[79]

TAMIL NADU

GOVERNMENT GAZETTE

PUBLISHED BY AUTHORITY

DTP—VI-2 (30)

NOTIFICATIONS BY HEADS OF DEPARTMENTS, ETC.

CONTENTS

No.  30]

CHENNAI, WEDNESDAY, JULY 30, 2025

Aadi 14, Visuvaavasu, Thiruvalluvar Aandu–2056

Part VI—Section 2

Notifications of interest to a section of the public

issued by Heads of Departments, etc.

© [Regd. No. TN/CCN/467/2012-14.

GOVERNMENT OF TAMIL NADU [R. Dis. No. 197/2009.

2025 [Price: Rs. 4.00 Paise.

Pages.

TAMIL NADU ELECTRICITY REGULATORY COMMISSION, CHENNAI.

Amendments to the Tamil Nadu Electricity Regulatory Commission (Terms and Conditions

for determination of Tariff) Regulations, 2005. ..

..

..

..

..

..

..

..

80-85

Nomination of member of the State Advisory Committee. ..

..

..

..

..

..

86-88

TAMIL NADU GOVERNMENT GAZETTE

80

[Part   VI—Sec. 2

NOTIFICATIONS BY HEADS OF DEPARTMENTS, ETC.

TAMIL NADU ELECTRICITY REGULATORY COMMISSION, CHENNAI.

Amendments to the Tamil Nadu Electricity Regulatory Commission (Terms and Conditions for

determination of Tariff) Regulations, 2005.

(Notification No. TNERC/TR/5-5/2025, dated 01-07-2025)

(Lr.No. TNERC/Legal/1368/D.No.906/2025)

No. VI(2)/16/2025.

In exercise of the powers conferred by section 61 of the Electricity Act, 2003 (Central Act 36 of 2003) read with

section 181 of the said Act and all other powers enabling it in this behalf, the Tamil Nadu Electricity Regulatory Commission

hereby makes the following amendments to the Tamil Nadu Electricity Regulatory Commission (Terms and conditions for

determination of Tariff) Regulations, 2005 (hereafter referred to as “the Principal Regulations”) and the draft of the same

having been previously published as required by sub-section (3) of section 181 of the said Act.

Amendments

(i) These Regulations may be called the “Tamil Nadu Electricity Regulatory Commission (Terms and conditions

for determination of Tariff) (Amendment) Regulations, 2025”.

(ii) These Regulations shall come into force on the date of publication in the Tamil Nadu Government Gazette.

1. Amendment to Regulation 37 of the Principal Regulations:

1.1 The clause (vii) in Regulation 37 of the Principal Regulations notified vide Notification No. TNERC/TR/5/3, dated

26-05-2021 shall be read as clause (viii);

1.2. In Regulation 37 of the Principal Regulations, for the clause (viii), the following clause shall be substituted,

namely:

“(viii) Impact of Part Load Operation on performance of Thermal Generating Stations:

where any of the Generating station is directed by the State Load Despatch centre to operate below Target plant

availability factor but at or above technical minimum, such generating station may be compensated depending on the

average unit loading duly taking into account the forced outages, planned outages, PLF, generation at generator terminal,

energy sent out ex-bus, number of start-stop, secondary fuel oil consumption and auxiliary energy consumption, in due

consideration of actual and normative operating parameters of station heat rate and auxiliary energy consumption on

monthly basis duly supported by relevant data verified by SLDC.

1. Coal/lignite based thermal generating stations:

i) Impact on the station heat rate:

The applicable factors for unit heat rate degradation at part loading for sub-critical and super-critical units are as

follows:

Unit Heat Rate degradation (%)

Sl.

No.

Unit loading (%)

Sub-critical

units

Super-critical

units

1

80 – 100

Nil

Nil

2

75-<80

3.0

2.5

3

70-<75

4.0

3.3

4

65-<70

5.1

4.1

5

60-<65

6.1

4.9

6

55-<60

7.6

6.0

7

50-<55

9.2

7.1

8

45-<50

11.3

8.3

9

40-<45

13.8

9.9

July 30, 2025]

TAMIL  NADU  GOVERNMENT  GAZETTE

81

ii) Impact on auxiliary energy consumption:

The admissible additional auxiliary energy consumption values at part loading of coal / lignite based thermal

generating stations are as follows:

Sl.

No.

Module / Plant loading

as % of installed

capacity

Admissible % degradation in

auxiliary energy consumption

(% point)

1

80 – 100

Nil

2

70-<80

1.1

3

60-<70

1.8

4

50-<60

2.5

5

40-<50

3.2

Provided that in case of additional auxiliary consumption arised due to implementation of DeSOx system and/or

DeNOx system, the generation company concerned may file appropriate petition before the Commission for revision of

parameters.

iii) Impact on Specific Fuel Oil Consumption:

Considering flexible operation requirement of coal based thermal stations in view of capacity addition from Renewable

sources, additional specific oil consumption of 0.2 ml/kWh is provided for units operating in 40-55% average loading.

2. Gas / liquid fuel based thermal generating stations:

i) Impact on station heat rate:

The degradation of module / plant gross heat rate for gas / liquid fuel based thermal generating stations in Combined

Cycle Gas Turbine mode of operation are as below:

Sl.

No.

Module / Plant loading as % of

installed capacity

Increase in Module/Plant heat

rate (%)

1

80-100

Nil

2

70-<80

5

3

60-<70

8

4

50-<60

12

ii) The degradation of module / plant heat rate for gas/liquid fuel based thermal generating stations in Open Cycle

mode of operation are as below:

Sl.

No.

Module / Plant loading as % of

installed capacity

Increase in Module/Plant heat

rate (%)

1

80-100

Nil

2

70-<80

7

3

60-<70

11

4

50-<60

16

iii) Impact on auxiliary energy consumption:

The additional auxiliary energy consumption admissible at part loading of gas / liquid fuel based thermal generating

station is proposed to be considered as below:

Sl.

No.

Module / Plant loading as % of

installed capacity

Admissible % additional auxiliary

energy consumption (% point)

1

80-100

Nil

2

70-<80

0.50

3

60-<70

0.80

4

50-<60

1.20

TAMIL NADU GOVERNMENT GAZETTE

82

[Part   VI—Sec. 2

1.3. In Regulation 37 of the Principal Regulations, after the clause (viii), the following clause shall be added, namely:

(ix) Transit losses of coal:

For coal and lignite, the transit and handling losses shall be as per the following norms:

Thermal Generating Station

Transit and Handling

losses (%)

Pit-head (using Rail/Road)

0.20%

Non-pit head (All rail route – where loading into railway rakes is done by coal company)

0.80%

Non-pit head (Road cum Rail or Sea Route – where coal is lifted from mines, transported

to good shed / other siding by road and then loading into railway rakes/Sea is done by

generating company or other multi-modal transportation system involving multiple

transshipments)

1.00%

Provided that in the case of any combination of the above modes of transportation, the transit and handling losses

shall be calculated on pro-rata basis using the formula given below:

Transit loss of coal / lignite based stations (%) = 0.2% x (Percentage of coal transported through pit-head source) +

0.8% x (Percentage of coal transported through All Rail Route) + 1.0% x (Percentage of coal transported through Road

cum Rail or Sea Route or other multi-modal transportation system involving multiple trans-shipments).

Provided further that in case of imported coal, the transit and handling losses applicable for pit-head station shall

apply.

(By Order of the Tamil Nadu Electricity Regulatory Commission)

Chennai - 600 032,

S. JOHN SUNDARARAJ,

10th July 2025.

Secretary (In-charge),

Tamil Nadu Electricity Regulatory Commission.

Explanatory Statement

The amendment to the TNERC (Terms and conditions for determination of Tariff) Regulations, 2005 is made by

including the new items namely “(ix) Impact of Part Load Operation on performance of Thermal Generating Stations and

(x) Transit losses of coal” due to the following reasons:

1. Tamil Nadu being the RE rich state and further potential for development of RE power projects, has to further

promote development of RE power within the State in line with the RPO trajectory notified by the Ministry of Power.

Accordingly, the Commission had earlier notified the Tamil Nadu Electricity Regulatory Commission (Renewable Energy

Purchase Obligation) Regulations, 2023.

2. Further, it is noted that the power generation mix is rapidly shifting towards a more significant share of Renewable

Energy in our country. Further, the Government of India’s vision is to achieve Net Zero emissions by 2070, in addition to

attain the short-term target of achieving 500 GW capacity by the year 2030.

3. Tamil Nadu is being the RE rich state, the generated RE power should be absorbed into the grid without any

curtailment. To absorb such RE power, which are infirm in nature, the existing State owned thermal power plants should

be ramped up and down very frequently, which results in increased station heat rate, auxiliary consumption, specific

fuel consumption, etc. Most of the State owned thermal power plants operate at lesser PLF than the normative PLF of

80%. Therefore, it is necessary either to compensate these State owned Power Plants or fixing some relaxed technical

parameters to these power plants.

4. It is pertinent to note that the Central Electricity Authority (CEA) vide their letter dated 15-03-2024 addressed to

the Hon’ble CERC suggested “relaxed operational parameters” for the thermal power stations being operated at part load.

5. The TANGEDCO in their recent true-up petitions filed before the Commission for the year 2022-23 has requested

to consider the actual operating parameters since the same is exceeded the normative operating parameters.

6. In order to safeguard the interest of the State owned Thermal Power Plants, the Commission has made this

amendment duly considering the parameters suggested by the CEA.

(By Order of the Tamil Nadu Electricity Regulatory Commission)

Chennai - 600 032,

S. JOHN SUNDARARAJ,

10th July 2025.

Secretary (In-charge),

Tamil Nadu Electricity Regulatory Commission.

July 30, 2025]

TAMIL  NADU  GOVERNMENT  GAZETTE

83

Statements showing existing provisions and provisions as amended

Amendment to Tamil Nadu Electricity Regulatory Commission

(Terms and conditions for determination of Tariff) Regulations, 2005

Sl.

No.

Existing Regulation

Regulation as amended

1.

37. Norms of Operation

(i) To (vii) xxx

"(vii) (a) where any of the Generating station is directed by

the State Load Despatch centre to operate below Target

plant availability factor but at or above technical minimum,

such generating station may be compensated depending

on the average unit loading duly taking into account the

forced outages, planned outages, PLF, generation at

generator terminal, energy sent out ex-bus, number of

start-stop, secondary fuel oil consumption and auxiliary

energy consumption, in due consideration of actual and

normative operating parameters of station heat rate and

auxiliary energy consumption on monthly basis duly

supported by relevant data verified by SLDC.

Provided that;

(i) In case of coal / lignite based generating stations,

following station heat rate degradation or actual heat rate,

whichever is lower, shall be considered for the purpose of

compensation:

Sl.

No.

Unit loading as

a % of installed

capacity of the

unit

Increase in

SHR (for

super-

critical

units) (%)

Increase in SHR

(for sub-critical

units) (%)

1

85-100

Nil

Nil

2

75-84.99

1.25

2.25

3

65-74.99

2

4

4

55-64.99

3

6

(ii) In case of coal/lignite based generating stations, the

following auxiliary energy consumption degradation or

actual, whichever is lower, shall be considered for the

purpose of compensation:

Sl.

No.

Unit loading as a % of

installed capacity of

the unit

% degradation in

AEC admissible

1

85-100

Nil

2

75-84.99

0.35

3

65-74.99

0.65

4

55-64.99

1

37. Norms of Operation

(i) To (vii) xxx

(viii) Impact of Part Load Operation on performance

of Thermal Generating Stations:

where any of the Generating station is directed by the

State Load Despatch centre to operate below Target plant

availability factor but at or above technical minimum,

such generating station may be compensated depending

on the average unit loading duly taking into account the

forced outages, planned outages, PLF, generation at

generator terminal, energy sent out ex-bus, number of

start-stop, secondary fuel oil consumption and auxiliary

energy consumption, in due consideration of actual and

normative operating parameters of station heat rate and

auxiliary energy consumption on monthly basis duly

supported by relevant data verified by SLDC.

1. Coal/lignite based thermal generating stations:

i) Impact on the station heat rate:

The applicable factors for unit heat rate degradation at

part loading for sub-critical and super-critical units are

as follows:

Unit Heat Rate degradation (%)

Sl.

No.

Unit loading (%)

Sub-critical

units

Super-

critical

units

1

80 – 100

Nil

Nil

2

75-<80

3.0

2.5

3

70-<75

4.0

3.3

4

65-<70

5.1

4.1

5

60-<65

6.1

4.9

6

55-<60

7.6

6.0

7

50-<55

9.2

7.1

8

45-<50

11.3

8.3

9

40-<45

13.8

9.9

ii) Impact on auxiliary energy consumption:

The admissible additional auxiliary energy

consumption values at part loading of coal / lignite

based thermal generating stations are as follows:

TAMIL NADU GOVERNMENT GAZETTE

84

[Part   VI—Sec. 2

(b) Compensation for the station Heat Rate and

Auxiliary Energy consumption shall be worked out in

terms of energy charges.

(c) The compensation so computed shall be borne by

the entity which has caused the plant to be operated at

schedule lower than corresponding to Normative Plant

Availability Factor up to technical minimum.

(d) No compensation for heat rate degradation and

auxiliary energy consumption shall be admissible if

the actual heat rate and / or actual auxiliary energy

consumption are lower than the normative station heat

rate and / or normative auxiliary energy consumption

applicable to the unit (or) the generating station.

(e) There shall be reconciliation of the compensation

at the end of the financial year in due consideration of

actual operational parameters of station heat rate and

auxiliary energy consumption.

(f) No compensation for heat rate degradation and

auxiliary energy consumption shall be admissible if

the actual heat rate and / or actual auxiliary energy

consumption are lower than the normative station heat

rate and / or normative auxiliary energy consumption

applicable to the unit or the generating station in a

month or after annual reconciliation at the end of the

year.

(ii) Impact on auxiliary energy consumption:

The admissible additional auxiliary energy consumption

values at part loading of coal / lignite based thermal

generating stations are as follows.

Sl.No.

Module / Plant

loading as % of

installed capacity

Admissible %

degradation in

auxiliary energy

consumption (% point)

1

80 – 100

Nil

2

70-<80

1.1

3

60-<70

1.8

4

50-<60

2.5

5

40-<50

3.2

Provided that in case of additional auxiliary

consumption arised due to implementation of DeSOx

system and/or DeNOx system, the generation company

concerned may file appropriate petition before the

Commission for revision of parameters.

iii) Impact on Specific Fuel Oil Consumption:

Considering flexible operation requirement of coal

based thermal stations in view of capacity addition from

Renewable sources, additional specific oil consumption

of 0.2 ml/kWh is provided for units operating in 40-

55% average loading.

2. Gas / liquid fuel based thermal generating

stations:

i) Impact on station heat rate:

The degradation of module / plant gross heat

rate for gas / liquid fuel based thermal generating

stations in Combined Cycle Gas Turbine mode of

operation are as below:

Sl.No.

Module / Plant loading

as % of installed

capacity

Increase in Module/

Plant heat rate (%)

1

80-100

Nil

2

70-<80

5

3

60-<70

8

4

50-<60

12

ii) The degradation of module / plant heat rate

for gas/liquid fuel based thermal generating stations

in Open Cycle mode of operation are as below:

Sl.No.

Module / Plant

loading as % of

installed capacity

Increase in Module/

Plant heat rate (%)

1

80-100

Nil

2

70-<80

7

3

60-<70

11

4

50-<60

16

July 30, 2025]

TAMIL  NADU  GOVERNMENT  GAZETTE

85

iii) Impact on auxiliary energy consumption:

The additional auxiliary energy consumption

admissible at part loading of gas / liquid fuel based

thermal generating station is proposed to be considered

as below:

Sl.No.

Module / Plant

loading as % of

installed capacity

Admissible %

additional auxiliary

energy consumption

(% point)

1

80-100

Nil

2

70-<80

0.50

3

60-<70

0.80

4

50-<60

1.20

2

37.

37.

(ix) Transit losses of coal:

For coal and lignite, the transit and handling losses shall

be as per the following norms:

Thermal Generating Station

Transit and

Handling

losses (%)

Pit-head (using Rail/Road)

0.20%

Non-pit head (All rail route – where

loading into railway rakes is done

by coal company)

0.80%

Non-pit head (Road cum Rail or Sea

Route – where coal is lifted from

mines, transported to good shed /

other siding by road and then load-

ing into railway rakes/Sea is done

by generating company or other

multi-modal transportation system

involving multiple transshipments)

1.00%

Provided that in the case of any combination of the above

modes of transportation, the transit and handling losses

shall be calculated on pro-rata basis using the formula

given below:

Transit loss of coal / lignite based stations (%) = 0.2% x

(Percentage of coal transported through pit-head source)

+ 0.8% x (Percentage of coal transported through All

Rail Route) + 1.0% x (Percentage of coal transported

through Road cum Rail or Sea Route or other

multi-modal transportation system involving multiple

trans-shipments).

Provided further that in case of imported coal, the transit

and handling losses applicable for pit-head station shall

apply.

(By order of the Tamil Nadu Electricity Regulatory Commission)

Chennai - 600 032,

S. JOHN SUNDARARAJ,

10th July 2025.

Secretary (In-charge),

Tamil Nadu Electricity Regulatory Commission.

TAMIL NADU GOVERNMENT GAZETTE

86

[Part   VI—Sec. 2

Nomination of member of the State Advisory Committee

(Notification No.TNERC/SACR/2-60 dated 08.07.2025)

(Lr.No. TNERC/Legal/1369/D.No.907/2025)

No. VI(2)/17/2025.

In exercise of the powers conferred on it by sub-section (1) and (2) of Section 87 of the Electricity Act,

2003 (Central Act No.36 of 2003) and as per Regulation 7 of the TNERC State Advisory Committee Regulations,

2004 the Tamil Nadu Electricity Regulatory Commission hereby nominate the following person as Member of the

State Advisory Committee for the area of ‘Labour’ for the period of three years with immediate effect:

S. No.

Name and address of Member

Area of Interest

1

Thiru.V. Govindan,

Former State Treasurer,

Electricity Board Workers’ Progress Association,

Assistant Account Officer (Retired),

No.106A, 9th Street,

North Jekanath Nagar,

Villivakkam – Chennai 600049.

Labour

Further, consequent to issuance of G.O. (Ms.) No.6, Energy (B2) Department, dated 24.01.2024, the erstwhile

Tamil Nadu Generation and Distribution Corporation Limited (TANGEDCO) was restructured into separate Generating

and Distribution Companies, under the Companies Act, 2013. Post this, it has been renamed as ‘Tamil Nadu

Power Distribution Corporation Limited’ (TNPDCL). As such, the erstwhile designation of Chairman & Managing

Director/TANGEDCO has to be revised as Chairman & Managing Director/TNEB limited & TNPDCL, Chairman/

TNPGCL, TANTRANSCO & TNGECL.

Accordingly, the following existing designation is revised for the area of interest of ‘Distribution Licensee’ as

follows:

Existing designation and Address

of Member

Revised designation and Address of

Member

Area of Interest

Chairman & Managing Director,

TNEB Limited

and TANGEDCO Limited,

No.144, Anna Salai,

Chennai 600 002.

Chairman & Managing Director,

TNEB Limited

& TNPDCL,

Chairman, TNPGCL, TANTRANSCO &

TNGECL,

No.144, Anna Salai,

Chennai 600 002.

Distribution

Licensee

Further, consequent to issuance of G.O. (Ms.) No.7, Energy (B2) Department, dated 24.01.2024, Tamil Nadu

Energy Development Agency (TEDA) has been merged with newly formed Tamil Nadu Green Energy Corporation

Limited (TNGECL) under the Companies Act, 2013 by integrating Renewable Energy wing of TANGEDCO. As

such the erstwhile post of Chairman & Managing Director/TEDA cease to exist and Managing Director/TNGECL

is entrusted with the functions of TNGECL.

Accordingly, the following existing designation is revised for the area of interest of ‘New and Renewable

Sources of Energy’ as follows:

July 30, 2025]

TAMIL  NADU  GOVERNMENT  GAZETTE

87

Existing designation and Address of

Member

Revised designation and Address of

Member

Area of Interest

Chairman and Managing Director,

Tamil Nadu Energy Development Agency

(TEDA),

5th Floor,

EVK Sampath Maaligai,

College Road, Chennai-600 006.

Managing Director,

Tamil Nadu Green Energy Corporation

Limited (TNGECL),

No.144, Anna Salai,

Chennai-600 002.

New and

Renewable

Sources of

Energy

(By Order of the Tamil Nadu Electricity Regulatory Commission)

Chennai - 600 032,

S. JOHN SUNDARARAJ,

9th July 2025.

Secretary (In-charge),

Tamil Nadu Electricity Regulatory Commission.

தமிழ்நாாடு மின்சாார ஒழுங்குமுறைை ஆணைை†யம், செென்னைை‰

தமிழ்நாாடு மின்சாார ஒழுங்குமுறைை ஆணைை†யம், செென்னைை‰

(அறிவிக்கைை எண்.த.மி.ஒ.ஆ/மாா.ஆ.கு.ஒ/2-60, நாாள்: 08.07.2025)

(Lr.No. TNERC/Legal/1369/D.No.907/2025)

2003 ஆம் ஆண்டு மின்சாாரச் சட்டத்தின் (மத்தியச் சட்டம் 36/2003) 87 ஆம் பிரிவின் (1) மற்றும் (2) ஆம் உட்பிரிவு மற்றும்

2004 ஆம் ஆண்டு தமிழ்நாாடு மின்சாார ஒழுங்குமுறைை ஆணைை†ய – மாாநில ஆலோ�ோசனைை

‰க் குழு ஒழுங்குமுறைை விதிகளின்,

ஒழுங்குமுறைை விதி 7 ஆகியவற்றினால் அதற்கு வழங்கப்பட்ட அதிகாரங்களைை

யும் செெலுத்தி, தமிழ்நாாடு மின்சாார ஒழுங்குமுறைை

ஆணைை†யம் பின்வரும் நபரைை ‘தொ�ொழிலாளர்’ பிரதிநிதித்துவத்திற்கான மாாநில ஆலோ�ோசனைை

‰க் குழுவின் உறுப்பினராக மூன்று

ஆண்டு காலத்திற்கு உடனடியாக அமலுக்கு வரும் வகைையில் நியமன

ம் செெய்கிறது.

வரிசைை

எண்

உறுப்பினர் பெெயர்

மற்றும் முகவரி

பிரதிநிதித்துவம்

செெய்யும் துறைை

1

வ.கோ�ோவிந்தன்,

முன்னாள் மாாநில பொ�ொருளாளர்,

மின்கழக தொ�ொழிலாளர் முன்னே‰ற்ற சங்கம்,

உதவி கணக்கு அலுவலர் (ஓய்வு),

க.எண். 106A, 9 வது தெெரு,

வடக்கு ஜெெƒகநாாத நகர், வில்லிவாக்கம்,

செென்னைை‰-600049.

தொ�ொழிலாளர்

மே�லும், 24.01.2024 தே�தியிட்ட அரசாாணைை† (Ms.) எண்.6, எரிசக்தி (B2) துறைையின் வெ�ளியீட்டின் விளைை

வாக, 2013 ஆம்

ஆண்டு நிறுவனங்கள் சட்டத்தின் கீழ் முந்தைைய தமிழ்நாாடு மின் உற்பத்தி மற்றும் பகிர்மாானக் கழக லிமிடெெட் (TANGEDCO),

தற்போ�ோது மின்உற்பத்தி மற்றும் பகிர்மாான நிறுவனமாாக தனித்தனியாகப் பிரிக்கப்பட்டது. இதன் பின்னர், ‘தமிழ்நாாடு மின்

பகிர்மாானக் கழக லிமிடெெட்’ (TNPDCL) என மறுபெெயரிடப்பட்டது. இதன் காரணமாாக, முந்தைைய தலைைவர் மற்றும் மே�லாாண்மைை

இயக்குநர்/TANGEDCO பதவியைை, தலைைவர் மற்றும் மே�லாாண்மைை இயக்குநர், TNEB லிமிடெெட் & TNPDCL, தலைைவர்/TNPGCL,

TANTRANSCO & TNGECL என திருத்தப்பட வே�ண்டும்.

அதன்படி, ‘மின்பகிர்மாான உரிமதாாரரின்’ பிரதிநிதித்துவத்திற்கான தற்போ�ோதைைய பதவி பின்வருமாாறு திருத்தப்படுகிறது:

தற்போ�ோதுள்ள உறுப்பினரின் பதவி

மற்றும் முகவரி

திருத்தப்பட்ட உறுப்பினரின் பதவி

மற்றும் முகவரி

பிரதிநிதித்துவம்

செெய்யும் துறைை

தலைைவர் மற்றும் மே�லாாண்மைை இயக்குநர்,

TNEB லிமிடெெட் மற்றும் TANGEDCO லிமிடெெட்,

எண்.144, அண்ணா சாாலைை,

செென்னைை‰-600 002 .

தலைைவர் மற்றும் மே�லாாண்மைை இயக்குநர்,

TNEB லிமிடெெட் & TNPDCL, தலைைவர்/

TNPGCL, TANTRANSCO & TNGECL,

எண்.144, அண்ணா சாாலைை,

செென்னைை‰-600 002.

மின்பகிர்மாான

உரிமம்தாரர்

TAMIL NADU GOVERNMENT GAZETTE

88

[Part   VI—Sec. 2

மே�லும், 24.01.2024 தே�தியிட்ட அரசாாணைை† (Ms.) எண்.7, எரிசக்தி (B2) துறைையின் வெ�ளியீட்டின் விளைை

வாக, 2013 ஆம்

ஆண்டு நிறுவனங்கள் சட்டத்தின் கீழ், ‘தமிழ்நாாடு எரிசக்தி வளர்ச்சி முகமைையாானது’ (TEDA), தற்போ�ோது TANGEDCO வின்

புதுப்பிக்கத்தக்க எரிசக்தி பிரிவைை ஒருங்கிணைை†த்து, புதிதாக உருவாக்கப்பட்ட தமிழ்நாாடு பசுமைை எரிசக்தி நிறுவனத்துடன் (TNGECL)

ஒன்றிணைை†க்கப்பட்டுள்ளது. இதன் காரணமாாக, முந்தைைய தலைைவர் மற்றும் மே�லாாண்மைை இயக்குநர்/TEDA பதவி நீக்கப்பட்டு,

தமிழ்நாாடு பசுமைை எரிசக்தி நிறுவனத்தின் செெயல்பாடுகள் மே�லாாண்மைை இயக்குநர்/TNGECL-லிடம் ஒப்படைைக்கப்பட்டுள்ளன.

அதன்படி, ‘புது மற்றும் புதுப்பிக்கத்தக்க எரிசக்தி ஆதாரங்கள்’ என்ற பிரதிநிதித்துவத்திற்கான தற்போ�ோதுள்ள பதவி

பின்வருமாாறு திருத்தப்படுகிறது:

தற்போ�ோதுள்ள உறுப்பினரின் பதவி

மற்றும் முகவரி

திருத்தப்பட்ட உறுப்பினரின் பதவி

மற்றும் முகவரி

பிரதிநிதித்துவம்

செெய்யும் துறைை

தலைைவர் மற்றும் மே�லாாண்மைை இயக்குநர்,

தமிழ்நாாடு எரிசக்தி வளர்ச்சி முகமைை,

5 வது தளம், ஈ.வி.கே�. சம்பத் மாாளிகைை,

கல்லூரி சாாலைை, செென்னைை‰-600 006.

மே�லாாண்மைை இயக்குநர், தமிழ்நாாடு பசுமைை

எரிசக்தி நிறுவனம்,

எண்.144, அண்ணா சாாலைை,

செென்னைை‰-600 002.

புது மற்றும்

புதுப்பிக்கத்தக்க

எரிசக்தி ஆதாரங்கள்

(தமிழ்நாாடு மின்சாார ஒழுங்குமுறைை ஆணைை†யத்தின் ஆணைை†ப்படி)

செென்னைை‰ 600 032,

எஸ்.ஜான் சுந்தரராஜ்

எஸ்.ஜான் சுந்தரராஜ்,

2025 ஜூலைை 9.

செெயலாளர் (பொ�ாறுப்பு),

தமிழ்நாாடு மின்சாார ஒழுங்குமுறைை ஆணைை†யம்.

PRINTED  AND  PUBLISHED  BY  THE COMMISSIONER  OF  STATIONERY  AND  PRINTING, CHENNAI

ON  BEHALF  OF  THE  GOVERNMENT  OF  TAMIL  NADU