Panaji, 9th August, 2023 (Sravana 18, 1945)
SERIES I No. 18
Reg. No. RNP/GOA/32/2021-2023
RNI No. GOAENG/2002/6410
PUBLISHED BY AUTHORITY
GOVERNMENT OF GOA
Department of Town & Country Planning
–––
Notification
21/1/TCP/2021-23/Steering Committee/105
Whereas, the draft regulations, namely, the
Goa Land Development and Building
Construction (Amendment) Regulations, 2021
which the Government of Goa proposed to
make in exercise of the powers conferred by
sub-sections (1) and (2) of section 4 of the Goa
(Regulation of Land Development and Building
Construction) Act, 2008 (Goa Act 6 of 2008)
(hereinafter referred to as the “said Act”) so
as to further amend the Goa Land
Development and Building Construction
Regulations, 2010, were pre-published as
required by section 5 of the said Act vide the
Government Notification No. 21/1/TCP(A)/
/2021/Steering
Committee/993
dated
22-06-2021, published in the Official Gazette,
Series I No. 14 dated 01-07-2021, inviting
objections and suggestions from all persons
likely to be affected thereby within 30 days
from the date of publication of the said
Notification in the Official Gazette;
And whereas, the said Official Gazette was
made available to the public on 01-07-2021;
And
whereas,
the
objections
and
suggestions received from the public on the
said draft Regulations have been considered
EXTRAORDINARY
No. 2
1731
Suggestions are welcome on e-mail: dir–[email protected]
by the Sub-Committee appointed under
sub-section (2) of section 6 of the said Act and
submitted its report to the Steering Committee
constituted under sub-section (1) of section 6
of the said Act vide the Government
Notification No. 21/1/TCP/2018/SC/481 dated
22-02-2018, published in the Official Gazette,
Series II No. 48 dated 01-03-2018;
And whereas, the Steering Committee after
considering the report of the Sub-Committee
submitted
its
report
together
with
recommendations to the Government;
And whereas, the Government has
considered the report and recommendations
of the Steering Committee and approved the
same and directed the Chief Town Planner
(Land Use) to notify the Amendment
Regulations in the Official Gazette.
Now, therefore, in exercise of the powers
conferred by sub-sections (1) and (2) of section
4 of the Goa (Regulation of Land Development
and Building Construction) Act, 2008 (Goa Act
6 of 2008) and all other powers enabling it in
this behalf, the Government of Goa hereby
makes the following regulations so as to
further amend the Goa Land Development and
Building Construction Regulations, 2010,
namely:—
1. Short title and commencement.— (1)
These regulations may be called the Goa Land
Development and Building Construction
(Amendment) Regulations, 2023.
OFFICIAL GAZETTE — GOVT. OF GOA
SERIES I No. 18
(EXTRAORDINARY No. 2)
9TH AUGUST, 2023
1732
(2) They shall come into force on the date
of their publication in the Official Gazette.
2. Amendment of regulation 2.— In
regulation 2 of the Goa Land Development and
Building Construction Regulations, 2010
(hereinafter referred to as the “principal
Regulations”),—
(i) in clause (17), for the expression “Fire
and Life Safety as per National Building Code
2005”, the words “Part 4 of the National
Building Code of India 2016” shall be
substituted;
(ii) in clause (20A), for sub-clause (h), the
following sub-clause shall be substituted,
namely:—
“(h) “High Rise Building” means a
building 15 meters or above in height
(irrespective of its occupancy);”;
(iii) for clause (66), the following clause
shall be substituted, namely:—
“(66) “Fire resistant materials” means
and includes those materials serving
appropriate fire resistance rating as per
the relevant provisions of National
Building Code of India, 2016 as amended
from time to time and relevant Bureau of
Indian Standards (BIS) Codes.”;
(iv) clause (77) shall be omitted;
(v) after clause (86), the following clause
shall be inserted, namely:—
“(86A) “National Building Code of
India, 2016” means the National Building
Code of India, 2016 as amended from time
to time;”.
3. Amendment of regulation 3.6.2.— In
regulation 3.6.2 of the principal Regulations,
for clause (c), the following clause shall be
substituted, namely:—
“(c) In case of the buildings specified in
regulation 15.2.1, No Objection Certificate
from the Director of Fire and Emergency
Services shall be obtained by the owner
before applying for Construction License to
the Local Authority.”.
4. Amendment of regulation 3.11.— In
regulation 3.11 of the principal Regulations,
for clause (b), the following clause shall be
substituted, namely:—
“(b) Clearance from the Directorate of Fire
and Emergency Services before issue of
Occupancy Certificate shall be required for
the buildings specified in regulation 15.2.1.”.
5. Amendment of regulation 6A.5.— In
regulation 6A.5 of the principal Regulations,
for clause (2), the following clause shall be
substituted, namely.—
“(2) In case of building on stilts or
building with basements, the height of the
buildings shall be measured from the top of
the stilts/basement. However, if the building
height is 15 meters or more from the
ground. Fire and Life Safety Regulations
shall be applicable.”.
6. Amendment of regulation 13.10.— In
regulation 13.10, of the principal Regulations,
in clause (b), item (iii) shall be omitted.
7. Amendment of regulation 13.11.— In
regulation 13.11, of the principal Regulations,
for clause (c), the following clause shall be
substituted, namely.—
“(c) The requirements for installation of
Lifts, Escalators and Moving Walks shall be
as per provisions of part 8 of the National
Building Code of India 2016.”.
8. Substitution of regulation 15.— For
regulation 15 of the principal Regulations, the
following regulation shall be substituted,
namely:—
“15. Fire and life safety requirements:—
15.1.1. General Provisions:—
Buildings specified in regulation 15.2.1 shall
be planned, designed and constructed to
ensure adequate fire safety of the buildings,
property and inhabitants and this shall be
carried out in accordance with the provisions
of Part 4 of the National Building Code of India,
2016 except clauses 3.2 and 3.4.4 thereof and
any other provisions of the fire safety made in
these regulations. Fire Fighting requirement
arrangement and installations required in the
OFFICIAL GAZETTE — GOVT. OF GOA
SERIES I No. 18
(EXTRAORDINARY No. 2)
9TH AUGUST, 2023
1733
building shall also be as per the provisions of
the Part 4 of the National Building Code of India,
2016. All the technical terms shall have the
meaning as defined in Part 4 of the National
Building Code of India, 2016 except the terms
which are defined in these regulations.
15.1.2. Notwithstanding anything contained
in regulation 4.2. (g) and 4.4.2 for high rise
buildings, the following provisions of means
of access and open spaces (set backs) shall
be ensured:
(a) The width of the main street on which
the building abuts shall not be less than 10
meters;
(b) The approach to the building and open
spaces on all its sides shall be not less than 6
meters in width, the layout for the same shall
be done to the satisfaction of the Directorate
of Fire and Emergency Services and the open
space shall be of hard surface capable of
taking the mass of fire engine weighing up to
45 tonnes. A turning radius of atleast 9 meters
shall be provided for movement of fire service
vehicles. The said open space shall be kept
free of obstructions and shall be motorable,
further no projections shall be allowed in the
said open spaces. In case of buildings with no
side set backs or setbacks with 1.5 meters or
less, a clear height of atleast 5 meters shall be
maintained below the bottom of lowest
structural member and the open space as
aforesaid shall be made available through the
building on all sides for movement of fire
service vehicles.
(c) The main entrance of the plot shall be of
adequate width to allow easy access to the
fire service vehicles and in no case it shall
measure less than 6 meters. The entrance
gate shall fold back against the compound wall
of the premises, thus leaving the exterior
access way within the plot free for movement
of fire service vehicle. If the main entrance at
the boundary wall is built over, the minimum
clearance shall be 5 meters.
15.2. Requirement for Fire Dept Clearance:—
15.2.1.
The
NOC
from
Director,
Directorate of Fire and Emergency Services
shall be obtained by the Owner/Developer
before applying for construction license to
the local authority and also before applying
for occupancy certificate to local authority
in case of,—
(a) highrise buildings; and
(b) special building such as (i) hotel,
educational, institutional, business,
mercantile, industrial, storage, hazardous
and mixed occupancies, where any of these
buildings have floor area more than 500
square meter on any one or more floors;
(ii) educational building having height of
9 meters or above;
(iii) institutional building having height
of 9 meters or above;
(iv) assembly building;
(v) building, having area more than 300
square meter of incidental assembly
occupancy on any floor; and
(vi) building with two basements or more,
or with one basement of area more than 500
square meters.
15.2.2. Above buildings shall be as per Part
4 of the National Building Code of India, 2016.
15.2.3. Any alterations/modifications/
/renovation for floor area exceeding 500
square meters for all high rise buildings shall
also require No objection certificate from
Director, Directorate of Fire and Emergency
Services (DFES) before applying for license to
the local authority
15.3. Records, documents, application
forms, fees, fire drills and appointment of fire
officer at the premises, if any, shall be as
specified by the Directorate of Fire and
Emergency Services for issue of Clearance
(NOC).
15.4.Classification of Buildings Based on
Occupancy:
15.4.1. All buildings, whether existing or
hereafter erected shall be classified according
to use or the character of occupancies in the
following groups:
Group
Occupancy
Group A
Residential
Group B
Educational
OFFICIAL GAZETTE — GOVT. OF GOA
SERIES I No. 18
(EXTRAORDINARY No. 2)
9TH AUGUST, 2023
1734
Group C
Institutional
Group D
Assembly
Group E
Business
Group F
Mercantile
Group G
Industrial
Group H
Storage
Group J
Hazardous
15.4.2. The above classification of buildings
is for the purpose of Fire and Life Safety and
the same is as per clause 3.1.1 of Part 4, of the
National Building Code of India, 2016. The
details of each occupancy and example of
buildings in each group are as per clause 3.1.2
to 3.1.10 and Mixed occupancy if any shall be
as per clause 3.1.1.2 and 3.1.11 of Part 4 of the
National Building Code of India, 2016.
15.5. Fire Resistance of various Types of
Construction/Building Components:—
The minimum fire resistance ratings of
structural and non-structural members for
various types of construction shall be as
specified in clause 3.3, of Part 4 of the National
Building Code of India, 2016 and to the
satisfaction of the Directorate of Fire and
Emergency Services.
15.6. Glazing:—
The glazing shall be in accordance with
provisions contained in section 8 of Part 6 of
the National Building Code of India, 2016. The
entire glazing assembly shall be rated to the
type of construction as given in Table I as
specified in clause 3.4.1 of Part 4 of the National
Building Code of India, 2016. The use of glass
shall not be permitted for enclosures of exits
and exit passageway.
15.7. Glass facade:—
Glass facade shall be in accordance with
clause 3.4.10.2 of Part 4 of the National Building
Code of India, 2016.
15.8. Occupant Load:—
15.8.1. For determining the exits required,
the number of persons within any floor area
or the occupant load shall be based on the
actual number of occupants declared, but
in no case less than that specified in Table
XXI. The occupant load of a mezzanine floor
discharging to a floor below shall be added
to that floor occupancy and the capacity of
the exits shall be designed for the total
occupancy load thus established.
15.8.2. The occupant load of each storey
considered individually shall be required to
be used in computing the number of means
of egress at each storey, provided that the
required number of means of egress is not
decreased in the direction of egress travel.
15.8.3. The capacity of any open
mezzanine/balcony shall be added to the
capacity of the floor below for the purpose
of determining exit capacity.
15.8.4. The assembly occupancies and
call centres shall be required to display,
limiting occupant load details positioned in
a conspicuous place near the entrance of
each of such respective occupancy to avoid
possible overcrowding and overloading to
the satisfaction of the Directorate of Fire and
Emergency Services. The display shall
preferably be engraved on a metal plate of
not less than 300 mm X 200 mm, with letters
of height and width not less than 50 mm,
with detail of occupancy, area and
occupancy load (see Sketch No. 10.).
TABLE-XXI
Occupant Load
Sr.
Group of Occupancy
Occupant Load
No.
Factor
(m2/person)
(See Note 1)
1
Group A: Residential
12.50
2
Group B: Educational
4.00
3
Group C: Institutional (see Note 2)
a) Indoor patients area
15.00
b) Outdoor patients area
10.00
4
Group D: Assembly:
a) Concentrated use without
fixed seating
0.65
b) Less Concentrated use without
fixed seating (see Note 3)
1.40
c) Fixed Seating
See Note 4
OFFICIAL GAZETTE — GOVT. OF GOA
SERIES I No. 18
(EXTRAORDINARY No. 2)
9TH AUGUST, 2023
1735
d) Dining areas and restaurants
with seating and table
1.80
5
Group E: Business
10.00
6
Group F: Mercantile
a) Street floor and sales basement
3.00
b) Upper sale floors
6.00
c) Storage/warehouse and the like
20.00
6
Group G: Industrial
10.00
7
Group H: Storage (see Note 5)
30.00
8
Group J: Hazardous
10.00
Notes:
(1) Gross area shall be the area of the floor
within the inside perimeter of the outside
walls of the floor of the building under
consideration with no deductions for corridors
and passage-ways, stairs, closets, thickness
of interior walls, columns, lifts and building
shafts or other features. However the
proponent may consider the area including
the outside wall thickness, if he so desires. All
factors expressed are in gross area unless
marked net.
(2) Occupant load in dormitory portions of
homes for the aged, orphanages, insane
asylums, etc, where sleeping accommodation
is provided, shall be calculated at not less than
7.5 m2 gross floor area per person.
(3) These shall include gymnasium, table
tennis room, billiard room and other gaming
rooms, library, swimming pool and like.
(4) In case of assembly occupancy having
fixed seats, the occupant load shall be
determined by multiplying the number of seats
by 1.2.
(5) Car parking areas under occupancy
other than storage shall also be 30 square
meter per person.
15.9. Exit Requirements:—
15.9.1. Every building meant for human
occupancy shall be provided with exits
sufficient to permit safe escape of occupant,
in case of fire or other emergency as per
clauses 4.2 to 4.4.2.5 of Part 4 of the National
Building Code of India, 2016/this part of
regulations.
15.9.2. General Requirements:—
The following general requirements shall
apply to exits.—
(a) Unless otherwise specified, lifts,
escalators, moving walks and revolving
doors shall not be considered as exits and
shall not constitute any part of the required
exit.
(b) Every exit, exit passageway and exit
discharge shall be continuously maintained
free of all obstructions or impediments to
full use in the case of fire or other emergency.
(c) Every building having human
occupancy shall be provided with exits
sufficient to permit safe egress of occupants
in case of fire or other emergency.
(d) In every building or structure, exits
shall
comply
with
the
minimum
requirements of this Part of regulations,
except those not accessible for general
public use.
(e) No building shall be so altered as to
reduce the number, width or protection of
exits to less than that required.
(f) For non-naturally ventilated areas, fire
doors with 120 minutes fire resistance
rating shall be provided and particularly at
the entrance to lift lobby and stair well
where a ‘funnel or flue effect’ may be
created, inducing an upward spread of fire,
to prevent spread of fire and smoke.
(g) Exits shall be so arranged that they
may be reached without passing through
another occupied unit/passage in others
control, if they pose challenge or restriction
in means of egress.
(h) Doors in exits shall open in the
direction of exit. In case of Group D
Assembly Buildings and Group C
Institutional Buildings (Subdivision C-1
Hospitals and sanatoria), exit door shall not
open immediately upon a flight of stair and
all such entries to the stair shall be through
a landing, so that such doors do not impede
movement of people descending from a
higher floor when fully opened (see Sketch
No. 8 A). While for other occupancies, such
doors shall not reduce the pathway in the
landing by more than half the width of such
staircase (see Sketch No. 8 B). Overhead or
sliding doors shall not be installed.
OFFICIAL GAZETTE — GOVT. OF GOA
SERIES I No. 18
(EXTRAORDINARY No. 2)
9TH AUGUST, 2023
1736
(i) At least half of the required exit stairs
from upper floors (rounded to the next
higher number) shall discharge directly to
the exterior or through exit passageways.
(j) Unless otherwise specified, all the exits
and exit passageways to exit discharge shall
have a clear ceiling height of at least 2.4
meter. However, the height of exit door
shall be at least 2.0 meter (see Sketch No.
9.)
(k) Where changes in elevation of more
than 300 mm are encountered in the exits,
ramps or sloped surfaces shall be used with
handrails and floor finish materials that
contrast with the adjacent finish materials.
(l) The capacity of the means of egress
required from any storey of the building
shall not be reduced along the path of
egress travel until arrival to the exit
discharge.
(m) The lifts, escalators, moving walks,
turnstiles and revolving doors shall not be
considered in determining the required
capacity of means of egress for the
individual floors or the building.
(n) Turnstiles or similar devices that
restrict travel to one direction or that are
used to restrict unauthorized entry shall not
be so placed as to obstruct any required
means of egress. Alternative door openings
of required exit width shall be available
within 3 meter of such devices, if installed.
(o) Suitable means shall be provided so
that all access controlled exit doors,
turnstiles, boom barriers and other such
exits shall automatically operate to open
mode during emergencies like fire, smoke,
acts of terrorism, etc, so that people can
safely and quickly egress into safe areas
outside. If required, a master controlling
device may be installed at a strategic
location to achieve this.
(p) Penetrations into and openings
through an exit are prohibited except those
necessary like for the fire protection piping,
ducts for pressurization and similar life
safety services. Such openings as well as
vertical passage of shaft through floors shall
be protected by passive systems.
(q) Walking surfaces in exit access shall
comply with the following requirements for
smooth exit:
(i) Walking surfaces shall be nominally
levelled.
(ii) The slope of walking surface in the
direction of travel shall not exceed 1 in
20 unless the ramp requirements are met.
(iii) Slope perpendicular to the direction
of travel shall not exceed 1 in 48.
(iv) Walking surfaces shall be slip
resistant along the entire path of travel.
15.9.3. Number of Exits:— The minimum
required number of exits in a building shall
be determined based on occupant load (see
Table XXI as specified in regulation 15.8.1) and
width required per person (see Table XXII as
specified in regulation 15.9.5) as appropriate
to the type of exit for respective occupancies,
subject to complying with maximum travel
distance requirement (see Table XXIII as
specified in regulation 15.9.6).
15.9.4. Arrangement of Exits:—
(a) Exits shall be so located that the travel
distance on the floor shall not exceed the
distance given in Table XXIII as specified in
regulation 15.9.6.
(b) Travel distance shall be measured
from the most remote point within a storey
or a mezzanine floor along the natural and
un-obstructed path of horizontal or vertical
egress travel to the door to an exit.
(c) The dead end corridor length in exit
access shall not exceed 6 meters for
educational, institutional and assembly
occupancies. For other occupancies, the
same shall be 15 meter (see Sketch No. 11.).
(d) Exits shall be placed as remote from
each other as possible and shall be
arranged to provide direct access in
separate directions from any point in the
area served.
OFFICIAL GAZETTE — GOVT. OF GOA
SERIES I No. 18
(EXTRAORDINARY No. 2)
9TH AUGUST, 2023
1737
15.9.5. Capacity of Exits:—
(a) Exit capacity is the number of people
that can pass through a stairway, level
components (door and corridor) and ramps.
The total capacity of all the respective means
of egress serving a floor shall be sufficient
to allow egress of the entire population of
the floor.
(b) The unit of exit width, used to measure
the capacity if any exit, shall be 500 mm. A
clear width of 250 mm shall be counted as
an additional half unit. Clear width less than
250 mm shall not be counted for exit width.
(c) Width per person for stairways, level
components and ramps shall be determined
using the capacity factors in accordance
with Table XXII.
Note: If an exit doorway measures 1,000 mm
in clear width, it would be defined as providing
exit capacity for 1,000/6.5 occupants, that is,
153 persons (say 150 persons) and number of
such exit doorways can then be calculated
depending on the occupant load.
TABLE-XXII
Capacity Factors
Sr.
Occupancy Group
Width per Person mm
No.
Stairways
Level
Components
and Ramps
1 Residential (Group A)
10
6.5
2 Educational (Group B)
3 Institutional (Group C)
15
13
4 Assembly (Group D)
5 Business (Group E)
6 Mercantile (Group F)
10
6.5
7 Industrial (Group G)
8 Storage (Group H)
9 Hazardous (Group J)
18
10
(d) When calculating stairways, level
components and ramps and other exit
means, the capacity of the entire system
shall have to be based upon the minimum
capacity available from any part of the
system. The corridor, if so provided shall
also to be planned with consideration of exit
access adequacy for the number of
occupants. Further, the situation of doors
opening to an exit stairway shall be
considered. If the stairway provides an exit
capacity of 150 persons, and the doors
leading into the stairway provide an exit
capacity of 153 persons, the overall exit
system would be considered to provide the
minimum exit capacity of only 150 persons
afforded by the stairway. The exit planning
will be limited by the most restrictive exit
calculation under the means of egress.
(e) In the procedures for determining
required egress capacity, the number of
required means of egress is based on a floor-
by-floor consideration, rather than the
accumulation of the occupancy loads of all
the floors. However, the number of means
of egress cannot decrease as an occupant
proceeds along the egress path.
15.9.6. Types of Exit access and exits:—
Various types of exit access and exits are
doorways, corridors and passageways,
horizontal exits, internal staircases, exit
passageways, external staircases and ramps.
TABLE-XXIII
Travel Distance (Based on Occupancy and
Construction Type)
Sl.
Occupancy Group
Maximum Travel
No.
Distance (m)
Types 1
Types 3
and 2
and 4
1
Residential (Group A)
30.00
22.50
2
Educational (Group B)
30.00
22.50
3
Institutional (Group C)
30.00
22.50
4
Assembly (Group D)
30.00
30.00
5
Business (Group E)
30.00
30.00
6
Mercantile (Group F)
30.00
30.00
7
Industrial (Group G)
G-1, G-2
45.00
G-3
22.50
8
Storage (Group H)
30.00
9
Hazardous (Group J)
22.50
}
}
}
See
Note c
OFFICIAL GAZETTE — GOVT. OF GOA
SERIES I No. 18
(EXTRAORDINARY No. 2)
9TH AUGUST, 2023
1738
Notes: (a) For fully sprinklered building, the
travel distance may be increased by 50
percent of the values specified.
(b) Ramp shall not be counted as an exit in
case of basements below the first basement
in car parking.
(c) Construction of Type 3 or Type 4 is not
permitted.
15.9.7. Doorways:—
(a) Every exit doorway shall open into an
enclosed stairway or a horizontal exit of a
corridor
or
passageway
providing
continuous and protected means of egress
(see Sketch No. 12. on unaccepted
arrangement of doors in a stair).
(b) No exit doorway shall be less than
1,000 mm in width except assembly
buildings, where door width shall be not
less than 2,000 mm (see Sketch No. 13.).
Doorways shall not be less than 2,000 mm
in height (Doorway for bathroom, water
closet etc. shall not be less than 750mm in
width. However in case of disabled friendly,
the door widths in case of toilets shall be
as specified in Rights of Persons with
Disabilities Rules, 2017 as amended from
time to time, and for other uses they shall
be 1000mm or as per Rights of persons with
Disabilities Rules, 2017 whichever is
higher).
(c) Exit doorways shall be operable from
the side which they serve, without the use
of a key.
(d) Mirrors shall not be placed on exit
doors and in exits to avoid confusion
regarding the direction of exit.
(e) Revolving doors can be accepted as a
component in a means of egress where the
following requirements are fully complied
with, namely:—
(i) Doors shall be capable of collapsing
to a book fold position with parallel egress
paths, of width not less than 1,000 mm.
(ii) Doors shall not be located within 3
meters of the foot or top of stairs or
escalators. A dispersal area shall be
provided between the stairs or escalators
and the doors.
(iii) Each revolving door shall be
provided with a hinged door in the same
wall within 3 meters thereof, with same
exiting capacity.
(iv) Each revolving door shall be
considered as capable of exiting only 50
persons.
(f) All fire rated doors and assembly shall
be provided with certificate and labels
prominently indicating the manufacturer’s
identification, door details covering door
type, serial/batch number, month and year
of manufacture, fire resistance rating, etc.
The doors and assembly shall be certified
with all prescribed hardware such as
hinges, locks, panic bars, door closer and
door viewers.
(g) Access controlled doors – Access
controlled doors and electromagnetic doors
shall meet the following requirements,
namely:—
(i) Doors shall have fire rating as per
the requirements at the location of
installation.
(ii) Activation of the building automatic
sprinkler or fire detection system, if
provided, shall automatically unlock the
doors in the direction of egress, and the
doors shall remain unlocked until the
automatic sprinkler system or fire-alarm
system has been manually reset.
(iii) Loss of power to the part of the
access control system that locks the
doors shall automatically unlock the
doors in the direction of egress.
(iv) A manual release device shall be
provided in the readily accessible vicinity
of the egress door with a signage ‘PUSH
TO EXIT’ and when the same is operated,
it shall result in direct interruption of
power to the lock, independent of the
access control system electronics.
(h) Turnstiles– Turnstiles or similar
devices that restrict travel to one direction
OFFICIAL GAZETTE — GOVT. OF GOA
SERIES I No. 18
(EXTRAORDINARY No. 2)
9TH AUGUST, 2023
1739
or are used to collect fares or admission
charges shall not be placed so as to obstruct
any required means of egress unless door
openings of required width are available
within 3 meters thereof and they shall be
disengaged through automatic or manual
intervention to allow egress in the direction
of exit.
(i) Doors in folding partition shall not be
treated as approved means of egress.
15.9.8. Corridors and passage ways:—
(a) Corridors and passageways shall be
of width not less than the calculated
aggregate width of exit doorways leading
from them in the direction of travel to the
exit (see table XXII and table XXIII as
specified in regulation 15.9.5 and 15.9.6
respectively.)
(b) In the case of buildings where there
is a central corridor, which is part of exit
access, the doors of rooms (except for rooms
having assembly occupancy) shall open
inwards to permit smooth flow of traffic in
the corridor.
15.9.9. Staircases:—
(I) General:
(A) The requirements of number of
staircases
shall
supplement
the
requirement of different occupancies as per
clause 6.1 to 6.9 of Part 4 of the National
Building Code of India, 2016.
(B) All buildings, as specified in
regulation 15.2.1 shall have a minimum of
two staircases. The actual number of
staircases
shall
comply
with
the
requirement of 15.9.3.
(C) All exit staircases shall discharge, at
the level of exit discharge, to the exit
discharge, either,—
(i) directly, or
(ii) through an exit passageway, or
(iii) through a large lobby.
(D) At least 50 percent of the staircases
shall discharge as per (i) and/or (ii) above.
(E) The minimum width of tread without
nosing shall be 250 mm for staircase of
residential buildings. This shall be minimum
300 mm for assembly, hotels, educational,
institutional, business and other buildings.
The treads shall be constructed and
maintained in a manner to prevent slipping.
The maximum height of riser shall be 150
mm.
(F) The number of risers shall be limited
to 12 per flight. The staircases may be
internal staircases or external staircases.
(G) Only enclosed staircase including its
doorof required fire resistance and rating
shall be considered for the purpose of this
part of regulations (and shall have details
as per regulation 15.9.7 (f).
(II) Internal Staircases: The internal
staircases may be constructed with an
external wall, or otherwise, and shall comply
with the following requirements, namely:—
(a) Internal stairs shall be constructed of
non-combustible materials throughout, and
shall have fire resistant rating of minimum
120 minutes.
(b) A staircase shall not be arranged
round a lift shaft.
(c) Exits shall not be used as a portion of
a supply, return or exhaust air system
serving adjoining areas. Any opening(s)
shall not be permitted in walls or in doors,
separating exits from adjoining areas.
(d) No flue chimney, electromechanical
equipment, air conditioning units, gas
piping or electrical panels shall be allowed
in the stairway.
(e) Notwithstanding the detailed
provision for exits in accordance with
Regulations 15.8 and 15.9. The following
minimum width shall be provided for
staircases for respective occupancies:
(i) Residential (A-2): 1.00 meters
(ii) Residential (A-1, A-3 and A-4): 1.25
meters
(iii) Residential Hotel (A-5 and A-6): 1.50
meters
(iv) Assembly: 2.00 meters
OFFICIAL GAZETTE — GOVT. OF GOA
SERIES I No. 18
(EXTRAORDINARY No. 2)
9TH AUGUST, 2023
1740
Note: The width of stairs may be accepted
to be 1.50 meter in case of assembly
occupancy having less than 150 persons.
(v) Educational: 1.50 meters
(vi) Institutional: 2.00 meters
(vii) All other occupancies: 1.50
meters.
(f) A handrail shall be provided on one
side of the staircase of width less than 1,500
mm, and on both sides of the staircase of
width 1,500 mm and more. The projection
of handrail(s) in the staircase width shall not
be more than 115 mm.
(g) Handrails may project inside the
measured width by not more than 90 mm.
(h) The design of staircase shall also take
into account,—
(i) The minimum headroom in a
passage under the landing of a staircase
and under the staircase shall be 2.2
meters.
(ii) Access to exit staircase shall be
through a fire door of a minimum 120
minutes fire resistance rating.
(iii) Openings if any shall have a fire
rating of atleast 120 minutes. The
staircase shall be pressurized/Naturally
ventilated or cross ventilated as per
provisions of Table 6 of clause 4.4.2.5. of
Part 4 of the National Building Code of
India, 2016. For buildings having height
more than 30 meters they shall have cross
ventilation (through opposite/adjacent
walls or the same shall be ventilated
through the corridor) or pressurized.
(iv) No living space, store or other fire
risk shall open directly into staircase.
(v) The exit (including staircases) shall
be continuous from refuge floors or
terrace level, as applicable, to the level
of exit discharge.
(vi)
No
electrical
shafts/air
conditioning ducts or gas pipes, etc, shall
pass through or open in the staircases.
(vii) Lifts shall not open in staircase.
(viii)
No combustible material shall
be used for decoration/wall paneling in
the staircase.
(ix) Beams/columns and other building
features shall not reduce the head room/
width of the staircase.
(x) The floor indication board,
indicating the location/designated
number of staircase, respective floor
number and direction to exit discharge
shall be placed inside the staircase, on
the wall nearest to the fire door. It shall
be of size not less than 300 mm x 200 mm
(see Sketch No. 14.).
(xi)
Individual floors shall be
prominently indicated on the wall outside
the staircase and facing it.
(xii) All staircases shall terminate at the
level of exit discharge. The access to the
basement shall be by a separate
staircase. However, in case of separation
of stairs leading from ground (exit
discharge) to the upper floors and stairs
leading to the basement by fire protection
wall and both the stair flights are
accessible by separate entries, then
access to the basement need not be by a
separate staircase.
(xiii)
Scissors type staircases shall not
be treated as part of exit.
(III) Curved Stairs:—
Curved stairs shall not be treated as part
means of egress. However, these may be used
as part of exit access provided the depth of
tread is not less than 280 mm at a point 350
mm from the narrower end of the tread and
the smallest radius is not less than twice the
stair width.
(IV) External Staircases.— The external
staircases are the staircases provided on the
external wall/façade, which shall comply with
the following requirements, namely:—
(a) External stairs shall always be kept in
sound and usable condition.
OFFICIAL GAZETTE — GOVT. OF GOA
SERIES I No. 18
(EXTRAORDINARY No. 2)
9TH AUGUST, 2023
1741
(b) All external stairs shall be directly
connected to the ground.
(c) Entrance to the external stairs shall
be separate and remote from the internal
staircase.
(d) Where an external staircase is
provided, it shall be ensured that the use of
it at the time of fire is not prejudiced by
smoke and flame from openings (for
example, windows, doors) in the external
face of the building. Care shall be taken to
ensure that no external wall or window
opening opens on to or close to an external
stair. If such openings exists within 3
meters from an external staircase, they shall
be protected with fire rated doors/window
assemblies with rating of at least 60
minutes.
(e) The external stairs shall be
constructed of non-combustible materials,
and any doorway leading to it shall have
minimum 120 minutes fire resistance.
(f)The light and ventilation for the
staircase shall be provided from an external
wall by providing openings of not less than
1/10th of the area of the staircase and such
openings shall be provided at each landing
stage. The openings shall have a fire rating
of atleast 120 minutes.
(g) No external staircase flight of steps
shall be inclined at an angle greater than
45 degrees from the horizontal.
(h) External stairs shall have straight
flight not less than 1,500 mm wide.
(i)Handrails, to be provided on both sides,
shall be of a height not less than 1,000 mm
and not exceeding 1,200 mm. There shall
be provisions of balusters with maximum
gap of 150 mm.
(V) Spiral Stairs:— The use of spiral
staircase shall be limited to low occupant load
and to a building not exceeding 9 m in height.
A spiral staircase shall be not less than 1,500
mm in diameter and shall be designated to
give adequate headroom.
15.9.10. Ramps:— (a) In addition to the
provisions contained in clause 6 of Part 4 of
the National Building Code of India, 2016,
ramps shall comply with all the applicable
requirements for staircases regarding
enclosure, capacity (see Table XXII as specified
in regulation 15.9.5) and limiting dimensions.
(b) The slope of a ramp shall not exceed 1
in 12 (8 percent).
(c) Ramps shall be surfaced with approved
slip resistant materials that are securely
attached. No perforations are permissible on
the ramp floors.
(d) Any changes in travel direction in ramp
shall be preceded by landings of 1.5 meters x
1.5 meters size.
(e) Ramps and intermediate landings shall
continue with no decrease in width along the
direction of egress travel.
(f) Outside ramps and landings shall be
designed to minimize water accumulation on
their surfaces.
(g) Ramps shall have landings located at the
top, at the bottom, and at doors opening onto
the ramp.
(h) Every landing shall be not less than 1,500
mm long in the direction of travel.
(i) Where the ramp is not part of an
accessible route, the ramp landings shall not
be required to exceed 1,250 mm in the
direction of travel, provided that the ramp has
a straight run.
(j) Handrails shall be provided on all ramps
on both sides (see regulation 15.9.9 (IV) (i)).
(k) The minimum width of vehicular ramp
to basement shall be 3.60m wide, atleast two
ramps shall be provided, located preferably
at opposite ends and the maximum gradient
of vehicular ramp shall be 1 in 8 (12.5%).
Note: Above requirements at (a) to (j) shall
not be applicable to basement car parking
ramps.
15.10. Fixed Fire Fighting Installations.—
These shall be provided in all buildings
depending upon the occupancy use and
height in accordance with the provisions of
clause 5 of Part 4 of the National Building Code
of India, 2016.
OFFICIAL GAZETTE — GOVT. OF GOA
SERIES I No. 18
(EXTRAORDINARY No. 2)
9TH AUGUST, 2023
1742
15.11.
Miscellaneous.—
Wherever
applicable, Lightning protection of buildings,
Compartmentation, Smoke Control, and
Additional Occupancy Wise Requirements
shall be as per clause 3.4.6.5, 4.5, 4.6 and 6 of
Part 4 of the National Building Code of India,
2016. Fire Requirements for Basement and
Building Services shall be as per Annexure-
III, 27.III. Lightning Protection shall be
required for buildings specified in regulation
15.2.1 and also for buildings having Ground
or Stilt + 2 floors or more, or for buildings
having height 9 meters and above when
measured from adjoining Ground. Lightning
protection of building shall be installed to the
satisfaction of the Electricity Department.”.
9. Substitution of regulation 16.— For
regulation 16 of the principal Regulations, the
following regulation shall be substituted,
namely:—
“16. Facilities for the Persons with
Disabilities and elderly persons.—
16.1. All buildings and recreational
spaces including beaches under the
occupancies listed below at (i) to (vii) which
have access to the public, shall be provided
with facilities for persons with disabilities
and elderly persons.
(i) Assembly Building.
(ii) Business/commercial/office building/
/mercantile building.
(iii) Educational buildings.
(iv) Industrial buildings (Arrangement for
employees with disabilities are directly
related to the type of work they perform.
Arrangement for persons with disabilities
need not be considered in heavy
manufacturing Industry. Arrangement for
all persons with disabilities should be
incorporated into the design of new light
manufacturing factories where persons
with disabilities may be employed).
(v) Institutional buildings.
(vi) Residential buildings with 24 dwelling
units and more or having 2,000 sq. mts. of
built up area and more, at least 20% of the
number of units shall comply with the space
standards and facilities as per the
Harmonised Guidelines and Space
Standards for Barrier Free Built Environment
for Persons with Disability and Elderly
Persons.
(vii) Recreational (Playground, parks,
gardens and beaches).
16.2. The above occupancies shall provide
the following facilities, namely:—
(1) Every such building shall have easy
access to the main entrance through a ramp
with railing on both the sides as specified
in clause (3).
(2) Every such building shall have a lift
or separate approach through a ramp
intended for persons with disabilities to
each floor, provided that, the entrance door
width for such lift shall not be less than 90
cm and its minimum size should be 1500
mm wide by 1500 mm deep; wherever
possible 13 passenger lift to be provided,
which allows easy maneuverability of
wheel chair user, also the lift should have
Braille marking on buttons inside and
outside on the panels. It should have audio
announcement, the lift should have railing
on all three sides. In case lifts are provided
with touch screen panel, there should be
additional panel with physical button
having Braille marking.
(3) The maximum gradient of any ramp
approach intended for the persons with
disabilities shall not exceed 1 in 12 (for
details refer clause 7.2.2 of Harmonised
Guidelines and Space Standards for Barrier
Free Built Environment for Persons with
Disability and Elderly Persons) and shall be
finished with non-slippery material. The
minimum clear width of ramp shall be 120
cm. and provided with handrails on both
sides at 80 cm. height. The slope of all such
ramps shall be constant within a building
as far as possible. The ramp also should
carry tactile tiles as prescribed in the said
Harmonised guidelines.
(4) Entrance Landing: Entrance landing
shall be provided adjacent to ramp with the
minimum dimension 1800mm x 2000mm.
OFFICIAL GAZETTE — GOVT. OF GOA
SERIES I No. 18
(EXTRAORDINARY No. 2)
9TH AUGUST, 2023
1743
The entrance landing that adjoins the top
end of a slope shall be provided with floor
materials to attract the attention of visually
impaired person’s (limited to coloured floor
material whose colour and brightness is
conspicuously different from that of the
surrounding floor material or the material
that emits different sound to guide visually
impaired persons. Finishes shall have a non-
slip surface with a texture traversable by a
wheel chair. Kerbs wherever provided
should blend to a common level.
(5) Corridor connecting the entrance/exit
for persons with disabilities:— The corridor
connecting the entrance/exit for persons
with disabilities leading directly outdoors
to a place where information concerning the
overall use of the specified building can be
provided to visually impaired persons either
by a person or by signs, shall be provided
as follows:—
(a) Guiding floor materials’ shall be
provided or device that emits sound to guide
visually impaired persons should be
installed.
(b) The minimum width shall be 1500mm.
(c) In case there is a difference of level,
slope ways shall be provided with maximum
slope of 1:12.
(d) Handrails shall be provided for ramps/
slope ways on both the sides of stair-ways.
(6) Stair-ways:— One of the stair-ways– near
the entrance/exit for the persons with
disabilities shall have the following
provisions:—
(a) The minimum width shall be 1350 mm.
(b) Height of the riser shall not be more
than 150 mm and width of the tread 300mm.
The steps shall not have abrupt (square)
nosing.
(c) Maximum number of risers on a flight
shall be limited to 12.
(d) Handrails shall be provided on both
sides and shall extend 300 mm on the top
and bottom of each flight of steps.
(7) Toilets General:
(7) (a) In all public buildings, one unisex
accessible toilet should be provided in each
toilet block in each floor. Apart from this all
toilet blocks must have one cubicle suitable
for use by persons with ambulatory
disabilities.
Note: (1) For small office buildings where the
floor area limits the provision of accessible
washrooms/toilets on each floor, one unisex
accessible washroom on ground level shall be
provided to serve the entire building. The
unisex accessible washroom/toilet should be
located adjacent to an accessible elevator.
Note: (2) Where an office building is sub-
divided among various tenants, unisex
accessible washroom/toilet should be
provided on each floor.
(7) (b) The unisex toilet should have:—
(i) The minimum size shall be 2200mm x
2000mm.
(ii) Minimum clear opening of the door
shall be 900mm and the door shall open
outward or have two way opening door or
a sliding type with a sliding/horizontal pull
bar at least 600mm long.
(iii) The layout of the fixtures in the toilet
should be such that there is a clear
maneuvering space of 1800mm x 1800mm
in front of water closet and wash basin in
the accessible toilet unit.
(iv) Centre of WC shall be located at a
distance of 460mm to 480mm from the
adjacent wall.
(v) There should be an adequate clear
floor space of atleast 1350mm depth and
900mm width both in front and on the
transfer side, adjacent to water closet.
(vi) Suitable arrangement of vertical/
horizontal handrails with atleast 50mm
clearance from wall shall be made in toilet.
(vii) The top of WC seat shall be 450-
480mm from the floor.
(viii) At least one sink (washbasin) in each
floor shall have a knee room of 70 cms high
under the sink and
OFFICIAL GAZETTE — GOVT. OF GOA
SERIES I No. 18
(EXTRAORDINARY No. 2)
9TH AUGUST, 2023
1744
(ix) Locks if any, of such toilet doors shall
be of a type that can be opened from outside
in case of emergency.
(7) (c) One special W. C. at each floor in a
set of toilets shall be provided for the use of
persons with disabilities with essential
provision of washbasin near the entrance for
the persons with disabilities.
(i) The minimum size shall be 900 x 2000
mm.
(ii) Minimum clear opening of the door
shall be 900 mm and the door shall open
outward or have two way opening door or
a sliding type with a sliding/horizontal pull
bar at least 600mm long.
(iii) Suitable arrangement of vertical/
/horizontal handrails with minimum 50mm
clearance from wall shall be made in the
toilet.
(iv) The top of W.C. seat shall be 450-
480mm from the floor.
(v) At least one sink (washbasin) in each
floor shall have a knee room of 70 cms high
under the sink and 900mm width both in
front and on the transfer side, adjacent to
water closet.
(vi) Locks if any, of such toilet doors shall
be of a type that can be opened from outside
in case of emergency.
(8) Parking facilities:—
(a) Two accessible parking lot should be
provided for every 25 car parking spaces
or part thereof exclusively for persons with
disabilities with maximum travel distance
of 30 meters from the building entrance.
(b) The width of such parking bay shall
be minimum of 3.6 meters.
Specific sign boards should be available for
notifying reserve parking for persons with
disabilities in all building structures/
recreational spaces specified in regulation
16.1.
(9) Walks and paths:—
(a) Walks shall be smooth with hard level
surface suitable for walking and wheeling.
Avoid grates and manholes in walks. If
grates cannot be avoided, then bearing bar
shall be perpendicular to the travel path and
opening between bars shall not be greater
than 12 mm. in width.
(b) The walkway shall not cross vehicular
traffic.
(10) Other Special Treatments:—
(a) All obstructions and projections up to
a minimum of 2.1 metre height from the
finished floor level shall be avoided.
(b) Recoil doors shall be avoided,
wherever there is access to the general
public
(c) Appropriate signages shall be
provided at salient locations for facilitating
the persons with disabilities. Graphical and
simple, prominent signage as per standard
requirements of colour and contrast should
be provided.
(d) In the buildings meant for the
predominant use of the children, it will be
necessary to suitably alter the height of the
handrail and other fittings and fixture etc.
Note: Whatever not specifically specified
in these regulations shall be as per
Harmonised Guidelines and Space
Standards for Barrier Free Environment for
Persons with Disability and Elderly Persons
as issued by the Government of India and
as amended from time to time.”.
10. Substitution of Annexure-III.— For
Annexure-III of the principal regulations, the
following Annexure shall be substituted,
namely:—
“ANNEXURE-III
27.III.
1. Lift:— The requirements for lift shall be as per
provisions of section 5 of Part 8 of the National
Building Code of India, 2016.
2. Fire Lift:— The requirements for fire lift shall be
as per provisions of section 5 of Part 8 of the National
Building Code of India, 2016.
3. Basement:— As provided under Annexure-VI at
27.VI.
3.1 Requirements:— (a) Basement exits shall be
sufficient to provide for the capacity of the
basement as determined in accordance with
OFFICIAL GAZETTE — GOVT. OF GOA
SERIES I No. 18
(EXTRAORDINARY No. 2)
9TH AUGUST, 2023
1745
15.9.3. In no case there shall be less than two
independent basement exits.
(b) Basements having incidental occupancies
to main occupancy shall be planned with exit
requirements of the basements for the actual
occupancy within the basement.
(c) Where basement is used for car parking and
also there is direct approach from any occupancy
above to the basement, door openings leading to
the basement shall need to be protected with fire
doors with 120 min fire rating, except for exit
discharge doors from the basement.
(d) The basement shall be partitioned and in
no case compartment shall be more than 500 sq.
m. and less than 50 sq. m. area except parking.
Each compartment shall have ventilation
standards as laiddown in Regulations separately
and independently. The partition shall be made
in consultation with the Director, Directorate of
Fire and Emergency Services.
(e) The first basement (immediately below
ground level) can be used for services/parking/
other permissible services. Lower basement, if
provided, shall exclusively be used for car parking
only.
(f) Each basement shall be separately
ventilated. Vents with cross-sectional area
(aggregate) not less than 2.5 percent of the floor
area spread evenly round the perimeter of the
basement shall be provided in the form of grills or
breakable starboard lights or pavement lights or
by way of shafts. Alternatively a system of air
inlets shall be provided at basement floor level
and smoke outlets at basement ceiling level. Inlets
and extracts may be terminated at ground level
with starboard or pavement lights as before. But
ducts to convey fresh air to the basement floor
level have to be laid. Starboard and pavement
lights should be in positions easily accessible to
the firemen and clearly marked “SMOKE
OUTLET” or AIR INLET” with an indication of area
served at or near the opening.
(g) The staircase of basement shall be of
enclosed type having fire resistance of not less
than two hours and shall be situated at the
periphery of the basement to be entered at
ground level only from the open air and in such
positions that smoke from any fire in the basement
shall not obstruct any exit serving the ground and
upper storeys of the building and shall
communicate with basement through a lobby
provided with fire resisting self closing door of
one hour rating. In case of basement being used
as car parking only, the travel distance shall be
45 meters.
(h) In multi-storeyed basements, intake duct
may serve all basements levels, but each
basement and basement compartment shall have
separate smoke outlet duct or ducts. Mechanical
extractors for smoke venting system from lower
basement levels shall also be provided. The
system shall be of such design as to operate on
actuation of smoke, heat sensitive detectors/
/sprinklers, if installed, and shall have a
considerably superior performance compared to
the standard units. It shall also have an
arrangement to start it manually.
(i) Mechanical extractors shall have an internal
locking arrangement so that extractors shall
continue to operate and supply fans shall stop
automatically with the actuation of fire detectors.
Mechanical extractors shall be designed to permit
12 air changes per hour in case of fire or distress
call. However, for normal operation, only 12 air
changes or any other convenient factor can be
maintained. (i) Mechanical extractors shall have
an alternate source of power supply.
(j) Ventilating ducts shall be integrated with
the structure and made out of brick masonry or
RCC as far as possible and when this duct crosses
the transformer area of electrical switchboard, fire
dampers shall be provided.
(k) Kitchens working on gas fuel shall not be
permitted in basement/sub-basement.
(l) If cutouts are provided from basement to the
upper floors or to the atmosphere, all side cutout
openings in the basements shall be protected by
sprinkler heads at closed spacing so as to form a
water curtain in the event of a fire.
(m) Dewatering pump shall be provided in all
basements.
(n) Additional provisions shall apply to parking
structures of the closed or open type, within
buildings above or below grade as per Annex H
of Part 4 of the National Building Code of India,
2016.
4. All high-rise buildings having height above 200
meters shall have provision for a Helipad on the
terrace for specific requirements like landing of fire
equipment and support facilities or other
emergencies. The same shall be subject to approval
of the Airport Authority and Structural Safety from
Indian Institute of Technology/National Institute of
Technology.
5. Service Ducts/Refuse Chute:— Service Ducts/
Refuse Chute shall be as per Clauses 3.4.5.4 and
3.4.5.5 of Part 4 of the National Building Code of India,
2016.
OFFICIAL GAZETTE — GOVT. OF GOA
SERIES I No. 18
(EXTRAORDINARY No. 2)
9TH AUGUST, 2023
1746
6. Electrical Services:— Electrical Services shall be as per Clause 3.4.6 to Clause 3.4.6.2 of Part 4 of the
National Building Code of India.
7. Staircase and Corridor Lights:— The staircase and corridor lighting shall be as per Clause 3.4.7 to 3.4.7.2
of Part 4 of the National Building Code of India, 2016.
8. Air-Conditioning:— Air-conditioning shall be as per Clause 3.4.8 to 3.4.9 of Part 4 of the National
Building Code of India, 2016.
9. Fire Dampers:— Fire Dampers shall be as per Clause 3.4.8.4 of Part 4 of the National Building Code of
India, 2016.
10. Boiler Rooms:— Boiler Rooms shall be as per Clause 3.4.9.2 of Part 4 of the National Building Code of
India, 2016.
11. Alternate Source of Electric Supply:— Alternate Source of Electric Supply shall be as per Clause 3.4.6.4
of Part 4 of the National Building Code of India, 2016.
12. Safety Measures in Electric Sub-Station:— Safety Measures in Electric Sub-Station shall be as per
Clause 3.4.6.3 to 3.4.6.3.2 of Part 4 of the National Building Code of India, 2016.
13. Control room:— Control room/Fire Command Centre shall be as per Clause 3.4.12 of Part 4 of the
National Building Code of India, 2016.”.
11. Amendment of Annexure-IV, 27.IV.— The ANNEXURE-IV, 27.IV of the principal Regulations
shall be omitted.
12. Amendment of Annexure-VI, 27.VI.— In Annexure VI, 27.VI of the principal Regulations
in clause (2),—
(i) for sub-clause (j), the following clause, shall be substituted, namely,
“(j) Fire and Safety requirements as applicable to each basement floor shall be as per
Annexure-III, regulation 27.III.”;
(ii) sub-clause (k) shall be omitted.
13. Amendment of Annexure-VII, 27.VII.— In Annexure VII, 27.VII of the principal Regulations,
in clause 7.3, in sub-clause (c), for the words “Chief Fire Officer”, the expression “Director,
Directorate of Fire and Emergency Services” shall be substituted.
14. Insertion of Sketches.— After Sketch No. 7 of the principal Regulations, the following
sketches shall be inserted, namely:—
“Sketch No. 8. A Door Location at Landing in Fire Exits
(see Regulation 15.9.2 (h))
Minimum Required Unobstructed Clearance with Door Leaf Encroaching on Landing In
Institutional and Assembly Buildings
OFFICIAL GAZETTE — GOVT. OF GOA
SERIES I No. 18
(EXTRAORDINARY No. 2)
9TH AUGUST, 2023
1747
Sketch No. 8B. Door location at Landing in Fire Exists (See Regulation 15.9.2 (h))
Minimum Required Unobstructed Clearance with Door Leaf Encroaching On Landing
Sketch No. 9. Minimum Head Room Measurement
(See Regulation 15.9.2 (j))
Sketch No. 10. Display Board Regarding Maximum Occupancy
(See Regulation 15.8.4)
OFFICIAL GAZETTE — GOVT. OF GOA
SERIES I No. 18
(EXTRAORDINARY No. 2)
9TH AUGUST, 2023
1748
Sketch No. 11. Dead End Corridor
(See Regulation 15.9.4 (c)
Sketch No. 12. Unacceptable Arrangement for Enclosing a
Stair Serving as Required Exit
(See Regulation 15.9.7 (a))
Sketch No. 13. Minimum Clear Door Width
(See Regulation 15.9.7 (b))
OFFICIAL GAZETTE — GOVT. OF GOA
SERIES I No. 18
(EXTRAORDINARY No. 2)
9TH AUGUST, 2023
1749
Sketch No. 14. Floor indication Board
(See Regulation 15.11)
14a. Example of a Stairway Marking Sign (Floor Indication Board)
14b. Stair Sign Placement
By order and in the name of the Governor of Goa.
Vertika Dagur, Chief Town Planner (Land Use) & ex officio Joint Secretary.
Panaji, 09th August, 2023.
OFFICIAL GAZETTE — GOVT. OF GOA
SERIES I No. 18
(EXTRAORDINARY No. 2)
9TH AUGUST, 2023
1750
Notification
21/1/TCP/2021-23/Steering Committee/106
Whereas, the draft regulations, namely, the
Goa Land Development and Building
Construction (Amendment) Regulations, 2023
which the Government of Goa proposed to
make in exercise of the powers conferred by
sub-sections (1) and (2) of section 4 of the
Goa (Regulation of Land Development and
Building Construction) Act, 2008 (Goa Act 6
of 2008) (hereinafter referred to as the “said
Act”) so as to further amend the Goa Land
Development and Building Construction
Regulations, 2010, were pre-published as
required by section 5 of the said Act vide the
Government Notification No. 21/1/TCP(A)/
2021/Steering
Committee/675
dated
19-04-2023, published in the Official Gazette,
Series I No. 4 dated 27-04-2023, read with
Corrigendum No. 21/1/TCP(A)/2021/Steering
Committee/747 dated 03-05-2023, published
in the Official Gazette, Series I No. 5 dated
04-05-2023
inviting
objections
and
suggestions from all persons likely to be
affected thereby within 30 days from the date
of publication of the said Notification in the
Official Gazette;
And whereas, the said Notification and
Corrigendum were published in the Official
Gazettes and were made available to the
public on 27-04-2023 and 04-05-2023,
respectively;
And whereas, objections and suggestions
received from the public on the said draft
Regulations have been considered by the
Sub-Committee appointed under sub-section
(2) of section 6 of the said Act and submitted
its report to the Steering Committee
constituted under sub-section (1) of section 6
of the said Act vide the Government
Notification No. 21/1/TCP/2018/SC/481 dated
22-02-2018, published in the Official Gazette,
Series II No. 48 dated 01-03-2018;
And whereas, the Steering Committee after
considering the report of the Sub-Committee
submitted
its
report
together
with
recommendation to the Government;
And whereas, the Government has
considered the report and recommendations
of the Steering Committee and approved the
same and directed the Chief Town Planner
(Land Use) to notify the Amendment
Regulations in the Official Gazette.
Now, therefore, in exercise of the powers
conferred by sub-sections (1) and (2) of
section 4 of the Goa (Regulation of Land
Development and Building Construction) Act,
2008 (Goa Act 6 of 2008) and all other powers
enabling it in this behalf, the Government of
Goa hereby makes the following regulations
so as to further amend the Goa Land
Development and Building Construction
Regulations, 2010, namely:—
1. Short title and commencement.— (1)
These regulations may be called the Goa
Land Development and Building Construction
(Amendment) Regulations, 2023.
(2) They shall come into force on the date
of their publication in the Official Gazette.
2. Amendment of regulation 2.— In
regulation 2 of the Goa Land Development
and Building Construction Regulations, 2010
(hereinafter referred to as the “principal
Regulations”),—
(i) in clause (52), after the word
“established”, the expression “and having
work experience atleast for a period of two
years under an Engineer/Structural
Engineer registered with the Town and
Country Planning Department or any local
authority. This experience shall only be
applicable to fresh pass out Graduate
Engineers only who have completed their
graduation within 05 years from the date
of application for registration and also
Experience certificate shall be to the
satisfaction of the registering authority”
shall be inserted;
(ii) in clause (52A), for the expression “3
years”, the expression “5 years” shall be
substituted;
OFFICIAL GAZETTE — GOVT. OF GOA
SERIES I No. 18
(EXTRAORDINARY No. 2)
9TH AUGUST, 2023
1751
(iii) in clause (52B), for the words “two
years”, the words “five years” shall be
substituted.
3. Amendment of regulation 6A.3.1.— In
regulation
6A.3.1
of
the
principal
Regulations,—
(i) in clause (e), for the expression
“housing”, “10,000 sq. mts” and “2.50%”
the expressions “accommodation for
staff”,”5,000 m2” and “7.5%” shall be
respectively substituted;
(ii) in clause (i),—
(a) the existing paragraphs shall be
numbered as (i) and (ii) respectively and
after the paragraphs so numbered, the
following paragraphs shall be inserted,
namely:—
“(iii) Uses such as Agricultural
Research Centre/development centre/
Agricultural Educational Institute/
Educational Institute/Bio-Technology unit
shall be permitted provided that the plot
has minimum area of 2,00,000m2, the
maximum Coverage, FAR and height of
building permissible shall be 5%, 5% and
7.60m respectively.
(iv) Yoga or meditation centre shall be
permitted provided that the plot has
minimum area of 50,000m2, the
maximum Coverage, FAR and height of
building permissible shall be 5%, 5% and
7.60m respectively.”;
(b) in paragraph (ii) as so numbered,
for the word “dairy”, the expression
“dairy and processing units allied to
agro products” shall be substituted.
4. Amendment of regulation 6A.4.— In
regulation 6A.4 of the principal Regulations,—
(i) for the existing Note (4), the following
note shall be substituted, namely:—
“(4) Farm houses within A1 and A2
zones shall be permitted within
maximum permissible FAR and other
parameters as provided in Annexure–XI,
provided these lands are not classified
as “rice” (Paddy field) in Survey Records
and “forest”.”;
(ii) in Note (16), for the expression
“Further, at the time of approval of
development plans, minimum 6 meters
wide right of way should be available on
the site.”, the expression “Notwithstanding
minimum width of road in zones I-1 to I-3
and S-4/R-4 to S-1/R-1 specified in
regulation 6A.4, TABLE-VIII, the minimum
width of road requirements for buildings
shall be as per ANNEXURE-XII” shall be
substituted.
5. Amendment of regulation 10.— In
regulation 10 of the principal Regulations,
after clause (e), the following shall be
inserted namely:—
“(f) All new and renovated non-
residential buildings and other residential
buildings, Co-operative Housing Societies
and Colonies managed by Residents
Welfare Associations (RWAs), with parking
demarcated for more than 10 equivalent
car spaces (‘ECS’) shall have atleast 20% of
such ‘ECS’ to be made ‘Electric Vehicle
ready’ ECS spots with conduits installed
as per the GOA ELECTRIC MOBILITY
PROMOTION POLICY – 2021 as amended
from time to time.
Note: Independent house on single holding
shall be exempted from the above
regulation.”.
6. Amendment of regulation 12.4.—In
regulation 12.4 of the principal Regulations,
for clause (d), the following clause shall be
substituted, namely:—
“(d) The open spaces shall be used for
recreational and community purposes of
the occupants of the sub-divided plots and/
or for installations of public utilities,
provided that such installations do not
cover more than 5% of each of the open
space or they may cover by combining the
5% of each of the various existing/proposed
open space parcels within the existing/
/proposed sub-division layout and utilize
OFFICIAL GAZETTE — GOVT. OF GOA
SERIES I No. 18
(EXTRAORDINARY No. 2)
9TH AUGUST, 2023
1752
in one bigger parcel of the existing/
/proposed sub-division open space, a
minimum of 3.00 metre setback from all
edges of the plot is kept and the maximum
height of any construction is restricted to
6.00 m only. In case of water tower, the
height restriction will not be applicable.”.
7. Amendment of regulation 12.6.— In
regulation 12.6 of the principal Regulations,
in clause (b), sub-clause (iii) shall be
omitted.
8. Amendment of regulation 12.7.— In
regulation 12.7 of the principal Regulations,
in clause (a),—
(i) for sub-clause (i), the following
sub-clause shall be substituted, namely:—
“(i) The owner shall be permitted to
propose any of the following amenities
in case of proposed sub-division as well
as existing sub-division to be revised as
per the requirement like schools,
community centers, commercial centers,
sports complexes, parking lots and
charging stations, health clubs, hospital,
nursing homes, dispensary, post office,
police station, electrical sub-station, ATM
of bank, library, open market, garbage
bins/MRF, assisted living and hospice
together, senior citizen housing and
orphanage, project affected persons
housing, water supply, electric supply
installations and includes other utilities,
services and conveniences.”;
(ii) in sub-clause (iii) after the word
“unchanged”, the expression “except for
amenities mentioned at (i) above.”.
9. Amendment of regulation 22.4. (a).— In
regulation 22.4. (a) of the principal
Regulations,—
(i) the existing provision shall be
numbered as clause (a);
(ii) after clause (a) so numbered and
before the note the following clause shall
be inserted, namely:—
“(b) Regularization of unauthorized
construction having an area of more
than 500 square metres, complying with
these regulations and built before
31-12-2020
may
be
done
on
recommendation of Town and Country
Planning Department or the Planning &
Development Authority by verifying that
the construction is carried out prior to
the cutoff date i.e. 31-12-2020, period of
construction shall be ascertained based
on documents like electricity bill, water
supply bill, tax receipts and other
evidences. Compounding fee shall be six
times the normal license fee for
regularization of these structures.”.
(iii) for the existing note, the following
Note shall be substituted, namely:—
“Note: Regularization of constructions may
be considered in the conservation zones, only
with the recommendation of the Conservation
Committee. Similarly, regularization in
Coastal Regulation Zone can be considered
only after obtaining approval from the Goa
Coastal Zone Management Authority.”.
10. Amendment of regulation 22.5.— In
regulation 22.5 of the principal Regulations,—
(i) after the word “regularization”, the
expression “, whichever is higher” shall be
inserted;
(ii) the following Note shall be inserted
at the end, namely:—
“Note: In case of increase in height of
buildings upto 5% or overall shift of position
of the building without reducing the setback
requirements by more than 5% and there is
no increase in additional floor area and is
complying with regulation 13.1(b) then the
levy of compounding fee/charges as
mentioned above shall not be applicable.”.
11. Substitution of Annexure-XI.— In
Annexure–XI of the principal Regulations,—
(i) in clause 2, for the expression “5%
subject to a maximum of 500m2 per
holding. The maximum area permissible for
a farm house irrespective of the area of
plot will be 500m2.”, the expression “10%
subject to a maximum built up area of
OFFICIAL GAZETTE — GOVT. OF GOA
SERIES I No. 18
(EXTRAORDINARY No. 2)
9TH AUGUST, 2023
1753
1000m2 per holding. The maximum built up area permissible for a farm house irrespective
of the area of plot will be 1000m2 or 10% Coverage whichever is lower.” shall be substituted;
(ii) in clause 3, for the figure “5”, the figures “10” shall be substituted.
12. Substitution of Annexure-XII.— For Annexure–XII appended to the principal Regulations,
the following annexure shall be substituted, namely:—
“ANNEXURE – XII
27. XII
The requirement of minimum width of road for various residential buildings, commercial buildings
(Resort/hotels) and Industrial buildings with restrictions shall be as follows:
Minimum width of road and extent of units/floor area in respect of residential buildings
Minimum width of
No. of units
Total Maximum
existing road required
floor area of entire/
in meters.**
/all building
3 mts. or more, but public road
1 (single dwelling)
500 m2
PUBLIC ROADS
> 3 upto 4 mts.
2 units
400 m2
> 4 upto 5 mts.
4 units
600 m2
> 5 upto 6 mts.
8 units
1000 m2
6 mts. or greater
180 units
20,000 m2
8 mts. or greater
More than 180 units
> 20,000 m2
** The project proponents shall leave the road widening area as prescribed in the Regional Plan/Outline
Development Plan, and other roads not less than 6.0 mts. Most restrictive criteria among No. of units and
floor area shall be considered for fixing the minimum width of access.
Minimum width of road and extent of rooms/floor area in respect of Resorts/hotel buildings
(1)
(2)
(3)
(4)
(5)
Sl. No.
Type of Occupancy
Total floor area of the
Number of rooms
**Minimum width of existing
building in sq. mts.
road required in meters.
1
Resorts/Hotel
Up to 2000
40
6
Above 2000
More than 40
8
** The project proponents shall leave the road widening area as prescribed in the Regional Plan/Outline
Development Plan and the Resorts/Hotels shall be allowed on proposed road widths of atleast 8.0 mts.
Most restrictive criteria among No. of rooms and floor area shall be considered for fixing the minimum
width of access.
Minimum width of access and extent of floor area and number of storeys in
respect of Industrial buildings
Sl. No.
Type of Occupancy
Total floor area of the
Number of storeys
**Minimum width of
building in sq. mts.
existing road required
in meters
(1)
Small Industry
1000
2
6
(2)
Small Industry
2000
2
8
(3)
others
Any area
As per permissible
10
height in Regulations
OFFICIAL GAZETTE — GOVT. OF GOA
SERIES I No. 18
(EXTRAORDINARY No. 2)
9TH AUGUST, 2023
1754
** The project proponents shall leave the road widening area as prescribed in the Regional Plan/
Outline Development Plan and small industry buildings shall be allowed on proposed road widths of
atleast 10.0 mts. Most restrictive criteria among number of storeys and floor area shall be considered for
fixing the minimum width of access.
Note: Small scale industrial unit means an industrial unit carrying on small scale industry classified by
Government from time to time for this purpose, but does not include an industry included in first schedule
of the Factories Act, 1948.”.
By order and in the name of the Governor of Goa.
Vertika Dagur, Chief Town Planner (Land Use) & ex officio Joint Secretary.
Panaji, 9th August, 2023.
_____
Notification
21/1/TCP/2021-23/Steering Committee/107
In exercise of the powers conferred by sub-sections (1) and (2) of section 4 read with
sub-section (1) of section 5 of the Goa (Regulation of Land Development and Building
Construction) Act, 2008 (Goa Act 6 of 2008) and all other powers enabling it in this behalf,
the Government of Goa hereby makes the following regulations so as to further amend the
Goa Land Development and Building Construction Regulations, 2010, namely:—
1. Short title and commencement.— (1) These regulations may be called the Goa Land
Development and Building Construction (Amendment) Regulations, 2023.
(2) They shall come into force on the date of their publication in the Official Gazette.
2. Amendment of regulation 4.11.— In regulation 4.11 of the Goa Land Development and
Building Construction Regulations, 2010 (hereinafter referred to as the principal Regulations),
in clause (d), for the expression “Authority/Council/Panchayat”, the expression “Authority/
Council/Panchayat/Town and Country Planning Department” shall be substituted.
3. Amendment of regulation 6.1.1.— In regulation 6.1.1 of the principal Regulations, in
clause (a),—
(i) in the TABLE-V, the following entries shall be omitted, namely:—
“VP1
Area 4000m2 & above
60
As per S2/R2
VP2
Area 4000m2 & above
50
9.00 mts. including stilt”;
(ii) the existing note shall be numbered as (1) and after the note (1) so numbered, the
following note shall be inserted, namely:—
“(2) The Government on recommendation of the Town and Country Planning Board
shall grant additional height and FAR to the proposals on case to case basis in
consideration of the locational aspect, nature of development, use proposed, information
available and on any such other criteria, if required. Such relaxation shall however not
be relaxed for more than 20% permitted in the prevailing Regulations.”.
4. Amendment of regulation 6A.4.— In regulation 6A.4 of the principal Regulations,—
(i) in the TABLE – VIII,—
(a) for the entry “SPR (Special Residential)
10.00m
40%
200
3 .0 0m
24.00m”, the entry “SPR (Special Residential)
10.00m
40%
200
3 .0 0m
28.00m” shall be substituted;
OFFICIAL GAZETTE — GOVT. OF GOA
SERIES I No. 18
(EXTRAORDINARY No. 2)
9TH AUGUST, 2023
1755
(b) for the entry “CS 10.00m 40%
250
10.00m 28.00m”, the entry “CS
10.00m 40% 250 10.00m 32.00m” shall be substituted;
(c) for the entry “SPC (Special Commercial) 10.00m 40% 300 10.00m 32.00m”,
the entry “SPC (Special Commercial) 10.00m 40% 300 10.00m 40.00m” shall
be substituted;
(ii) in the existing Note (20),—
(a) for the figures “20%”, the figures “30%” shall be substituted;
(b) after the expression “Annexure XIII”, the expression “No additional FAR, if provided
under any other regulations shall be applicable/availed by the project proponent, whoever
has availed of this 30% FAR, other than which is already available under floor area” shall
be inserted;
(iii) after Note (26), the following notes shall be inserted, namely:—
“(27) Permissions/clearances in zones SPR (Special Residential), CS and SPC (Special
Commercial) shall be subject to approval of the Government and fulfillment of the
requirement of fire safety by Directorate of Fire and Emergency Services.
(28) Incentives for Indian Green Building Council (IGBC) Certified Green Building: An
additional FAR of 10% may be granted with the approval of the Government, for Green
Building projects which will be pre-certified/provisionally certified by IGBC. All such
project proponents availing this additional FAR shall be issued Completion Certificate
with the approval of the Government post certification by IGBC and this IGBC Certification
shall be renewed every 5 years by IGBC.”.
5. Amendment of regulation 12.8.— The regulation 12.8 of the principal Regulations shall
be omitted.
6. Insertion of regulation 14.3.4.— After regulation 14.3.3 of the principal Regulations, the
following regulation shall be inserted, namely:—
“14.3.4. In Building Solutions for Common Telecommunication Infrastructure (CTI):
A. Multi dwelling units, commercial complexes, public buildings and Transport facilities:
1. New building constructions shall have to properly demarcate section (area) within
buildings and on roof tops for installing broadband/digital connectivity infrastructure/antenna.
These areas should have access to power supply for reliable, un-interrupted services.
2. Provisions of In-building Solutions (IBS) components in building premises:
(a) Entrance facilities (EF)/lead-in conduits: Minimum 1.2m x 1.83m space to be allocated
for each Telecom Service provider adjacent to the EF, if a separate space is required for
service providers.
Underground conduits/pipes to Main Distribution Frame room shall be through min
100 mm dia encased conduits.
(b) Main Distribution Frame (MDF)/Equipment Room: The minimum recommended size
for ER is 14m2 with L:W ratio between 1:1 to 2:1, with proper lighting for vision of equipments
and ventilation of room. This room shall be located at a level above from the Natural
Ground Level to avoid incidence of flooding. Necessary Electric distribution panels, isolaters,
sockets and earthing shall be provided as per specific requirements.
OFFICIAL GAZETTE — GOVT. OF GOA
SERIES I No. 18
(EXTRAORDINARY No. 2)
9TH AUGUST, 2023
1756
(c) Telecommunications Room (TR): at each building block unless provided with MDF
Room with appropriate numbers and size (length x width) of Service/Telecom risers (vertical
shafts) for all multi-storeyed buildings w.r.t. the area proposed for Coverage (DUs/service
subscribers) with access door at each floor.
(d) Telecommunications Enclosures (TE): at each floor of a block or TR.
(e) (i) Telecom room space norm for buildings with built-up area (floor space) greater
than 465 sq. mts.
Sl.No.
Area* to be covered by IBS
Size of Telecom Room (all dimension in m)
1
Upto 465 sqmt
3.0 x 2.4
2
465.0 sqmt to 930.0 sqmt
3.0 x 3.4
3
More than 930.0 sqmt
Additional TR required with same space rooms
* usable floor space to be served.
(ii) Space requirements for smaller buildings with built-up area less than 465 sq. mts.
Sl.No.
Area to be covered by IBS
Space provisions (all dimensions in m)
1
Upto 93.0 sqmt
Wall cabinets, self-contained enclosed
cabinets
2
93.0 sqmt to 465.0 sqmt
Shallow Room (0.6 x 2.6)
Walk-in Room (1.3 x 1.3)
3. For the purpose of floor area calculation, the above said room area(s) of IBS components
in building premises shall be exempted as per sub regulation (63) (k) of regulation 2.
4. Occupancy certificate/Completion Order to a building shall be granted only after ensuring
that an undertaking is given by the Architect or Engineer or other professional who is
competent to submit application for issue of completion order/occupancy certificate under
GLDBCR-2010 certifying that building has ensured common access to all digital infrastructure
to all service provider at building level and in-building components are in accordance with
plan of creation of CTI.
B. At layout level (sub-division): (1) Layout plans should clearly indicate the telecom as
utility infrastructure lines. Telecommunication cables should be placed in a duct/pipe that
can be accessed at frequent service points with sufficient spare capacity to enable scaling
and future expansion and empty popes (large size hume popes/HDPE pipes) should be laid
before planting trees in order to accommodate additional infrastructure.
(2) Telecommunication cables should ideally be placed below the parking area or service
lane. Where this is not possible, the cables may be placed at the outer edge of the right-of-
way. Telecom boxes if required, should be placed after leaving 2m space for pedestrian path
(foot path).
(3) Final NOC for sub-division shall be granted after ensuing that an undertaking is given
by the Architect or Engineer or other Professional who is competent to submit application for
issue of NOC for sub-division under GLDBCR-2010 certifying that the layout has all the
Telecommunication cables to service provider in accordance with plan of CTI.
(4) For any other necessary detailing of building components and service installations with
respect to common Telecom/Digital Connectivity Infrastructure architects/engineers/planners/
/other professionals may be advised to refer the above said Addendum to Model Building
OFFICIAL GAZETTE — GOVT. OF GOA
SERIES I No. 18
(EXTRAORDINARY No. 2)
9TH AUGUST, 2023
1757
Bye-laws/Part 8–Section 6: Information and Communication Enabled Installations of Volume
2 of the National Building Code, 2016”.
7. Amendment of Annexure–XIII.— In Annexure–XIII of the principal Regulations, for the
figures “20%, wherever they occur, the figures “30%” shall be substituted.
By order and in the name of the Governor of Goa.
Vertika Dagur, Chief Town Planner (Land Use) & ex officio Joint Secretary.
Panaji, 9th August, 2023.