be provided
along the
means of
egress with
alternate
power source
photolumin
escent exit
signage
shall be
provided
along the
way to exits
(no point
shall be
more than
30 meters
from a
visible exit
signage).
Required to
be provided
along the
means of
egress with
alternate
power source
16
Doorways
Shall not be
less than 1
meter in
width and 2
meter in
height
Shall not be
less than 1
meter in
width and 2
meter in
height
Shall not be
less than 1
meter in
width and 2
meter in
height
Shall not be
less than 1
meter in
width and 2
meter in
height
Shall not be
less than 1
meter in
width and 2
meter in
height
17
Fire drill
and fire
order
Fire drill to
be conducted
once in a
year, fire
order should
be displayed
at each floor.
Fire drill to
be conducted
once in a
year, fire
order should
be displayed
at each floor
Fire drill to
be conducted
once in a
year, fire
order should
be displayed
at each floor
Fire drill to
be
conducted
once in a
year, fire
order
should be
displayed at
each floor
Fire drill to
be conducted
once in a
year, fire
order should
be displayed
at each floor
18
Compartme
ntalization
In
consultation
with fire
department
In
consultation
with fire
department
In
consultation
with fire
department
In
consultation
with fire
department
In
consultation
with fire
department
LADAKH GAZETTE : EXTRAORDINARY 49
19
Cable and
other ducts
Shall be
sealed at each
floor level
Shall be
sealed at each
floor level
Shall be
sealed at each
floor level
Shall be
sealed at
each floor
level
Shall be
sealed at each
floor level
20
Fire lift
Not required
Not required
Not required
At least one
fire lift
required
At least one
fire lift
required if
more than
ground plus
one storeys
21
Fire damper
shall be
provided
where ducts
enter vertical
shafts, pass
through
floors or fire-
rated walls,
and at the
inlets of
supply and
return air
ducts.
shall be
provided
where ducts
enter vertical
shafts, pass
through
floors or fire-
rated walls,
and at the
inlets of
supply and
return air
ducts.
shall be
provided
where ducts
enter vertical
shafts, pass
through
floors or fire-
rated walls,
and at the
inlets of
supply and
return air
ducts.
shall be
provided
where ducts
enter
vertical
shafts, pass
through
floors or
fire-rated
walls, and
at the inlets
of supply
and return
air ducts.
shall be
provided
where ducts
enter vertical
shafts, pass
through
floors or fire-
rated walls,
and at the
inlets of
supply and
return air
ducts.
22
Fire
Command
Centre
Not required
Not required
Not required
required
Required
23
Lightening
arrester
Not required
Not required
Not required
required
Required
(ii) Subdivision G-3 Buildings used for high hazard industries: This subdivision shall
include any building in which the contents or industrial processes or operations
conducted therein are liable to give rise to a fire which will burn with extreme rapidity
or result in other hazardous situation or from which poisonous fumes or explosions are
to be feared in the event of a fire. For example, aircraft hangers, cotton waste factories,
godowns and warehouses storing combustible/ flammable goods, grass, hay, fodder
and bhoosa pressing factories, LPG bottling plants, saw mills etc. besides these norms
the buildings shall also adhere to IS standards as applicable.
Upto 15 meters in height (height above 15 meters shall not be allowed)
S.
N
o
Firefightin
g
installation
s
covered
area upto
50 m2
covered area
more than
50 m2 and
upto 150 m2
covered
area more
than 150
m2 and
upto 300 m2
Covered area
more than
300 m2 and
upto 500 m2
Covered
area more
than 500 m2
1
Fire
Extinguishe
rs
Required
Required
Required
Required
Required
LADAKH GAZETTE : EXTRAORDINARY 50
2
First Aid
Hose Reel
Required
Required
Required
Required
Required
3
Wet Riser
Not
Required
Not Required Required
Required
Required
4
Yard
Hydrant
Not
Required
Not Required Not
Required
Required
Required
5
Automatic
sprinkler
System
Required
Required
Required
Required
Required
6
Manually
operated
Electronic
Fire Alarm
System
Not
Required
Required
Required.
Required
Required
7
Automatic
Detection
and Alarm
System
Not
Required
Required
Required
Required
Required
8
Undergroun
d Static
water
Storage
Tank
Not
required
Not Required 50000
Litres
100000 Litres
150000
Litres
9
Terrace
Tank
10000
Litres
25000 Litres
10000
Litres
20000 Litres
20000 Litres
10
Fire Pump
(for
undergroun
d water
storage
Tank)
Not
Required
Not Required One set of
pumps (one
electric and
one diesel
pump of
capacity
1620 Litres/
min) for
each 100
hydrant or
part thereof
(only in
buildings
with more
than one
storey)
One set of
pumps (one
electric and
one diesel
pump of
capacity 2280
Litres/ min)
for each 100
hydrant or part
thereof (only
in buildings
with more than
one storey)
One set of
pumps (two
electric and
one diesel
pump of
capacity
2280 Litres/
min) for each
100 hydrant
or part
thereof (only
in buildings
with more
than one
storey)
11
Fire Pump
(at terrace
Level)
900 LPM
900 LPM
900 LPM
900 LPM
900 LPM
Life Safety (Passive Defence)
LADAKH GAZETTE : EXTRAORDINARY 51
12
Staircase
Minimum
two
separate
exits
(minimum
1.5 meter
wide) so
arranged
that
maximum
travel
distance on
the floor
shall not
exceed 30
meters
Minimum
two separate
exits
(minimum
1.5 meter
wide) so
arranged that
maximum
travel
distance on
the floor
shall not
exceed 30
meters
Minimum
two
separate
exits
(minimum
1.5 meter
wide) so
arranged
that
maximum
travel
distance on
the floor
shall not
exceed 30
meters
Minimum two
separate exits
(minimum 1.5
meter wide)
so arranged
that maximum
travel distance
on the floor
shall not
exceed 30
meters
Minimum
two separate
exits
(minimum
1.5 meter
wide) so
arranged that
maximum
travel
distance on
the floor shall
not exceed 30
meters
13
"Exit"
signage
photolumin
escent exit
signage
shall be
provided
along the
way to exits
(no point
shall be
more than
30 meters
from a
visible exit
signage).
photolumines
cent exit
signage shall
be provided
along the
way to exits
(no point
shall be more
than 30
meters from
a visible exit
signage).
photolumin
escent exit
signage
shall be
provided
along the
way to exits
(no point
shall be
more than
30 meters
from a
visible exit
signage).
photoluminesc
ent exit
signage shall
be provided
along the way
to exits (no
point shall be
more than 30
meters from a
visible exit
signage).
photolumines
cent exit
signage shall
be provided
along the
way to exits
(no point
shall be more
than 30
meters from a
visible exit
signage).
14
Emergency
Lights
Required to
be provided
along the
means of
egress with
alternate
power
source
Required to
be provided
along the
means of
egress with
alternate
power source
Required to
be provided
along the
means of
egress with
alternate
power
source
Required to be
provided along
the means of
egress with
alternate
power source
Required to
be provided
along the
means of
egress with
alternate
power source
15
Doorways
Shall not be
less than 1
meter in
width and 2
meter in
height.
There shall
be at least
two ways of
escape from
every room
Shall not be
less than 1
meter in
width and 2
meter in
height. There
shall be at
least two
ways of
escape from
every room
Shall not be
less than 1
meter in
width and 2
meter in
height.
There shall
be at least
two ways of
escape from
every room
Shall not be
less than 1
meter in width
and 2 meter in
height. There
shall be at
least two ways
of escape from
every room
Shall not be
less than 1
meter in
width and 2
meter in
height. There
shall be at
least two
ways of
escape from
every room
LADAKH GAZETTE : EXTRAORDINARY 52
16
Fire drill
and fire
order
Fire drill to
be
conducted
once in a
year, fire
order
should be
displayed at
each floor.
Fire drill to
be conducted
once in a
year, fire
order should
be displayed
at each floor.
Fire drill to
be
conducted
once in a
year, fire
order
should be
displayed at
each floor.
Fire drill to be
conducted
once in a year,
fire order
should be
displayed at
each floor.
Fire drill to
be conducted
once in a
year, fire
order should
be displayed
at each floor.
17
Compartme
ntalization
750 m2
750 m2
750 m2
750 m2
750 m2
18
Cable and
other ducts
Shall be
sealed at
each floor
level
Shall be
sealed at
each floor
level
Shall be
sealed at
each floor
level
Shall be sealed
at each floor
level
Shall be
sealed at each
floor level
19
Fire lift
Not
required
Not required
Not
required
Not required
Required for
buildings
with more
than ground
plus one
storeys
20
Fire damper
shall be
provided
where ducts
enter
vertical
shafts, pass
through
floors or
fire-rated
walls, and
at the inlets
of supply
and return
air ducts.
shall be
provided
where ducts
enter vertical
shafts, pass
through
floors or fire-
rated walls,
and at the
inlets of
supply and
return air
ducts.
shall be
provided
where ducts
enter
vertical
shafts, pass
through
floors or
fire-rated
walls, and
at the inlets
of supply
and return
air ducts.
shall be
provided
where ducts
enter vertical
shafts, pass
through floors
or fire-rated
walls, and at
the inlets of
supply and
return air
ducts.
shall be
provided
where ducts
enter vertical
shafts, pass
through
floors or fire-
rated walls,
and at the
inlets of
supply and
return air
ducts.
21
Fire
Command
Centre
Not
required
Not required
Not
required
Not required
required
22
Lightening
arrester
Not
required
Not required
Not
required
Not required
required
23
Fire
separation
wall
Area
housing
hazardous
materials
shall be
separated
from no
hazardous
areas by
minimum
Area housing
hazardous
materials
shall be
separated
from no
hazardous
areas by
minimum
120-minute
Area
housing
hazardous
materials
shall be
separated
from no
hazardous
areas by
minimum
Area housing
hazardous
materials shall
be separated
from no
hazardous
areas by
minimum 120-
minute fire
resistance
Area housing
hazardous
materials
shall be
separated
from no
hazardous
areas by
minimum
120-minute
LADAKH GAZETTE : EXTRAORDINARY 53
120-minute
fire
resistance
rating walls/
doors
fire
resistance
rating walls/
doors
120-minute
fire
resistance
rating walls/
doors
rating walls/
doors
fire
resistance
rating walls/
doors
24
Explosion
relief vents
To be
provided at
suitable
places with
suitable size
wherever
applicable
To be
provided at
suitable
places with
suitable size
wherever
applicable
To be
provided at
suitable
places with
suitable size
wherever
applicable
To be
provided at
suitable places
with suitable
size wherever
applicable
To be
provided at
suitable
places with
suitable size
wherever
applicable
25
Roof
screens/
curtain
boards
To be
provided
from the
roof
downwards
at 30 meters
interval to
prevent
lateral
spread of
smoke and
heat
To be
provided
from the roof
downwards
at 30 meters
interval to
prevent
lateral spread
of smoke and
heat
To be
provided
from the
roof
downwards
at 30 meters
interval to
prevent
lateral
spread of
smoke and
heat
To be
provided from
the roof
downwards at
30 meters
interval to
prevent lateral
spread of
smoke and
heat
To be
provided
from the roof
downwards
at 30 meters
interval to
prevent
lateral spread
of smoke and
heat
8. Group H Storage Buildings These shall include any building or part of a building used
primarily for the storage or sheltering (including servicing, processing or repairs
incidental to storage) of goods, ware or merchandise (except those that involve highly
combustible or explosive products or materials), vehicles or animals, for example,
warehouses, cold storages, freight depots, transit sheds, storehouses, truck and marine
terminals, garages, hangars, grain elevators, barns and stables.
Upto 15 meters in height
Multi
Level Car
parking
S.
No
Firefightin
g
installation
s
Covered
are less
than 250 m2
covered area more than 250 m2
Ground floor
only
Ground
plus one
floor
More than
ground plus
one floor
1
Fire
Extinguisher
s
Required
Required
Required
Required
Required
2
First Aid
Hose Reel
Required
Required
Required
Required
Required
3
Wet Riser
Not
Required
Required
Required
Required
Required
4
Down
Comer
Not
Required
Not Required
Not
Required
Not Required
Not
Required
5
Yard
Hydrant
Not
Required
Required
Required
Required
Required
LADAKH GAZETTE : EXTRAORDINARY 54
6
Automatic
sprinkler
System
Required
Required
Required
Required
Required
7
Manually
operated
Electronic
Fire Alarm
System
Not
Required
Required
Required.
Required
Required
8
Automatic
Detection
and Alarm
System
Not
Required
Required
Required
Required
Not
Required
9
Undergroun
d Static
water
Storage
Tank
Not required 50000 Litres
75000 Litres 100000 Litres
150000
Litres
10
Terrace
Tank
25000 Litres 10000 Litres
10000 Litres 10000 Litres
10000
Litres
11
Fire Pump
(for
undergroun
d water
storage
Tank)
Not
Required
One set of
pump (one
electric and
one diesel
pump of
capacity 1620
Litres/ min)
for each 100
hydrant or
part thereof
(only in
buildings
with more
than one
storey)
One set of
pump (one
electric and
one diesel
pump of
capacity
2280 Litres/
min) for
each 100
hydrant or
part thereof
(only in
buildings
with more
than one
storey)
One set of
pump (one
electric and
one diesel
pump of
capacity 2280
Litres/ min) for
each 100
hydrant or part
thereof (only in
buildings with
more than one
storey)
One set of
pump (two
electric and
one diesel
pump of
capacity
2280
Litres/ min)
for each
100
hydrant or
part thereof
(only in
buildings
with more
than one
storey)
12
Fire Pump
(at terrace
Level)
900 LPM
450 LPM
450 LPM
450 LPM
900 LPM
Life Safety (Passive Defence)
13
Staircase
Minimum
two separate
exits
(minimum
1.5 meter
wide) so
arranged
that
maximum
travel
Minimum
two separate
exits
(minimum
1.5 meter
wide) so
arranged that
maximum
travel
distance on
Minimum
two separate
exits
(minimum
1.5 meter
wide) so
arranged
that
maximum
travel
Minimum two
separate exits
(minimum 1.5
meter wide) so
arranged that
maximum
travel distance
on the floor
shall not
exceed 30
Minimum
two
separate
exits
(minimum
1.5 meter
wide) so
arranged
that
maximum
LADAKH GAZETTE : EXTRAORDINARY 55
distance on
the floor
shall not
exceed 30
meters
the floor shall
not exceed 30
meters
distance on
the floor
shall not
exceed 30
meters
meters
travel
distance on
the floor
shall not
exceed 45
meters
14
"Exit"
signage
photolumine
scent exit
signage
shall be
provided
along the
way to exits
(no point
shall be
more than
30 meters
from a
visible exit
signage).
photolumines
cent exit
signage shall
be provided
along the way
to exits (no
point shall be
more than 30
meters from a
visible exit
signage).
photolumine
scent exit
signage
shall be
provided
along the
way to exits
(no point
shall be
more than
30 meters
from a
visible exit
signage).
photoluminesc
ent exit signage
shall be
provided along
the way to
exits (no point
shall be more
than 30 meters
from a visible
exit signage).
photolumin
escent exit
signage
shall be
provided
along the
way to
exits (no
point shall
be more
than 30
meters
from a
visible exit
signage).
15
Emergency
Lights
Required to
be provided
along the
means of
egress with
alternate
power
source
Required to
be provided
along the
means of
egress with
alternate
power source
Required to
be provided
along the
means of
egress with
alternate
power
source
Required to be
provided along
the means of
egress with
alternate power
source
Required to
be provided
along the
means of
egress with
alternate
power
source
16
Doorways
Shall not be
less than 1
meter in
width and 2
meter in
height.
Shall not be
less than 1
meter in
width and 2
meter in
height.
Shall not be
less than 1
meter in
width and 2
meter in
height.
Shall not be
less than 1
meter in width
and 2 meter in
height.
Shall not
be less than
1 meter in
width and 2
meter in
height.
17
Fire drill
and fire
order
Fire drill to
be
conducted
once in a
year, fire
order should
be displayed
at each
floor.
Fire drill to
be conducted
once in a
year, fire
order should
be displayed
at each floor.
Fire drill to
be
conducted
once in a
year, fire
order should
be displayed
at each
floor.
Fire drill to be
conducted once
in a year, fire
order should be
displayed at
each floor.
Fire drill to
be
conducted
once in a
year, fire
order
should be
displayed
at each
floor.
LADAKH GAZETTE : EXTRAORDINARY 56
18
Compartme
ntalization
In
consultation
with fire
department
In
consultation
with fire
department
In
consultation
with fire
department
In consultation
with fire
department
In
consultatio
n with fire
department
19
Cable and
other ducts
Shall be
sealed at
each floor
level
Shall be
sealed at each
floor level
Shall be
sealed at
each floor
level
Shall be sealed
at each floor
level
Shall be
sealed at
each floor
level
20
Fire lift
Not required Not required
Not required Not required
Required
for
buildings
with more
than
ground plus
one storeys
21
Fire damper
shall be
provided
where ducts
enter
vertical
shafts, pass
through
floors or
fire-rated
walls, and at
the inlets of
supply and
return air
ducts.
shall be
provided
where ducts
enter vertical
shafts, pass
through floors
or fire-rated
walls, and at
the inlets of
supply and
return air
ducts.
shall be
provided
where ducts
enter
vertical
shafts, pass
through
floors or
fire-rated
walls, and at
the inlets of
supply and
return air
ducts.
shall be
provided where
ducts enter
vertical shafts,
pass through
floors or fire-
rated walls,
and at the
inlets of supply
and return air
ducts.
shall be
provided
where
ducts enter
vertical
shafts, pass
through
floors or
fire-rated
walls, and
at the inlets
of supply
and return
air ducts.
22
Fire
Command
Centre
Not required Not required
Not required Not required
required
23
Lightening
arrester
Not required Not required
Not required Not required
required
24
Fire
separation
wall
Not required Not required
Not required Not required
The
hazardous
areas like
DG sets,
transformer
, HT/LT
panel etc
shall be
suitably
segregated
from other
areas.
25
Evacuation
route plan
Not required Not required
Not required Should be
displayed on
each floor at
prominent
Should be
displayed
on each
floor at
LADAKH GAZETTE : EXTRAORDINARY 57
places
prominent
places
9. Group I; Hazardous Buildings These shall include any building or part thereof which
is used for the storage, handling, manufacture or processing of highly combustible or
explosive materials or products which are liable to burn with extreme rapidity and/or
which may produce poisonous fumes or explosions for storage, handling, manufacturing
or processing which involve highly corrosive, toxic or noxious alkalis, acids or other
liquids or chemicals producing flame, fumes and explosive, poisonous, irritant or
corrosive gases; and for the storage, handling or processing of any material producing
explosive mixtures of dust which result in the division of matter into fine particles
subject to spontaneous ignition.
Upto 15 meters in height
S.
No
Firefighting installations
Single storey
building
More than one floor building
1
Fire Extinguishers
Required
Required
2
First Aid Hose Reel
Required
Required
3
Wet Riser
Required
Required
4
Down Comer
Not Required
Required
5
Yard Hydrant
Required
Required
6
Automatic sprinkler System
Required
Required
7
Manually operated
Electronic Fire Alarm
System
Required
Required
8
Automatic Detection and
Alarm System
Required
Required
9
Underground Static water
Storage Tank
Minimum 240-minute
firefighting
requirements
Minimum 240-minute firefighting
requirements
10
Terrace Tank
Not required
50000 Litres
11
Fire Pump (for underground
water storage Tank)
Pump capacity shall
be based on the
covered area of the
building
Pump capacity shall be based on
the covered area of the building
12
Fire Pump (at terrace Level)
Not required
900 LPM
Life Safety (Passive Defence)
13
Staircase
Minimum two
separate exits
(minimum 1.5 meter
wide) so arranged that
maximum travel
distance on the floor
shall not exceed 30
meters
Minimum two separate exits
(minimum 1.5 meter wide) so
arranged that maximum travel
distance on the floor shall not
exceed 30 meters
LADAKH GAZETTE : EXTRAORDINARY 58
14
"Exit" signage
photoluminescent exit
signage shall be
provided along the
way to exits (no point
shall be more than 30
meters from a visible
exit signage).
photoluminescent exit signage
shall be provided along the way to
exits (no point shall be more than
30 meters from a visible exit
signage).
15
Emergency Lights
Required to be
provided along the
means of egress with
alternate power
source
Required to be provided along the
means of egress with alternate
power source
16
Doorways
Shall not be less than
1 meter in width and 2
meter in height.
Shall not be less than 1 meter in
width and 2 meter in height.
17
Fire drill and fire order
Fire drill to be
conducted once in a
year, fire order should
be displayed at each
floor.
Fire drill to be conducted once in a
year, fire order should be
displayed at each floor.
18
Compartmentalization
Shall be done in
consultation with fire
department
Shall be done in consultation with
fire department
19
Cable and other ducts
Shall be sealed at
each floor level
Shall be sealed at each floor level
20
Fire damper
shall be provided
where ducts enter
vertical shafts, pass
through floors or fire-
rated walls, and at the
inlets of supply and
return air ducts.
shall be provided where ducts
enter vertical shafts, pass through
floors or fire-rated walls, and at
the inlets of supply and return air
ducts.
21
Fire Command Centre
Not required
required
22
Lightening arrester
required
required
23
Fire separation wall
required
required
24
Evacuation route plan
required
required
“No legal responsibility is accepted for the contents of publication of advertisements/publications in this part of The
Ladakh Gazette. Persons notifying the advertisements/public notices will remain solely responsible for the legal
consequences and also for any other misrepresentation etc.”